IQ4E/.. Installation Instructions - Mounting TG201338 Issue 4, 19-Jan-2016. Applies to v3.33.

IQ4E/.. 

Installation Instructions - Mounting

3 INsTAllATIoN 

(continued)

13

Connect to xNC Interface 

(../XNC variants only, if required)

Earthing (Grounding) & Isolation Requirements

If the IQ4E and other units on the bus are in the same cabinet 

using the same power supply, each device must have a good 

physical earth (ground) connection.

If the IQ4E and other units on the bus are in different cabinets 

or use different power supplies (e.g. different UPS units), the 

cabinets must be isolated from each other. 

If the bus is likely to suffer from surge and grounding problems, 

surge  protection  should  be  added.  The  isolator  should  be 

connected to the earth (ground) of the nearest device, the 0V 

of the isolator and the surge protector should be connected 

together, and earth (ground) of the surge protector’s exposed 

side  (e.g.  backbone  bus)  should  be  connected  as  directly 

as possible to the surge ground or earth bond. Ensure that 

terminators are fitted where indicated.

Connect  using  either  the  RS-485  Port,  RS-232  Port  (local 

supervisor) or Ethernet Port.

RS-232 Port (local supervisor)

RS-485 Port

Ethernet Port (see step 7) 

Rs-485 2-wire system

Note: For connection to an RS-485 4-wire system a suitable 

2- to 4-wire converter will be required.

Rs-232 system

RJ12 / FFC68

Plug

Local 

Supervisor 

Port

1 - RX
2 - NC
3 - CTS
4 - RTS
5 - GND
6 - TX

TX

RX

RT

S

CT

S

G

ND

pin 1

Note: CTS and RTS connections may be connected differently 

or not used - check the device data/installation sheet.

Note: When in use for XNC the local supervisor port cannot 

be used to connect supervisory tools or devices.

Cabinet B

Backbone Bus

IQ4

Cabinet A

to more cabinets terminate at far end

Surge 

Ground 

or Earth 

Bond

Isolating 

Repeater

Isolating 

Repeater

Surge Ground 

or Earth Bond

Surge 

Protection

Surge 

Protection

terminate 

at far end

to other devices

0V

0V

A

A

B

B

0V

A

B

0V

A

T

T

B

0V

A

B

0V

A

B

0V

A

B

0V

A

T

B

0V

A

B

RS-485

82

83

Terminal size: 

0.14 to 2.5 mm

2

 (22 to 12 AWG). 

Terminal screw torque: 0.45 to 0.62 Nm (4 to 5.5 lb.in).

Number of Devices: 

up to 32

0V

A B

0V

A B

RS-485

82

83

Bias switch ON

120 Ohm 

terminator

Terminator 

switch ON

Terminators: 

The bus must be terminated at each end with 

a resistor matched to the cable characteristic impedance (i.e. 

±1%, ¼ Watt, range 100 to 130 ohms). If the IQ4E is at one end 

of a 120 ohm cable, switch in its built-in terminator, otherwise 

switch it out and fit a resistor at that end of the cable; the other 

end must be terminated with a matching resistor.

Bias: 

It is recommend that bias is applied at one location. The 

IQ4E can be used to apply bias using its bias switch.

Содержание IQ4E

Страница 1: ...reinforced insulation 3 Installation 1 Box Contents 2 Storing Contents 1 Box Contents 1 2 Storing 1 3 Installation 1 Note For temperatures below 0 C 32 F special care must be taken that there is no co...

Страница 2: ...tinued Must be installed in an enclosure rated to at least IP20 or equivalent Note For temperatures below 0 C 32 F special care must be taken that there is no condensation on or within the unit Protec...

Страница 3: ...structions Mounting IQ4E 3 Mount Unit on DIN Rail 4 Attach large Barcode label to Panel 5 open Rotating Covers 3 INsTAllATIoN continued I QECO Q3 B_ X7 3 0 8 0 0 3 1 SERIAL No IQ4e Q3B_X73080031 TREND...

Страница 4: ...0 C or greater This equipment must be earthed grounded 230 230 Vac 10 50 60 Hz at up to 70 VA The 230 V supply must include a dedicated 5 A fuse complying with IEC60269 BS1362 and a suitably rated swi...

Страница 5: ...5 lb in TP 1 1 22 HF 200 Belden 8761 cable recommended for all inputs outputs Screened cable is not generally required unless the cable passes through electrically noisy environments Where it is used...

Страница 6: ...equired 11 Connect Auxiliary Supply Output s if required 3 Installation continued Output voltage 0 to 10 Vdc Maximum current 20 mA source 3mA sink Output voltage 24 Vdc 5 Maximum current Terminals 70...

Страница 7: ...ystem 4 wire system T R T R T R T R panel enclosure ground T R R X T Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Maximum cable length depends on cab...

Страница 8: ...nnection to an RS 485 4 wire system a suitable 2 to 4 wire converter will be required RS 232 system RJ12 FFC68 Plug Local Supervisor Port 1 RX 2 NC 3 CTS 4 RTS 5 GND 6 TX TX RX RTS CTS GND pin 1 Note...

Страница 9: ...d Terminal size 0 14 to 2 5 mm2 22 to 12 AWG Terminal screw torque 0 45 to 0 62 Nm 4 to 5 5 lb in Cable type Unscreened twisted pair Maximum cable length 60 m 200 ft in total used to connect all wallb...

Страница 10: ...rigid interconnectors Maximum number of I O modules on I O bus IQ4 IO Installation Instructions Mounting TG201338 XCITE IO Installation Instructions Mounting TG200627 cable interconnection XCITE CC c...

Страница 11: ...ose Rotating Covers 17 Close Panel Enclosure 18 Configure IQ4E Controller and I O Modules 1 Remove from DIN rail 3 INsTAllATIoN continued IQ4E Installation Instructions Configuring TG201339 IQ4 IO Ins...

Страница 12: ...end Control Systems Ltd s software suppliers HAS RELIED UPON Trend Control Systems Ltd TO CONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE NO WARRANTIES FOR THE SOFTW...

Отзывы: