Checking the SPI 3 for correct operation
19
MODBUS RTU | SPI 3 | Trebing & Himstedt
an error in the communication with the serial device. Refer to »Error diagnosis and
remedies« on page 25 for details of how to locate the fault.
If no errors were detected, the SPI 3 is ready for use. During data transfer, the TX or
RX LEDs will flash (see »Indicating elements« on page 9).
Evaluating PROFIBUS diagnosis telegrams
In case of communication failures (PROFIBUS and/or MODBUS), the SPI 3 sends a
diagnosis telegram on DP master request. The diagnosis telegram contains general
PROFIBUS diagnosis data (see PROFIBUS Norm) as well as manufacturer-specific
diagnosis data.
You can evaluate the diagnosis telegram through the DP master and/or a PROFIBUS
diagnosis tool (e.g. the PROFIBUS Scope).
Hexacode – Significance
Remedy
17
– Invalid MODBUS start address
Check the default start address for the paramete-
rized module with the help of the data sheet for
the MODBUS slave (MODBUS register).
21
– MODBUS no response
Check the cable connection to the MODBUS
slave as well as the MODBUS slave address
which is set and parameterized.
22
– MODBUS frame error
Check the cable connection to the MODBUS
slave. Check the default start address for the
parameterized module.