Error diagnosis and remedies
25
MODBUS RTU | SPI 3 | Trebing & Himstedt
Error diagnosis and remedies
If errors are detected, the pattern of flashing of the PB and RUN LED’s on the SPI 3
can be used for error diagnosis. The LED’s can flash with the following patterns:
Note!
If the PB LED (“PROFIBUS”) is off, the RUN LED is on continuously and no
longer indicates a valid LED code. Accordingly, the RUN LED can only be
used for diagnosis when the PB LED is lit.
The PROFIBUS diagnosis and error statuses are reset when the error is no
longer present or when the slave gets new parameter and configuration
values
LED off
LED short
LED medium
LED long
LED on
LED off
LED is ¾ off ¼ on
LED is ½ off ½ on
LED is ¼ off ¾ on
LED always on
PB LED code Status
Significance
Remedy
PB LED off
Correct data transfer
rate could not be
determined
– No PROFIBUS master in
the network
– Connect up the DP master
– Check the wiring
PB LED short
DP master available
– A master is available but
communication is not
taking place with SPI 3
– Check address setting on
the SPI 3
PB LED
medium
Incorrect parameter
Incorrect configuration
– Parameter telegram faulty
– Configuration telegram
faulty
– Check the configured and
parameterized modules
PB LED on
Data exchange OK
– Data exchange is currently
taking place
– SPI 3 working correctly