Installation
(for qualified installers only)
2 3
Travis Industries
4041206
1 0 0 - 0 1 1 4 7
Horizontal Terminations with 1 Vertical Elbow
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor position.
NOTE:
• One horizontal elbow (45° or 90°) is allowed. The
horizontal vent length is calculated by adding the length
before and after the elbow (H1 + H2 = horizontal vent
length).
• Horizontal sections require a 1/4" rise every 12" of travel.
• The maximum vertical height is 20'.
• The maximum horizontal length is 24'.
H1
Horizontal Elbow
(45° or 90°)
Vertical
Elbow
H2