![Trapzilla TSS-27 Скачать руководство пользователя страница 23](http://html1.mh-extra.com/html/trapzilla/tss-27/tss-27_installation-and-maintenance-instructions-manual_1152985023.webp)
©2014 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651
MNL-TSS 23
A THERMACO® Technology
Section IV: System Maintenance
Measuring Solids Levels
Trapzilla Solids Separators are capable of retaining high quantities of solids in a compact foot-
print. To determine the current levels of solids in your Trapzilla Solids Separator, follow the
instructions below.
1. Remove four nuts/washers securing the Solid Top Cover. Note the size of the unit which is
marked on the cover by a metal plate.
2. Place a grease/sludge dipstick into the center of the unit, making sure that it goes all the
way to the bottom.
3. Once the dipstick has found its natural resting place at the lowest point in the conical
shaped bottom, take the measurement.
4. Remove dipstick and compare sludge levels to the corresponding unit in the charts below.
Solids
Total
Capacity:
Ready to
pump at:
TSS-95
32”
27”
TSS-70
24”
21”
TSS-27
22”
18”
Take measurement from
bottom of unit upward and
compare to chart above.