ServoPac GDPS – Power supply unit

 

Chapter 4 - Troubleshooting

 

Chapter 4 – Troubleshooting 

 
 
 
 
 
 
 
 
 

4.1 – UNDERVOLTAGE FAULT 
 

When switching on the auxiliary 24 V

DC 

supply, the ServoPac GDPS unit always displays the undervoltage fault.  

The undervoltage fault will go out when switching on the power voltage, after a few seconds time delay that 
corresponds to the soft start of the power capacitors.  
The soft start system will be activated again when the voltage will drop below the undervoltage threshold. 
If the fault display remains after switching on the power supply: 
 

Check that the power supply is actually on and the actual voltage value. The DC bus voltage value can 
be measured by mean of the digitizing oscilloscope. 

 
 
4.2 – OVERVOLTAGE FAULT 

 
The overvoltage fault is used to protect the drive against high voltage values on the DC bus. 
This fault can have different origins: 
 

Check that the braking resistor is not open. 

 

Check that the operating voltage is correctly set up according to the mains voltage (SW1 configuration). 
 

When the braking I²t protection becomes active, it prevents the braking resistor from switching. 
Check that the braking ability is sufficient for the application. 
In this case, a lower ohmic value may solve the problem. 

 
 
4.3 – BRAKING TRANSISTOR FAULT 

 
The braking transistor fault is used to protect the ServoPac GDPS unit and the braking resistor against a short 
circuited transistor. 
This fault can have two different origins: 
 

If no braking resistor is connected, the fault will be displayed. 
Check that a braking resistor is connected and not opened. 
 

Else the braking transistor has been destroyed. In this case, the ServoPac GDPS unit must be repaired. 

 
 

4.4 – CONFIGURATION FAULT 

 
The configuration fault is used to prevent a wrong configuration by means of the SW1 miniswitch. 
 

Check the SW1 miniswitch code in the table. 

 

Attention: The opening of the branch-circuit protective device may be an indication that a fault 
has been interrupted. To reduce the risk of fire or electric shock, current-carrying parts and 
other components of the controller should be examined. 

Содержание ServoPac GDPS

Страница 1: ...2 Power supply unit ServoPac GDPS...

Страница 2: ...with electrical parts even after power down may involve physical damage Wait for at least 10 minutes after power down before handling the devices a residual voltage of several hundreds of volts may r...

Страница 3: ...1 5 SIZING OF THE POWER SUPPLY 6 1 5 1 Continuous power 6 1 5 2 Braking system 7 CHAPTER 2 INPUTS OUTPUTS 9 2 1 X1 CONNECTOR POWER CONNECTOR 9 2 2 X2 CONNECTOR AUXILIARY POWER SUPPLY AND AOK CONNECTOR...

Страница 4: ...power values are given for a maximum voltage of 480 VAC 1 2 ORDERING CODE 1 2 1 SERVOPAC GDPS POWER SUPPLY UNIT 1 2 2 ACCESSORIES Connector kit FC GDPS This connector set includes power X1 and auxili...

Страница 5: ...C 2 VAC VDC 2 VAC Dynamic output DC voltage according to the mains voltage regenerative phase 480 800 VDC 275 400 VDC Triggering threshold of the braking system 790 V 5 390 V 5 Minimum braking resisto...

Страница 6: ...6 ServoPac GDPS Power supply unit Chapter 1 Specifications 1 4 MECHANICAL DIMENSIONS BOTTOM VIEW SIDE VIEW FRONT VIEW Dimensions are given in mm 157 8 VERTICAL MOUNTING IS MANDATORY...

Страница 7: ...ses Speed value in rad s Simplified method 1 If the continuous average power cannot be evaluated by the accurate method it may be convenient to use the power of the application motors The electrical p...

Страница 8: ...ower regenerated on the motor shaft in W COUPLING Efficiency of the mechanical coupling gearbox If no gearbox is used COUPLING 1 PJOULE Losses in the motor windings in W RMOTOR Winding resistance meas...

Страница 9: ...me rules must be observed heat must be evacuated shielded cable or at least twisted wires must be used wires must bear high voltage and high temperature recommended type UL1015 AWG 14 wires must be as...

Страница 10: ...ge output 6 DR O Braking resistor connection Recommended wire section 2 5 mm or AWG14 Braking resistor is required 7 DR O 2 2 X2 CONNECTOR AUXILIARY POWER SUPPLY AND AOK CONNECTOR Manufacturer Weidmul...

Страница 11: ...nfigure the operation mode of the ServoPac GDPS unit MINISWITCH DESCRIPTION 1 2 3 4 5 6 7 8 0 0 0 0 X X X X Operating voltage 400 VAC default configuration 1 1 0 0 X X X X Operating voltage 400 VAC wi...

Страница 12: ...drive TT drive Braking resistor AC 24V isolated 230 V 0 V 24 V AOK AOK L1 L2 L3 DC DC DR DR Power ON Power relay remote control KM1 24 V AOK GDPS AOK AXIS 1 AOK AXIS N STOP km1 KM1 F1 3 2 FUSE RATING...

Страница 13: ...voltage is correctly set up according to the mains voltage SW1 configuration When the braking I t protection becomes active it prevents the braking resistor from switching Check that the braking abili...

Отзывы: