To function correctly and read temperature accurately, the thermostat must have constant 

24

-volt pow-

er. If the thermostat temperature is steadily dropping, reading low, or reads 

08°

 when a remote sensor is 

installed, it can be traced to one of the three following conditions.

Condition

Test

Comments

1.

   Loss of 

24

-volt 

power.

On models with batteries, remove 
the batteries and re-install 
thermostat. If the display is blank, 
check heating and cooling system 
to determine why 

24

-volt power is 

absent.

For the sensor to read correctly, the 

24

-volt system power must be present. 

Some systems may require an isolation 
relay to provide constant power to the 
thermostat. Limit or safety devices in 
the equipment can also cause a power 
interruption.

2. 

  A broken wire on 

+, S

 or - from the 

thermostat to the 
remote.

Disconnect sensor wires at 
thermostat. Attach a short piece 

(2')

 of three-wire shielded cable to 

 

+, S, and - on the subbase. Bring the 
remote sensor to the thermostat 
location and , S, and -, 
respectively. Reattach thermostat. 
If the temperature begins to climb 
(slowly), it is reading correctly. If it 
reads correctly with the 

2' 

length 

but improperly when attached to 
the wire run, it indicates a fault in 
the wire run.

Repair or replace the 

wire shielded 

cable. Be sure the remote wire run is 
not parallel to line voltage wires that 
carry heavy inductive loads, or across 
fluorescent light ballasts that may 
cause an inductance to be transmitted 
to the thermostat.

3.

   A shorted or 

damaged remote 
sensor.

Because it is an electronic sensor, 
there are no Ohm values to test. If 
correct conditions as listed in 

1

 & 

2

 

above and the temperature stays at 
or near 

08°

, it indicates a shorted or 

damaged remote sensor.

Replace remote sensor.

Note:

 Digital thermostats and remote sensors acclimate very slowly to temperature change. It may take 

an hour or more for the temperature to acclimate to the room temperature from a low temperature 
reading as outlined above. To expedite the room temperature display use the reset instructions listed in 
the installation instructions for the thermostat model you are working with. When reset, the thermostat 
will default to a room temperature of 

70°

 and begin sensing room temperature. Be sure to reconfigure 

the installer menu for a remote sensor because the reset function may cancel remote sensing.

TROUBLESHOOTING 

 

Pub No. 

1

8-HD86D

1

-

1    

Part No. 

37-7772002

August 2018

Содержание ZZSENSAL0300AA

Страница 1: ...TEMPAOutdoorModel 40to140 F Operating Humidity Range 0 to 90 RH non condensing Maximum Distance fromThermostat 300 feet Recommended Wire 18 or 20 gauge 3 conductor shielded cable Color ClassicWhite Dimension 2 1 8 x 3 1 2 x 3 4 Outdoor Remote includes 12 ft of outdoor probe lead ZZSENSAL0300AA INDOOR REMOTE SENSOR BAYSEN30ATEMPA OUTDOOR REMOTE SENSOR Interior Mounting Base Outdoor Probe CONTENTS S...

Страница 2: ...a correct outdoor temperature reading Observethefollowinggeneralruleswhenselecting a location 1 The interior mounting base can be located a maximum of 300 feet from the thermostat 2 Install the interior mounting base within 12 ft of the intended outdoor probe location 3 Never install the outdoor probe where it will be exposed to direct light from lamps sun fireplaces or any temperature radiating e...

Страница 3: ... connect shield of 18 or 20 gauge 3 connector cable to on thermostat subbase Figure 1 TouchscreenThermostat ACONT302 303 TCONT302 303 Indoor Outdoor Remote Sensor Wiring ZZSENSAL0300AA BAYSEN30ATEMPA Thermostat Subbase Remote Outdoor Sensor S E2 To To S To Outdoor Probe Remote Indoor Sensor S To To S To CONFIGURATION Touchscreen Models When installing a remote sensor you must enable the remote sen...

Страница 4: ...eads correctly with the 2 length but improperly when attached to the wire run it indicates a fault in the wire run Repair or replace the 3 wire shielded cable Be sure the remote wire run is not parallel to line voltage wires that carry heavy inductive loads or across fluorescent light ballasts that may cause an inductance to be transmitted to the thermostat 3 A shorted or damaged remote sensor Bec...

Отзывы: