INSTALLATION 

INDOOR SENSOR

 

SELECT SENSOR LOCATION

Proper location insures that the remote sensor 
will provide a comfortable home or building 
temperature. Observe the following general rules 
when selecting a location:

1.

  The remote sensor can be located a maximum 

of 

300

 feet from the thermostat. 

2.

  Locate sensor about

 5 ft.

 above the room floor 

level.

3.

  Install sensor on a partitioning wall, not on an 

outside wall.

4.

  Never expose sensor to direct light from lamps, 

sun,  fireplaces  or  any  temperature  radiating 
equipment.

5.

  Avoid locations close to windows, adjoining 

outside walls, or doors that lead outside.

6.

  Avoid locations close to air registers or in the 

direct path of air from them.

7.

  Make sure there are no pipes or duct work in that 

part of the wall chosen for the sensor location.

8.

  Never locate sensor in a room that is normally 

warmer or cooler than the rest of the home 
(such as the kitchen) or building.

9.

  Avoid locations with poor air circulation, such 

as behind doors or in alcoves.

10.

  In the home, the living or dining room is normally 

a good location, provided there is no cooking 
range or refrigerator on opposite side of wall.

OUTDOOR SENSOR

 

SELECT SENSOR LOCATION

Proper location insures that the remote sensor will 
provide a correct outdoor temperature reading. 
Observe the following general rules when selecting 
a location:

1.

  The interior mounting base can be located a 

maximum of 

300 

feet from the thermostat. 

2.

  Install the interior mounting base within 

12 ft. 

of the intended outdoor probe location.

3.

  Never install the outdoor probe where it 

will be exposed  to direct light from lamps, 
sun,  fireplaces  or  any  temperature  radiating 
equipment.

4.

  Make sure there are no pipes or ductwork in the 

wall chosen for the base location.

5.

  Outdoor temperature measurement requires 

installing the probe outdoors. Good probe 
locations would be under a bay window or 
overhang, out of direct sunlight. Direct sun 
exposure will affect sensed temperature. Install 
probe with spacer to obtain a more accurate 
temperature.

Mounting

Surface

Spacer

6.

 

Although connected to the probe wire for 
outdoor temperature sensing, the interior 
mounting base must be placed indoors. 
Therefore, the interior mounting base must 
be installed near the perimeter of the building, 
so that the probe wire can be run through to 
the outside of the structure and placed in the 
selected (shaded) location. The outdoor probe 
wire is 

12

 feet long (and should not be cut or 

spliced), so plan the placement of both the 
probe and interior mounting base accordingly. 
Any excess wire may be coiled or bundled. The 
probe should be connected to 

E2

 as shown in 

figure 

1

.

Pub No. 

1

8-HD86D

1

-

1    

Part No. 

37-7772002

August 2018

Содержание ZZSENSAL0300AA

Страница 1: ...TEMPAOutdoorModel 40to140 F Operating Humidity Range 0 to 90 RH non condensing Maximum Distance fromThermostat 300 feet Recommended Wire 18 or 20 gauge 3 conductor shielded cable Color ClassicWhite Dimension 2 1 8 x 3 1 2 x 3 4 Outdoor Remote includes 12 ft of outdoor probe lead ZZSENSAL0300AA INDOOR REMOTE SENSOR BAYSEN30ATEMPA OUTDOOR REMOTE SENSOR Interior Mounting Base Outdoor Probe CONTENTS S...

Страница 2: ...a correct outdoor temperature reading Observethefollowinggeneralruleswhenselecting a location 1 The interior mounting base can be located a maximum of 300 feet from the thermostat 2 Install the interior mounting base within 12 ft of the intended outdoor probe location 3 Never install the outdoor probe where it will be exposed to direct light from lamps sun fireplaces or any temperature radiating e...

Страница 3: ... connect shield of 18 or 20 gauge 3 connector cable to on thermostat subbase Figure 1 TouchscreenThermostat ACONT302 303 TCONT302 303 Indoor Outdoor Remote Sensor Wiring ZZSENSAL0300AA BAYSEN30ATEMPA Thermostat Subbase Remote Outdoor Sensor S E2 To To S To Outdoor Probe Remote Indoor Sensor S To To S To CONFIGURATION Touchscreen Models When installing a remote sensor you must enable the remote sen...

Страница 4: ...eads correctly with the 2 length but improperly when attached to the wire run it indicates a fault in the wire run Repair or replace the 3 wire shielded cable Be sure the remote wire run is not parallel to line voltage wires that carry heavy inductive loads or across fluorescent light ballasts that may cause an inductance to be transmitted to the thermostat 3 A shorted or damaged remote sensor Bec...

Отзывы: