3

CAUTION

!

Do not allow the 

3

-conductor wire to be pinched 

between the sensor and the wall.
Check wire connections before applying power. 
Improper connections will lead to permanent 
damage to the sensor.
When shielded cable is used, cable shield must 
be connected to "-" on  the  THERMOSTAT ONLY.

 

 WIRING DIAGRAMS

Note: 

When using shielded cable, connect shield 

of 

18

 or 

20

 gauge 

3

 connector cable to "-" on 

thermostat subbase.

Figure 

1

 – Touchscreen Thermostat 

(ACONT302/303 & TCONT302/303)

 

Indoor/Outdoor Remote Sensor Wiring 

(ZZSENSAL0300AA/BAYSEN30ATEMPA)

Thermostat Subbase

Remote Outdoor Sensor

+

S

E2

To +

To S

To -

Outdoor Probe

Remote Indoor Sensor

+

S

To +

To S

To -

 

 CONFIGURATION

Touchscreen Models: 

When installing a remote sensor you must enable the remote sensor option in the 

Installation Menu. See Installation Instructions.

Pub No. 

1

8-HD86D

1

-

1    

Part No. 

37-7772002

August 2018

Содержание ZZSENSAL0300AA

Страница 1: ...TEMPAOutdoorModel 40to140 F Operating Humidity Range 0 to 90 RH non condensing Maximum Distance fromThermostat 300 feet Recommended Wire 18 or 20 gauge 3 conductor shielded cable Color ClassicWhite Dimension 2 1 8 x 3 1 2 x 3 4 Outdoor Remote includes 12 ft of outdoor probe lead ZZSENSAL0300AA INDOOR REMOTE SENSOR BAYSEN30ATEMPA OUTDOOR REMOTE SENSOR Interior Mounting Base Outdoor Probe CONTENTS S...

Страница 2: ...a correct outdoor temperature reading Observethefollowinggeneralruleswhenselecting a location 1 The interior mounting base can be located a maximum of 300 feet from the thermostat 2 Install the interior mounting base within 12 ft of the intended outdoor probe location 3 Never install the outdoor probe where it will be exposed to direct light from lamps sun fireplaces or any temperature radiating e...

Страница 3: ... connect shield of 18 or 20 gauge 3 connector cable to on thermostat subbase Figure 1 TouchscreenThermostat ACONT302 303 TCONT302 303 Indoor Outdoor Remote Sensor Wiring ZZSENSAL0300AA BAYSEN30ATEMPA Thermostat Subbase Remote Outdoor Sensor S E2 To To S To Outdoor Probe Remote Indoor Sensor S To To S To CONFIGURATION Touchscreen Models When installing a remote sensor you must enable the remote sen...

Страница 4: ...eads correctly with the 2 length but improperly when attached to the wire run it indicates a fault in the wire run Repair or replace the 3 wire shielded cable Be sure the remote wire run is not parallel to line voltage wires that carry heavy inductive loads or across fluorescent light ballasts that may cause an inductance to be transmitted to the thermostat 3 A shorted or damaged remote sensor Bec...

Отзывы: