ZZSENSAL0300AA/BAYSEN30ATEMPA

Indoor Remote Sensor/Outdoor Remote Sensor

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY 
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE 
PERSONAL INJURY AND/OR PROPERTY DAMAGE.

 

 SPECIFICATIONS

For applications where the wire run is short (

100

 ft. or 

less) shielded cable may not be required provided the 
wires are not routed parallel to or across other wires 
carrying electrical power. To reduce electrical inter-
ference or inductance from other electrical wiring or 
devices use shielded cable and keep Remote Sensor 
wire runs separate from thermostat wiring. Remote 
sensors cannot be used with systems where power 
interruptions are part of normal system operation. 

Operating Range:

 (based on thermostat range)

ZZSENSAL0300AA 

Indoor Model:

 

40

 to

 99°F

BAYSEN30ATEMPA 

Outdoor Model:

 

-40 

to

 140°F

Operating Humidity Range:

 

to

 90% 

RH 

(non-condensing)

Maximum Distance from Thermostat

300

 feet

Recommended Wire:

 

18 

or 

20

 gauge,    

3

-conductor shielded cable

Color:

 Classic White

Dimension:

 

2-1/8" x 3-1/2" x 3/4"

 

Outdoor Remote includes

 12

 ft. of outdoor 

probe lead

ZZSENSAL

0300

AA

INDOOR REMOTE SENSOR

BAYSEN

30

ATEMPA

OUTDOOR REMOTE SENSOR

Interior Mounting Base

Outdoor Probe

CONTENTS

Specifications ................................................ 

1

Installation .................................................... 

2

Wiring Diagram

 ...............................................3

Configuration .................................................

Troubleshooting

 ...............................................4

CAUTION

!

To prevent electrical shock and/or equipment 
damage, disconnect electric power to system at 
main fuse or circuit breaker box until installation 
is complete.

WARNING

!

Do  not  use  on  circuits  exceeding  specified 

voltage.  Higher voltage will damage control 

and could cause shock or fire hazard.

Do not short out terminals on gas valve or 
primary control to test.  Short or incorrect 
wiring will damage thermostat and could cause 
personal injury and/or property damage.

Pub No. 

1

8-HD86D

1

-

1    

Part No. 

37-7772001

August 2018

Содержание ZZSENSAL0300AA

Страница 1: ...TEMPAOutdoorModel 40to140 F Operating Humidity Range 0 to 90 RH non condensing Maximum Distance fromThermostat 300 feet Recommended Wire 18 or 20 gauge 3 conductor shielded cable Color ClassicWhite Dimension 2 1 8 x 3 1 2 x 3 4 Outdoor Remote includes 12 ft of outdoor probe lead ZZSENSAL0300AA INDOOR REMOTE SENSOR BAYSEN30ATEMPA OUTDOOR REMOTE SENSOR Interior Mounting Base Outdoor Probe CONTENTS S...

Страница 2: ...a correct outdoor temperature reading Observethefollowinggeneralruleswhenselecting a location 1 The interior mounting base can be located a maximum of 300 feet from the thermostat 2 Install the interior mounting base within 12 ft of the intended outdoor probe location 3 Never install the outdoor probe where it will be exposed to direct light from lamps sun fireplaces or any temperature radiating e...

Страница 3: ... connect shield of 18 or 20 gauge 3 connector cable to on thermostat subbase Figure 1 TouchscreenThermostat ACONT302 303 TCONT302 303 Indoor Outdoor Remote Sensor Wiring ZZSENSAL0300AA BAYSEN30ATEMPA Thermostat Subbase Remote Outdoor Sensor S E2 To To S To Outdoor Probe Remote Indoor Sensor S To To S To CONFIGURATION Touchscreen Models When installing a remote sensor you must enable the remote sen...

Страница 4: ...eads correctly with the 2 length but improperly when attached to the wire run it indicates a fault in the wire run Repair or replace the 3 wire shielded cable Be sure the remote wire run is not parallel to line voltage wires that carry heavy inductive loads or across fluorescent light ballasts that may cause an inductance to be transmitted to the thermostat 3 A shorted or damaged remote sensor Bec...

Отзывы: