6

XT500C DELUXE PROGRAMMABLE HEAT-PUMP THERMOSTAT

69-1404

Pub. No. 18-HD25D2-2

Table  3. Installer Setup Options for the XT500C 

(Continued).

(continued)

Press Time  

▲ 

or

 ▼  

 

Press Increase 

 or Decrease 

 to change setting

Installer   

Factory Setting

Other Choices

Actual

Select

Setup Number

Display

Description

Display

Description

Setting

Em. Ht. cycle rate 7

5

5—5 cph recommended
3, 6, or 9 cph not
recommended

3, 6, or 9

3—3 cph
6—6 cph
9—9 cph

Stage 1 cooling
cycle rate

9

3

3—3 cph recommended
2 or 5 cph not
recommended

2 or 5

2—2 cph
5—5 cph

Stage 2 cooling
cycle rate

10

3

3—3 cph recommended
2 or 5 cph not
recommended

2 or 5

2—2 cph
5—5 cph

System setting
adjustment  

12

0

Auto changeover

1 or 2

1—Manual
changeover
2—Auto changeover
only

Adaptive
Intelligent
Recovery™
control

13  

0

Adaptive  Intelligent
Recovery (a Honeywell
trademark) control is
activated (system starts
early so setpoint is
reached by start of
program period)

1

Conventional
recovery (system
starts recovery at
programmed time)

Degree temp -
erature display

14

0

Temperature displays   
in °F

1

Temperature displays
in °C

Clock format   

16

0

12-hour clock format

1

24-hour clock format

Extended fan
operation in
heating

a

19  

0

No extended fan
operation after the call
for heat ends

1, 2 or 3

1—Fan operation
extends 30 seconds
after the call ends.
2—Fan operation
extends 60 seconds
after the call ends.
3 —Fan operation
extends 90 seconds
after the call ends.

Extended fan
operation in
cooling   

20  

0

No extended fan
operation after the call
for cool ends

1, 2 or 3

1—Fan operation
extends 30 seconds
after the call ends.
2—Fan operation
extends 60 seconds
after the call ends.
3 —Fan operation
extends 90 seconds
after the call ends.

Outdoor
temperature
display (select
models)

24

0

No outdoor temperature
displays

1

Outdoor temperature
displays. Requires a
TAYSENS100A
Outdoor Sensor.

Comfort-R

Enable

28

0

No fan delay

1 or 2

1—30 seconds
2—15 seconds

Содержание XT500C

Страница 1: ...nd on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check...

Страница 2: ...e is located near each terminal for identification WARNING Electrical Shock or Equipment Damage Hazard Can shock individuals or cause equipment damage Disconnect power before wiring to prevent electri...

Страница 3: ...heating and cooling operation depending on the indoor temperature Time Set Program System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight...

Страница 4: ...s on changing the default settings Table 2 Default Program Settings M17150 LED INDICATOR M14610 Aux Ht System Em Heat Em Ht FLAME DISPLAYS DURING CALL FOR HEAT AUX HT DISPLAYS WHEN SYSTEM CALLS FOR AD...

Страница 5: ...of all the segments of the LCD IMPORTANT Only configurable numbers display Example Installer Setup Number 1 does not display because it is not configurable Review the factory settings in Table 3 and...

Страница 6: ...system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree temp erature display 14 0 Temperature displays in F 1 Tem...

Страница 7: ...essor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call for cool Temperature range stops in heating 34 85 Highest setpoint heating can be set to 55 to 85 Temperature...

Страница 8: ...shes on the display until a key is pressed 2 Press Day until the current day displays NOTE Tapping the Set Current Day Time will change the time in one hour increments Press Time or Press Increase or...

Страница 9: ...eat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 Key to Press Test Number Description Heating Equipment Self Test 1...

Страница 10: ...and Comfort R is enabled display reads If the terminals are closed no displays Keyboard Operation Self Test 60 Time 60 7 Enter keyboard operation self test Temp 60 9 Increase test number displays Tem...

Страница 11: ...ceed with troubleshooting Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup number 37 and reconfigure the display Thermostat is configured for F or...

Страница 12: ...g setpoint Set cooling setpoint to desired temperature Heating or cooling comes on momentarily and shuts off Heat or cool circuit is opening up or becoming high impedance Add resistor in parallel with...

Отзывы: