Trane XT500C Скачать руководство пользователя страница 10

10

XT500C DELUXE PROGRAMMABLE HEAT-PUMP THERMOSTAT

69-1404

Pub. No. 18-HD25D2-2

DEVICE INFORMATION
SELF-TEST (70)

1. Press Temp 

 and 

 keys simultaneously, then press

Time 

 

to access the thermostat information.

2. Press Increase 

 to display the production date code

in a 3-digit format. The first two digits represent the
month and the third digit represents the last digit of the
year (Example: 128=December 1998).

M14613

M14614

Table 5. Installer Self-Test Options (

Continued).

NOTE:

Press Time 

 to return to the previous test or Time 

 to advance to the next test.

NOTE:

To exit, press Time 

 or Time

  ▼

 then Run Program.

Key to
Press

Test
Number

Description

Comfort-R Terminals Self-Test (50)

Temp

 

50

Enter Comfort-R self-test.

Temp

 ▼

51

Reads HH terminals. If the terminals are open and Comfort-R is enabled, display reads  

. If the terminals are closed no 

▲ 

displays.

Keyboard Operation Self-Test (60)  

Time 

60   7

Enter  keyboard  operation  self-test.

Temp

 ▲

60   9

Increase  test  number  displays.

Temp

 ▼

60   8

Decrease test number displays.

D a y

60   11

Day test number displays.

C o p y

60   12

Copy test number displays.

S y s t e m
( s e l e c t
models)

60   3

System test number displays.

F a n
( s e l e c t
models)

60   10

Fan test number displays.

S e t
Current
D a y / T i m e

60   1

Set Current Day/Time test number displays.

Run
Program

60   15

Run Program test number displays.

Daylight
Time

60   19

Daylight Time test number displays.

H e a t /
Cool
S e t t i n g s

60   5

Heat/Cool Settings test number displays.

W a k e

60   0

Wake test number displays.

L e a v e

60   14

Leave test number displays.

Return

60   16

Return test number displays.

S l e e p

60   2

Sleep test number displays.

Filter

60   17

Filter test number displays.

i

60   13

Information test number displays.

Device Information Self-Test (70) -  Refer to following section.

Содержание XT500C

Страница 1: ...nd on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check...

Страница 2: ...e is located near each terminal for identification WARNING Electrical Shock or Equipment Damage Hazard Can shock individuals or cause equipment damage Disconnect power before wiring to prevent electri...

Страница 3: ...heating and cooling operation depending on the indoor temperature Time Set Program System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Day Heat Cool Settings Daylight...

Страница 4: ...s on changing the default settings Table 2 Default Program Settings M17150 LED INDICATOR M14610 Aux Ht System Em Heat Em Ht FLAME DISPLAYS DURING CALL FOR HEAT AUX HT DISPLAYS WHEN SYSTEM CALLS FOR AD...

Страница 5: ...of all the segments of the LCD IMPORTANT Only configurable numbers display Example Installer Setup Number 1 does not display because it is not configurable Review the factory settings in Table 3 and...

Страница 6: ...system starts early so setpoint is reached by start of program period 1 Conventional recovery system starts recovery at programmed time Degree temp erature display 14 0 Temperature displays in F 1 Tem...

Страница 7: ...essor 0 thru 15 Minimum number of minutes 0 thru 15 the compressor will be on during call for cool Temperature range stops in heating 34 85 Highest setpoint heating can be set to 55 to 85 Temperature...

Страница 8: ...shes on the display until a key is pressed 2 Press Day until the current day displays NOTE Tapping the Set Current Day Time will change the time in one hour increments Press Time or Press Increase or...

Страница 9: ...eat On Auto Off Cool Auto AM PM Hold for Heat Cool Repl Batt Recovery DST Tue Wed Thu Fri Sat Sun Days Temporary Setting Em Ht M14612 Key to Press Test Number Description Heating Equipment Self Test 1...

Страница 10: ...and Comfort R is enabled display reads If the terminals are closed no displays Keyboard Operation Self Test 60 Time 60 7 Enter keyboard operation self test Temp 60 9 Increase test number displays Tem...

Страница 11: ...ceed with troubleshooting Temperature display is incorrect Room temperature display has been reconfigured Enter Installer Setup number 37 and reconfigure the display Thermostat is configured for F or...

Страница 12: ...g setpoint Set cooling setpoint to desired temperature Heating or cooling comes on momentarily and shuts off Heat or cool circuit is opening up or becoming high impedance Add resistor in parallel with...