XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

69-1213—1 (T8624)

Pub. No. 18-HD25D7-5

Table  3. Installer Setup Options for the XT302C (continued).

(continued)

Press Time  

▲ 

or

  ▼  

 

Press Increase 

 or Decrease 

 to change setting

Installer   

Factory Setting

Other Choices

Actual

Select

Setup Number

Display

Description

Display

Description

Setting

Adaptive
Intelligent
Recovery™
control

13  

0

Adaptive  Intelligent
Recovery (a
Honeywell trademark)
control is activated
(system starts early so
setpoint is reached by
start of program
period)

1

Conventional recovery
(system starts recovery at
programmed time)

Degree
temperature
display

14

0

Temperature displays
in 

°

F

1

Temperature displays in 

°

C

Clock format   

16

0

12-hour clock format

1

24-hour clock format

Extended fan
operation in
heating

a

19  

0

No extended fan
operation after the call
for heat ends

1, 2 or 3

1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.

Extended fan
operation in
cooling   

20  

0

No extended fan
operation after the   
call for cool ends

1, 2 or 3

1—Fan operation extends
30 seconds after the call
ends.
2—Fan operation extends
60 seconds after the call
ends.
3 —Fan operation extends
90 seconds after the call
ends.

Outdoor
temperature
display (select
models)

24

0

No outdoor
temperature displays

1

Outdoor temperature
displays. Requires a
TAYSENS100A Outdoor
Sensor.

Comfort-R

Enable

28

0

No fan delay

1 or 2

1—30 seconds
2—15 seconds

Minimum
Deadband
Between
Heating and
Cooling in Auto
Changeover
Mode

30  

4

Heating and cooling
setpoints can be set
no closer than 4

°

F

(2

°

C)

3 thru 10

Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3

°

F (1.5

°

C)

4—4

°

F (2

°

C)

5—5

°

F (2.5

°

C)

6—6

°

F (3

°

C)

7—7

°

F (3.5

°

C)

8—8

°

F (4

°

C)

9—9

°

F (4.5

°

C)

10—10

°

F (5

°

C)

Minimum On
Time (Heat)

32

5

5-minute minimum on
time for compressor

0 thru 15

Minimum number of minutes
(0 thru 15) the compressor
will be on during call for
heat

Содержание XT302C

Страница 1: ...and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to che...

Страница 2: ...es See Fig 4 NOTE Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation...

Страница 3: ...y Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12957 Fan Auto Fan On Time Set Program System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Da...

Страница 4: ...ring to this chart Installer Setup Procedure 1 Press and hold the Information Increase and Decrease keys at the same time until all display segments and the first setup number displays all display seg...

Страница 5: ...ed Press Time or Press Increase or Decrease to change setting Installer Factory Setting Other Choices Actual Select Setup Number Display Description Display Description Setting Programming 42 Press Ti...

Страница 6: ...call ends 2 Fan operation extends 60 seconds after the call ends 3 Fan operation extends 90 seconds after the call ends Extended fan operation in cooling 20 0 No extended fan operation after the call...

Страница 7: ...ring call for cool Temperature range stops in heating 34 85 Highest setpoint heating can be set to 55 to 85 Temperature range 1 F increments heating setpoint can be set to Temperature range stops in c...

Страница 8: ...ments of the LCD To start the self test Press and hold the Increase and Decrease keys at the same time until all display segments and the number 10 appears all displays segments appear for approximate...

Страница 9: ...Enter Comfort R self test Temp 51 Reads HH terminals If the terminals are open and Comfort R is enabled display reads humidity If the terminals are closed no humidity displays Keyboard Operation Self...

Страница 10: ...l not come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the...

Страница 11: ...eed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System sele...