XT302C DELUXE PROGRAMMABLE HEAT-COOL THERMOSTAT

11

69-1213—1 (T8624)

Pub. No. 18-HD25D7-5

TROUBLESHOOTING (Continued).

Symptom

Possible Cause

Action

Heating will not come
on.

No power to the
thermostat.

Check for 24 Vac between R and W terminals.
If missing 24 Vac:
Check if the circuit breaker is tripped—reset the circuit breaker.
Check if the system fuse is blown—replace the fuse.
Check if the power switch on the HVAC equipment is in the Off
position—set to the On position.
Check wiring between thermostat and HVAC
equipment—replace any broken wires and tighten any loose
connections.
If 24 Vac is present, proceed with troubleshooting.

Heating will not come
on.

Thermostat minimum off
time is activated.

Wait up to five minutes for the system to respond.

System selection is not
set to Heat.

Set system selection to Heat.

Heating setpoint is below
room temperature.

Check heating setpoint. Set heating setpoint to desired temperature.

Cooling will not come
on.

No power to the
thermostat.

Check for 24 Vac between R and W terminals.
If missing 24 Vac:
Check if the circuit breaker is tripped—reset the circuit breaker.
Check if the system fuse is blown—replace the fuse.
Check if the power switch on the HVAC equipment is in the  
Off position—set to the On position.
Check wiring between thermostat and HVAC equipment—replace any
broken wires and tighten any loose connections.
If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off
time is activated.

Wait up to five minutes for the system to respond. Enter Installer Setup
number 39. Reconfigure minimum off time (if required).

System selection is not
set to Cool.

Set system selection to Cool.

Cool setpoint is above
room temperature.

Check cooling setpoint. Set cooling setpoint to desired temperature.

Heating or cooling
come on momentarily
and shut off

Heat or cool circuit is
opening up or becoming
high impedance.

Add resistor in parallel with load or install interface relay.

System on indicator
(flame=heat,
snowflake=cool)
displays, but no

Heating equipment turns
on the fan when the
furnace has warmed up   
to a setpoint.

Wait a minute after seeing the on indicator and then check the registers.

warm or cool air is
coming from the
registers.

Heating or cooling
equipment is not
operating.

Verify operation of heating or cooling equipment in self-test.

Outdoor temperature
not displayed

Option  not  activated.

Enter Installer Setup number 24 and set to 1. Thermostat must have OT

terminals and a TAYSENS100A installed.

or is incorrect.

Outdoor sensor is
connected incorrectly.

Refer to TAYSENS100A installation instructions and check wiring
between the thermostat and sensor.

Wrong sensor.

Replace sensor with TAYSENS100A sensor.

Filter expired.

Refer to the 

Filter Indication  section in the Owner’s Guide, Pub.  

No. 22-5127-04

System on indicator
reads Filter and
backlight is flashing.

Filter expired.

Refer to the 

Filter Indication  section.

Time displaying digits
as three E’s (EEE).

Internal memory failure.

Contact distributor or retailer.

Содержание XT302C

Страница 1: ...and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to che...

Страница 2: ...es See Fig 4 NOTE Use 18 gauge color coded thermostat cable for proper wiring 2 Securely tighten each terminal screw 3 Push excess wire back into the hole 4 Plug the hole with nonflammable insulation...

Страница 3: ...y Time Wake Leave Return Sleep Day Heat Cool Settings Daylight Time Copy M12957 Fan Auto Fan On Time Set Program System Filter Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep Da...

Страница 4: ...ring to this chart Installer Setup Procedure 1 Press and hold the Information Increase and Decrease keys at the same time until all display segments and the first setup number displays all display seg...

Страница 5: ...ed Press Time or Press Increase or Decrease to change setting Installer Factory Setting Other Choices Actual Select Setup Number Display Description Display Description Setting Programming 42 Press Ti...

Страница 6: ...call ends 2 Fan operation extends 60 seconds after the call ends 3 Fan operation extends 90 seconds after the call ends Extended fan operation in cooling 20 0 No extended fan operation after the call...

Страница 7: ...ring call for cool Temperature range stops in heating 34 85 Highest setpoint heating can be set to 55 to 85 Temperature range 1 F increments heating setpoint can be set to Temperature range stops in c...

Страница 8: ...ments of the LCD To start the self test Press and hold the Increase and Decrease keys at the same time until all display segments and the number 10 appears all displays segments appear for approximate...

Страница 9: ...Enter Comfort R self test Temp 51 Reads HH terminals If the terminals are open and Comfort R is enabled display reads humidity If the terminals are closed no humidity displays Keyboard Operation Self...

Страница 10: ...l not come on Thermostat is not being powered Check for 24 Vac between R and W terminals Check if the circuit breaker is tripped reset the circuit breaker Check if the system fuse is blown replace the...

Страница 11: ...eed with troubleshooting Thermostat minimum off time is activated Wait up to five minutes for the system to respond Enter Installer Setup number 39 Reconfigure minimum off time if required System sele...

Страница 12: ...12 XT302C DELUXE PROGRAMMABLE HEAT COOL THERMOSTAT 69 1213 1 T8624 Pub No 18 HD25D7 5 69 1213 1 T C Rev 1 99 American Standard Inc Troup Highway Tyler TX 75711 9010 Printed in Taiwan R O C...

Отзывы: