22-1825-09 5
General
Data
AHRI Standard Capacity Rating Conditions
AHRI STANDARD 210/240 RATING CONDITIONS —
(A) Cooling 80°F DB, 67°F WB air entering indoor coil,
95°F DB air entering outdoor coil.
(B) High Temperature Heating 47°F DB, 43°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(C) Low Temperature Heating 17°F DB, 15°F WB air entering
outdoor coil, 70°F DB air entering indoor coil.
(D) Rated indoor airflow for heating is the same as for cooling.
AHRI STANDARD 270 RATING CONDITIONS — (Noise
rating numbers are determined with the unit in cooling opera-
tion.) Standard Noise Rating number is at 95°F outdoor air.
Accessory Description and Usage
24 Volt Wiring Harness — Used to wire a communicating
outdoor unit to an existing 24 Volt indoor section.
Charge Assist™ Solenoid Kit — fast/accurate charging
every time.
Rubber Isolators
— 5 large rubber donuts to isolate con-
densing unit from transmitting energy into mounting frame or
pad. Use on any application where sound transmission needs
to be minimized.
Extreme Condition Mount Kit
— Bracket kits to securely
mount condensing unit to a frame or pad without removing
any panels. Use in areas with high winds, or on commercial
roof tops, etc.
Low Ambient Cooling
— For low ambient cooling below 55°
see Application Guide SSC-APG005-EN.