WSHP-SVX04A-EN
19
Low Voltage Wiring for Field
Provided Thermostats/Zone
Sensors
Ensure that the AC control wiring be-
tween the controls and the unit’s ter-
mination point does not exceed three
(3) ohms/conductor for the length of
the run.
Note: Resistance in excess of 3-ohms
per conductor may cause component
failure due to insufficient AC voltage
supply.
Check all loads and conductors for
grounds, shorts, and mis-wiring.
Use copper conductors unless other-
wise specified.
Do not run the AC low voltage wiring
in the same conduit with the high volt-
age power wiring.
Table 3: 24V AC conductors
Distance
from unit to Control
Recommended
Wire Size
000-460 feet
18 gauge
461-732 feet
16 gauge
733-1000 feet
14 gauge
Thermostat Location
Location of the room thermostat/zone sensor cis an important element of effec-
tive room control.
Areas where the thermostat or zone sensor should not be located include : be-
hind doors, or corners; Near hot or cold air ducts; Near radiant heat (heat emitted
from appliances or the sun); Near concealed pipes or chimneys; On outside walls
or other non conditioned surfaces; In airflows from adjacent zones or other units
(Figure 7)
.
Installation
Low Voltage Wiring
Figure 7: Thermostat/sensor location
Содержание WPHF
Страница 7: ...WSHP SVX04A EN 7 Dimensions WPHF 021 057 ...
Страница 8: ...8 WSHP SVX04A EN Dimensions WPVJ 018 024 LH ...
Страница 9: ...WSHP SVX04A EN 9 Dimensions WPVJ 018 024 RH ...
Страница 10: ...10 WSHP SVX04A EN Dimensions WPVJ 030 042 LH ...
Страница 11: ...WSHP SVX04A EN 11 Dimensions WPVJ 030 042 RH ...
Страница 12: ...12 WSHP SVX04A EN Dimensions WPVJ 048 072 LH ...
Страница 13: ...WSHP SVX04A EN 13 Dimensions WPVJ 048 072 RH ...
Страница 35: ...WSHP SVX04A EN 35 Unit Wiring WPVJ Basic 24V Diagram ...
Страница 36: ...36 WSHP SVX04A EN Unit Wiring WPVJ Tracer ZN510 Diagram ...
Страница 37: ...WSHP SVX04A EN 37 Unit Wiring WPHF Basic 24V Diagram ...
Страница 38: ...38 WSHP SVX04A EN Unit Wiring WPHF Tracer ZN510 Diagram ...