Connecting a Distributed Pump 
Kit to a Closed Loop System

All piping external to the unit is the re-
sponsibility of the installer. The water 
pipe installation must be done in ac-
cordance with local codes. If no local 
code applies, national codes should be 
followed. It is the contractor’s respon-
sibility to know and adhere to all appli-
cable codes.

Water inlet and outlet to the unit’s wa-
ter-to-refrigerant heat exchanger are 
clearly marked on the submittal draw-
ings found on pages 7 through 13. The 
supply and return piping must be in-
stalled correctly to the unit to ensure 
the safety devices will work properly. 
Units that are not piped accordingly 
will not obtain the manufacturers war-
ranty.

A pump module

 

and hose kit 

(Figure 5)

 

may be used to connect the unit to 
closed loop piping.

Using Antifreeze

In areas of the country where entering 
water temperatures drop below 45°F 
or where piping is being run through 
areas subject to freezing, the loop 
must be freeze protected by using an 
approved antifreeze solution to pre-
vent the earth loop water from freez-
ing inside the heat exchanger. 
Methanol, Ethylene, and Propylene 
Glycol are the most commonly used 
antifreeze solutions. Consult your geo-
thermal unit supplier for the best solu-
tions in your area.

Propylene glycol is not recommended 
in installations where the water tem-
perature are expected to fall below 
30°F. At extreme temperatures, the vis-
cosity increases to the point where 
normal loop circulating pumps cannot 
maintain proper flow.

Calculate the approximate volume of 
water in the system by using the re-
quirements detailed in

 Table 2

. Add 

three gallons to this total to allow for 
the water contained in the hose kit and 
geothermal unit.

Table 2: Required Antifreeze by volume

Cleaning and Flushing 
the Water Loop

After the piping system is complete, 
cleaning and flushing the water loop 
should be done to avoid trash settle-
out in the condenser 

(Figure 6)

. An ex-

tra pipe may be necessary to connect 
the hose kits. 

1  

 Electrical power to the unit should 

be disconnected.

2

   Double back the supply hose and 

connect directly to the return riser 
valve. 

3

   Fill the water system with clean wa-

ter using the water make up connec-
tions. 

Note: Air vents should be 

opened during filling.

 With the air vents closed, start the 

circulating pump and then crack the air 
vents to bleed off the trapped air, as-
suring circulation through all compo-
nents of the system. 

Note: Make up 

water must be available to the system

 

to replace the volume formerly occu-
pied by the air that is bled off.

Type of 

Antifreeze

Minimum Temperature for 

Freeze Protection

10

°F

15

°F

20

°F

25

°F

30

°F

Methanol

25% 21% 16% 10%

3%

Propylene 

Glycol

23% 21% 19%

9%

6%

Ethylene Glycol 20% 19% 16% 14% 12%

 With the air vented and the water 

circulating, the entire system should 
be checked for leaks with repairs made 
as required.

6

   Check and adjust the water/air level 

in the expansion tank.

7

  Operate the boiler (if used) by rais-

ing the loop temperature to approxi-
mately 85°F. Make checks per 
manufacturer’s instructions. During 
this operation, visual checks should be 
made for leaks that may have occurred 
due to increased heat. Repair as re-
quired.

 Open the system at the lowest point 

for the initial blow down (making sure 
the make up water is equal to the wa-
ter being dumped). Continue blow 
down until the water leaving the drain 
runs clear, but not less than 2 hours.

 Shut down pumps and boiler (if 

used). Reconnect the hoses to the 
proper supply/return for each unit, 
placing the water-to-refrigerant heat 
exchanger in the water circulating sys-
tem. 

Note: Vents should be open when 

the pumps and boiler are shut down.

10

  Refill the system and bleed off any 

air. Add antifreeze to the system in cli-
mates where ambient temperature 
falls below freezing, using the propor-
tion of antifreeze shown in 

Table 2

.

Installation

From Units

W.O.

To Units

W.I.

Bronze or Cast Iron Pump

Purging Cap (2)

Shut-off 3-way Valve (2)

1" MPT x barb fittings
1" MPT x barb elbows with
pressure temperature ports
and 10’ of rubber hose with
4 hose clamps

Figure 5: Pump module and hose kit

Figure 6: System flushing

Содержание WPHF

Страница 1: ...WSHP SVX04A EN Models A and later Design Sequence Installation Owner Diagnostics Extra High Efficiency Water Source Heat Pump Models WPVJ and WPHF WPVJ 018 072 60 HZ WPHF 021 057 60 HZ ...

Страница 2: ...ditioning system to knowingly vent or release any CFC or HCFC refrigerant Minimal releases air purges or refrigerant hoses associated with good faith attempts to recapture or recycle are exempt from the ban on venting Responsible Refrigerant Practices Trane believes that responsible refrigerant practices are important to the environment our customers and the air conditioning industry All technicia...

Страница 3: ... Information 5 Dimensions Weights 6 Installation Instructions 14 Electrical Requirements 20 Pre Startup Checklist 25 Startup Commissioning 26 Sequence of Operation 26 Operating Pressures 27 30 Startup Checklist Log 30 Maintenance 31 Warranty Information 32 Troubleshooting Checklist 33 Unit Wiring 35 ...

Страница 4: ...e has been retained reinstall the schrader caps to assure that refrigerant leakage does not occur WARNING Microbial Growth Wet interior unit insulation can become an amplification site for microbial growth mold which may cause odors and damage to the equipment and building materials If there is evidence of microbial growth mold on the interior insulation the insulation should be removed and replac...

Страница 5: ...ws Blower Motor The blower and motor is located inside the unit cabinet The motor may be easily removed for service through the equipment blower access panel Controls The control system offered to control the unit is a Basic 24 volt control Basic 24 volt control or TracerTM ZN510 control A 50 VA transformer is factory supplied on the Basic 24V control con figurations A 75 VA transformer is fac Dia...

Страница 6: ...t or property only damage Dimensions Weights Clearance Figure 2 Mechanical clearances WPVJ Unit Location and Clearances Locate the unit in an indoor area The ambient temperature surrounding the unit must not be less than 45 F Do not locate the unit in areas subject to freezing Attention should be given to service clearance and technician safety The unit should be easily maintained or serviced in a...

Страница 7: ...WSHP SVX04A EN 7 Dimensions WPHF 021 057 ...

Страница 8: ...8 WSHP SVX04A EN Dimensions WPVJ 018 024 LH ...

Страница 9: ...WSHP SVX04A EN 9 Dimensions WPVJ 018 024 RH ...

Страница 10: ...10 WSHP SVX04A EN Dimensions WPVJ 030 042 LH ...

Страница 11: ...WSHP SVX04A EN 11 Dimensions WPVJ 030 042 RH ...

Страница 12: ...12 WSHP SVX04A EN Dimensions WPVJ 048 072 LH ...

Страница 13: ...WSHP SVX04A EN 13 Dimensions WPVJ 048 072 RH ...

Страница 14: ...refrigeration access panel and inspect the unit Be certain the refrigerant tubing has clearance from adjacent parts WARNING Hazardous Voltage Disconnect all electric power including remote disconnects before servicing Follow proper lockout tagout procedures to ensure the power can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Ma...

Страница 15: ...sure trapping In a properly trapping system when condensate forms during normal operation the water level in the trap rises until there is a constant flow Figure 3 It is imperative to main tain water in the trap and not allow the trap to dry out during heating season Keeping the trap primed at all times will enable the water to flow properly Condensate piping must be installed to allow the cleanab...

Страница 16: ...sider the unit s draw thru design requiring negative pres sure trapping In a properly trapping system when condensate forms during normal operation the water level in the trap rises until there is a constant flow Figure 4 It is imperative to main tain water in the trap and not allow the trap to dry out during heating season Keeping the trap primed at all times will enable the water to flow properl...

Страница 17: ... pipe may be necessary to connect the hose kits 1 Electrical power to the unit should be disconnected 2 Double back the supply hose and connect directly to the return riser valve 3 Fill the water system with clean wa ter using the water make up connec tions Note Air vents should be opened during filling 4 With the air vents closed start the circulating pump and then crack the air vents to bleed of...

Страница 18: ...isconnect switch must be installed at or near the unit in accordance with the National Electric Code NEC latest edition Location of the applicable electric ser vice entrance for HIGH line voltage may be found on the unit submittals pages 7 to 13 1 The high voltage connection is made at the 1K1 contactor inside of the unit control box Refer to the connection diagram that is shipped with the unit fo...

Страница 19: ...in the same conduit with the high volt age power wiring Table 3 24V AC conductors Distance from unit to Control Recommended Wire Size 000 460 feet 18 gauge 461 732 feet 16 gauge 733 1000 feet 14 gauge Thermostat Location Location of the room thermostat zone sensor cis an important element of effec tive room control Areas where the thermostat or zone sensor should not be located include be hind doo...

Страница 20: ...8 0 1 17 0 1 30 1 4 1 16 4 25 No 0 WPVJ030 265 60 1 13 61 12 10 58 0 1 17 0 1 30 1 4 1 16 6 25 Yes 0 21 WPVJ036 208 60 1 17 8 15 00 73 0 1 21 0 2 80 1 3 1 21 6 35 No 0 WPVJ036 208 60 1 18 01 15 00 73 0 1 21 0 2 80 1 3 1 21 8 35 Yes 0 21 WPVJ036 208 60 3 13 5 10 70 63 0 1 15 0 2 80 1 3 1 16 2 25 No 0 WPVJ036 208 60 3 13 71 10 70 63 0 1 15 0 2 80 1 3 1 16 4 25 Yes 0 21 WPVJ036 220 240 50 1 16 6 14 3...

Страница 21: ... 9 6 7 50 49 5 1 10 5 2 10 3 4 1 11 5 15 No 0 WPVJ060 460 60 3 9 6 7 50 49 5 1 10 5 2 10 3 4 1 11 5 15 No 0 WPVJ060 460 60 3 9 81 7 50 49 5 1 10 5 2 10 3 4 1 11 7 15 Yes 0 21 WPVJ060 575 60 3 8 1 6 40 40 0 1 9 0 1 70 3 4 1 9 7 15 No 0 WPVJ060 575 60 3 8 31 6 40 40 0 1 9 0 1 70 3 4 1 9 9 15 Yes 0 21 WPVJ072 208 60 1 36 3 32 10 169 0 1 45 0 4 20 3 4 1 44 3 70 No 0 WPVJ072 208 60 1 36 51 32 10 169 0 ...

Страница 22: ...10 70 63 0 1 15 0 2 80 1 3 1 16 2 25 No 0 WPVJ036 230 60 3 13 71 10 70 63 0 1 15 0 2 80 1 3 1 16 4 25 Yes 0 21 WPVJ036 265 60 1 16 6 14 30 71 0 1 20 0 2 30 1 3 1 20 2 30 No 0 WPVJ036 265 60 1 16 81 14 30 71 0 1 20 0 2 30 1 3 1 20 4 30 Yes 0 21 WPVJ036 380 415 50 3 6 4 5 00 31 0 1 7 0 1 40 1 2 1 7 7 15 No 0 WPVJ036 460 60 3 6 4 5 00 31 0 1 7 0 1 40 1 2 1 7 7 15 No 0 WPVJ036 460 60 3 6 61 5 00 31 0 ...

Страница 23: ...VJ072 230 60 1 37 81 32 10 169 0 1 45 0 5 50 3 4 1 45 8 70 Yes 0 21 WPVJ072 230 60 3 24 8 19 30 137 0 1 27 0 5 50 3 4 1 29 6 45 No 0 WPVJ072 230 60 3 25 01 19 30 137 0 1 27 0 5 50 3 4 1 29 8 45 Yes 0 21 WPVJ072 380 415 50 3 13 3 10 00 62 0 1 14 0 3 30 3 4 1 15 8 25 No 0 WPVJ072 460 60 3 13 3 10 00 62 0 1 14 0 3 30 3 4 1 15 8 25 No 0 WPVJ072 460 60 3 13 51 10 00 62 0 1 14 0 3 30 3 4 1 16 0 25 Yes 0...

Страница 24: ...60 3 1 2 1 8 7 1 11 1 51 10 7 15 20 20 Model No Volts Hz Ph Blower Motor HP Blower Motor FLA Compr RLA Compr MCC Compr LRA Minimum Cir cuit Amps UL Max Fuse or HACR CSA Max Fuse Size CASE Max Circuit Brkr WPHF047 208 60 1 1 2 4 6 14 6 22 8 92 22 9 35 50 40 WPHF047 230 60 1 1 2 4 6 14 6 22 8 92 22 9 35 50 40 WPHF047 208 60 3 1 2 4 6 10 6 16 5 101 17 9 25 50 45 WPHF047 230 60 3 1 2 4 6 10 6 16 5 101...

Страница 25: ...Heat Pump Systems Installation Guide ____ Is vibration isolation provided i e unit isolation pad hosekits ____ Is unit serviceable See clearance specifications on page 6 ____ Are the low high side pressure temperature caps secure and in place ____ Are all the unit access panels secure and in place ____ Is the thermostat in the OFF position ____ Is the water flow established and circulating through...

Страница 26: ...ion line should be cool with no frost observed in the refrigerant circuit 4 Check the cooling refrigerant pressures against values in Table OP1 Page 27 5 Turn the thermostat switch to the OFF position Unit should stop running and the reversing valve should de energize 6 Leave unit off for approximately FIVE minutes to allow for pressure equalization 7 Turn the thermostat to the lowest setting 8 Se...

Страница 27: ... 35 WPVJ 024 68 4 88 71 82 147 187 10 13 18 23 71 82 210 268 5 7 30 39 WPVJ 024 68 6 1 71 81 143 182 8 11 18 23 72 83 212 270 4 5 31 40 WPVJ 024 75 4 88 72 83 164 208 10 13 18 22 77 89 218 277 6 7 32 41 WPVJ 024 75 6 1 72 83 159 202 8 11 18 23 78 90 220 280 5 6 33 42 WPVJ 024 86 4 88 74 85 193 245 10 13 17 22 86 99 229 292 6 8 35 45 WPVJ 024 86 6 1 74 85 187 238 8 11 17 22 87 100 232 295 5 7 36 46...

Страница 28: ... 18 23 74 85 210 267 7 9 34 43 WPVJ 048 86 9 2 75 86 200 255 11 14 18 22 78 90 214 272 9 11 34 44 WPVJ 048 86 11 5 74 85 192 245 9 11 18 23 77 89 215 274 7 9 35 44 WPVJ 048 95 9 2 76 87 226 288 11 14 17 22 WPVJ 048 95 11 5 76 87 218 277 9 11 17 22 WPVJ 060 35 11 92 41 47 160 204 6 7 20 26 WPVJ 060 35 14 9 41 47 162 206 4 6 21 26 WPVJ 060 45 11 92 66 75 110 140 13 16 23 30 51 58 169 215 6 8 23 29 W...

Страница 29: ...tart up WARNING Live Electrical Components During installation testing servicing and troubleshooting of this product it may be necessary to work with live electrical components Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks Failure to follow all electrical safety pre cautions when exposed to live el...

Страница 30: ...and costly system failures complete the following checks and data entries before the system is put into full operation MODE Entering fluid temperature Leaving fluid temperature Temperature differential Return air temperature DB WB Supply air temperature DB WB Temperature differential Water coil heat exchanger Water Pressure IN Water coil heat exchanger Water Pressure OUT Pressure Differential HEAT...

Страница 31: ...ated with dirt and scaling as a result of bad water the Model WPVJ Filter Size nominal 018 024 16 x 20 030 042 20 x 25 048 072 20 x 30 Model WPHF Filter Size nominal 021 027 16 x 24 035 040 1 16 x 16 1 16 x 20 047 057 18 x 20 Maintenance heat exchanger will have to be back flushed and cleaned with a chemical that will remove the scale This service should be performed by an experi enced service per...

Страница 32: ...ed 18 months from shipment Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year coverage through the fifth year These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start up Warranty Information ...

Страница 33: ...nary checks inspect the unit for other obvi ous problems such as leaking connec tion broken or disconnected wires etc If everything appears to be in or der but the unit still fails to operate properly refer to the troubleshooting chart on page 34 General Operation The standard model is designed for in door installation When the unit is in stalled in an unconditioned space the unit may not start in...

Страница 34: ...e X X Unit undersized Recalculate heat gains losses X X Inadequate water flow Increase GPM X X Scaling in heat exchanger Clean or replace X Water too hot Decrease temperature X Water too cold Increase temperature High pressure switch open X Inadequate GPM Increase water flow to unit X Water too hot Decrease temperature X Inadequate air flow Check clean blower and coil X Dirty filter Clean replace ...

Страница 35: ...WSHP SVX04A EN 35 Unit Wiring WPVJ Basic 24V Diagram ...

Страница 36: ...36 WSHP SVX04A EN Unit Wiring WPVJ Tracer ZN510 Diagram ...

Страница 37: ...WSHP SVX04A EN 37 Unit Wiring WPHF Basic 24V Diagram ...

Страница 38: ...38 WSHP SVX04A EN Unit Wiring WPHF Tracer ZN510 Diagram ...

Страница 39: ...cifications without notice Literature Order Number WSHP SVX04A EN File Number SV UN WSHP SVX04A 0803 Supersedes WSHP IOM 1 WPVF IOM 1 Stocking Location Inland Trane A business of American Standard Companies www trane com For more information contact your local district office or e mail us at comfort trane com ...

Отзывы: