Trane WCK024B1 Скачать руководство пользователя страница 4

Page  4

Electrical Wiring

Electrical Connections

Electrical wiring and grounding must be installed in accordance
with local codes or, in the absence of local codes, with the
National Electrical Code ANSI/NFPA 70, Latest Revision.

Disconnect Switch

•Provide an approved weather-proof disconnect either on the
side of the unit or within close proximity and

 within sight of the

unit.

Over Current Protection

•The branch circuit feeding the unit must be protected as shown
on the unit rating plate.

Power Wiring

•The power supply  lines must be run in weathertight conduit to
the disconnect and into the bottom of the unit control box.
Provide strain relief for all conduit with suitable connectors.

•Provide flexible conduit supports whenever vibration trans-
mission may cause a noise problem within the building struc-
ture.

•Ensure all connections are made tight. See Figures 5 and 6:
Typical Field Wiring Diagrams.

•NOTES:

1.

  For branch circuit wiring (main power supply to the unit

disconnect), wire size for the length of run should be
determined using the circuit ampacity found on the unit
nameplate and the N.E.C.

2.

  For more than 3 conductors in a raceway or cable, see the

N.E.C. for derating the ampacity of each conductor.

3.

  Wire size is based on 75 degrees C rated wire insulation.

Grounding

•The unit must be electrically grounded in accordance
with local codes or the National Electrical Code.

WARNING:

 

TO PREVENT INJURY OR DEATH 

DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING 
PARTS. LOCK UNIT DISCONNECT SWITCH IN OPEN 
POSITION BEFORE SERVICING UNIT.

Ground Level -- Horizontal

For ground level installations, the unit should be positioned on
a pad the size of the unit or larger.  The unit must be level on the
pad.  The pad must not come in contact with the structure.  Be
sure the outdoor portion of the supply and return air ducts are as
short as possible.

Proceed with the installation as follows:

1.  Place the unit on the pad.

2.  Attach the supply and return air ducts to the unit.

3.  Insulate any ductwork outside of the structure with at least

2 inches of insulation and weatherproof. There must be a
weatherproof seal where the duct enters the structure.

4.  Complete the installation according to the instructions in the

following sections of this manual.

Installation

Condensate Drain Piping

A 3/4-inch female NPT condensate drain connection is provided
on the evaporator access panel end of the unit.  See Figure 4.
Provide a trap and fill it with water before starting the unit to
avoid air from being drawn through.  Follow local codes and
standard piping practices when running the drain line.  Pitch the
line downward away from the unit.  Avoid long horizontal runs.
See Figure 2

NOTE:

  Do not use reducing fittings in the drain lines. The

condensate drain must be:

Made of 3/4" pipe size.

Pitched 1/4" per foot to provide free drainage to convenient
drain system.

Trapped.

Must not be connected to closed drain system.

3

/

4

" PVC OR COPPER

TUBING AND FITTINGS

1-1/2"

MIN.

2

ATTACHING HORIZONTAL DUCTWORK
TO UNIT

All conditioned air ductwork should be insulated to minimize
heating and cooling duct losses.  Use a minimum of two (2) inches
of insulation with a vapor barrier.  The outside ductwork must be
weatherproofed between the unit and the building.

When attaching ductwork to a horizontal unit, provide a flexible
watertight connection to prevent noise transmission from the unit to
the ducts.

Note: 

Duct flanges are located in blower and heater compartment.

Содержание WCK024B1

Страница 1: ...duct that are capable of conducting electri cal current are grounded If grounding wires screws straps clips nuts or washers used to complete a path to ground are removed for service they must be returned to their original position and properly fastened ALL phases of this installation must comply with NATIONAL STATE and LOCAL CODES These instructions do not purport to cover all variations in system...

Страница 2: ...s a make up air 5 Check the handling facilities to insure the safety of personnel and the unit s 6 CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID PERSONAL INJURIES AND OR DAMAGE TO EQUIP MENT 7 The unit must be mounted level for proper drainage of defrost water through the holes in the base pan 8 Flexible duct connectors must be of a flame retardant mate rial All duct work outside of the structure mu...

Страница 3: ...2 32 70 72 32 70 72 139 70 308 441 17 3 8 413 16 1 8 WCK030B1 33 60 74 37 20 82 33 60 74 30 40 67 135 20 298 302 11 7 8 413 16 1 8 WCK024B1 38 60 85 34 92 77 29 02 64 32 20 71 135 20 298 0 413 16 1 8 TCK042B1 34 90 77 37 20 82 34 90 77 32 70 72 139 70 308 441 17 3 8 413 16 1 8 TCK036B1 33 60 74 36 70 81 33 60 74 30 80 68 134 70 297 441 17 3 8 413 16 1 8 TCK030B1 30 80 68 38 60 85 34 90 77 28 10 62...

Страница 4: ...e positioned on a pad the size of the unit or larger The unit must be level on the pad The pad must not come in contact with the structure Be sure the outdoor portion of the supply and return air ducts are as short as possible Proceed with the installation as follows 1 Place the unit on the pad 2 Attach the supply and return air ducts to the unit 3 Insulate any ductwork outside of the structure wi...

Страница 5: ...sition causing continu ous evaporator indoor fan operation or the AUTO position causing fan operation to coincide with heating or cooling run cycles Continuous fan mode during cooling operation may not be appropriate in humid climates If the indoor air exceeds 60 relative humidity or simply feels uncomfortably humid it is recommended that the fan only be used in the AUTO mode COOLING MODE NOTE TSH...

Страница 6: ...Use a NIOSH approved dust mist respirator Avoid contact with the skin or eyes Wear long sleeved loose fitting clothing gloves and eye protection Wash clothes separately from other clothing rinse washer thoroughly Operations such as sawing blowing tear out and spraying may generate fiber concentrations requiring additional respiratory protection Use the appropriate NIOSH approved respirator in thes...

Страница 7: ...horoughly dry before re installing them in the unit Replace permanent filters annually if washing fails to clean them or if they show signs of deterioration Use the same type and size as was originally installed Outdoor Coil Unfiltered air circulated through the unit s outdoor coil can cause the coil s surface to become clogged with dust dirt etc To clean the coil stroke the coil surface with a so...

Страница 8: ...door ambi ent temperature with a sensor located outside the outdoor coil A second sensor located on the outdoor coil is used to measure the coil temperature The difference between the ambient and the colder coil temperature is the difference or delta T measurement This delta T measurement is representative of the operating state and relative capacity of the heat pump system By measuring the change...

Страница 9: ...sor 2 Does OD fan cycle off in defrost N Replace defrost control 3 Windy weather preventing normal termination 7 Defrost initiates on approximately 15 25 minute intervals Be sure OD coil is clean N Complete Check 2 1 Coil sensor open or reading a very high resistance Y Replace coil sensor 2 Ambient sensor reading less than normal N Complete Check 3 Y Replace ambient sensor 3 OD fan off in defrost ...

Страница 10: ...rate auto matically Operating Pressures After the unit has operated in the cooling mode for a short time install pressure gauges on the gauge ports of the discharge and suction line valves Check the suction and discharge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACTS Voltage Withthecompressoroperating checkthelinevoltageattheunit The voltage shoul...

Страница 11: ...ally this limited warranty will not apply unless the packaged unit is 1 installed by a licensed or qualified HVAC technician 2 applied and installed in accordance with the manufacturer s recommendations and its Installer s guide and 3 in compliance with all industry standards national state and local codes This limited warranty does not cover failure of your packaged unit if it is damaged while in...

Страница 12: ...ry or warehouse replacement parts for Warrantor s products covered under this warranty Warrantor shall not be obligated to pay for the cost of lost refrigerant No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective This limited warranty does not apply if the pack...

Отзывы: