28
UV-SVN03D-EN
WARNING
Hazardous Service
Procedures!
The maintenance and trouble-
shooting procedures recommend-
ed in this section of the manual
could result in exposure to electri-
cal, mechanical or other potential
safety hazards. Always refer to
the safety warnings provided
throughout this manual concern-
ing these procedures. When possi-
ble, disconnect all electrical
power including remote discon-
nects before servicing. Follow
proper lockout/tagout procedures
to ensure the power can not be in-
advertently energized. When nec-
essary to work with live electrical
components, have a qualified li-
censed electrician or other indi-
vidual who has been trained in
handling live electrical compo-
nents perform these tasks. Failure
to follow all of the recommended
safety warnings provided, could
result in death or serious injury.
Access to Fanboard & Motor
The unit ventilator fan board can be re-
moved for service to the blower motor
and fan wheels. The fan board must
also be removed for easier access to
the unit coils for cleaning and mainte-
nance. Utilize the following steps for
proper removal of the fanboard.
1
Turn off power to the unit and re-
move the front panel.
2
Disconnect P-trap from drain pan.
3
Disconnect fan plug.
4
Slide fan board by pulling deck
forward,
Figure 17
.
CAUTION
Equipment Damage!
Support the fanboard to prevent
the deck from sliding too far for-
ward and falling out of the unit.
Failure to do so may cause equip-
ment damage.
5
When reinstalling, use the same
steps in reverse order.
Motor
The fan motor is a permanent split ca-
pacitor type motor with voltage specif-
ic power. See Table E1 through E3 for
electrical performance and motor volt-
age.
Table E3:
Motor Voltage
If a replacement motor is required, it
should be ordered from The Trane
Company. To replace the fan motor,
complete the following steps:
6
Complete steps for removal of
fan board.
7
Disconnect the motor ground
wire.
8
Using a 7/16” Allen wrench, loos-
en the coupling on the fan shaft.
9
Loosen the screw on the motor
clamp until it allow the motor to
be lifted off the base,
Figure 18
.
10
Lift the motor and pull forward
until fan shaft separates from the
motor,
Figure 19
.
Unit Voltage
Motor Voltage
115-60-1
115-60-1
208-60-1
208/230-60-1
230-60-1
208/230-60-1
208-60-3
208/230-60-1
460-60-3
265-60-1
265-60-1
265-60-1
230-60-3
208/230-60-1
11
Attach new motor to fan shaft
and reverse steps to complete in-
stallation.
Maintenance
!
Figure 17:
Fan board removal for fan/
motor access
Figure 18
: Loosen screws
Figure 19
: Lift/pull motor forward
Содержание VUV
Страница 8: ...8 UV SVN03D EN Dimensions Standard Depth Unit ...
Страница 9: ...UV SVN03D EN 9 Dimensions Falseback Unit ...
Страница 10: ...10 UV SVN03D EN Dimensions Dynamic Air Barrier Unit ...
Страница 11: ...UV SVN03D EN 11 Dimensions End Covers ...
Страница 12: ...12 UV SVN03D EN Dimensions Wall Boxes ...
Страница 33: ...UV SVN03D EN 33 Unit Wiring Field Installed Wiring 120V 1 PH 3 Speed ...
Страница 34: ...34 UV SVN03D EN Unit Wiring End Device Controls 120V 1 PH 3 Speed DX Hot Water ...
Страница 35: ...UV SVN03D EN 35 Unit Wiring End Device Package 480V 3 PH 3 Speed Chilled Water Electric Heat 6 Element page 1 ...
Страница 36: ...36 UV SVN03D EN Unit Wiring End Device Package 480V 3 PH 3 Speed Chilled Water Electric Heat 6 Element page 2 ...
Страница 37: ...UV SVN03D EN 37 Unit Wiring End Device Package 120V 1 PH 3 Speed 4 Pipe Hot Water Chilled Water ...
Страница 38: ...38 UV SVN03D EN Unit Wiring Tracer ZN520 120V 1 PH 3 Speed 4 Pipe Hot Water Chilled Water ...
Страница 39: ...UV SVN03D EN 39 ...