Trane VUV Скачать руководство пользователя страница 21

UV-SVN03D-EN

21

Manually Opening Valve

The manual opener can be manipulat-
ed only when in the up position. The A 
port can be manually opened by firmly 
pushing the white manual lever down 
to the midway position and pushing 
the lever in. In this position, both A 
and B ports are open. This “manual 
open” position may be used for filling, 
venting and draining the system or 
opening the valve during power fail-
ure.

 The valve can be closed by depressing 
the white lever lightly and then pulling 
the lever outward. The valve and actu-
ator will return to the automatic posi-
tion when power is restored. 

Note: If the valve is powered open, it 
cannot be manually closed, unless the 
actuator is removed.

Wiring

A controller and a separate transform-
er is required to operate each valve. 
See 

Figures 9 and 10

. Port A “open” 

and “closed” denote valve open and 
closed positions.

Figure 9:

 Wiring for modulating valve 

actuator

Figure 10

: Wiring for modulating valve 

actuator

The typical floating controller is an 
SPDT controller with a center-off posi-
tion. On a change in temperature from 
the set point, the controller will close 

the normally open (NO) or normally 
closed (NC) contacts, driving the valve 
to an intermediate position until a fur-
ther change at the controller. 

The valve is set between the limits of 
the controller to satisfy various load 
requirements. In the event of power 
failure, the valve will stay in the posi-
tion it was in before loss of power. 
When power is restored, the valve will 
again respond to controller demand.

Isolation Valves
Installation

The valve can be mounted in any posi-
tion on a vertical line. If the valve is 
mounted horizontally, the actuator 
must be even with or above the center 
line. Make sure there is enough room 
to remove actuator cover for servicing. 
Mount the valve on the tube or pipe.

Note: Ensure the flow through the 
valve is in the direction indicated by 
the arrow stamped on the valve body.

Figure 11: 

Proper mounting for 

 

isolation valves.

Servicing/Removal of Valves

The actuator can be removed from the 
valve body. Removing the actuator is 
recommended if soldering is being 
conducted near the valve. To remove 
the actuator:

1

Place the manual operating lever 

to the Open position, 

Figure 12

 

2

Depress the locking button and lift 
actuator until it separates from the 
valve body.

Figure 12: Removing valve actuator

To install the actuator to the valve 
body:

3

Align the slot on the shaft of the 

valve with the valve body notch on 

side of body. See 

Figure 13

.

Figure 13

: Installing isolation valve

4

Install body valve into pipe.

5

Wiring connections may be made 

either before or after actuator in-
stalled on body.

6

Place the manual operating lever 

on the actuator in the OPEN posi-
tion.

7

Align actuator coupling to slot on 

the shaft of the valve body and fit 
the head onto the valve body to 
ensure the shaft seats correctly, 

Figure 11

.

8

Press the actuator and valve body 
until it secures together.

Installation

Содержание VUV

Страница 1: ...UV SVN03D EN October 2007 Models A and later Design Sequence Installation Owner Maintenance Vertical Unit Ventilator Classroom Unit Ventilator Model VUV VUVE 750 CFM 1500 CFM ...

Страница 2: ...sult in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices CAUTION Indicates a situation that may result in equipment or property damage only accidents Important Equipment is shipped FOB Free on Board at the manufacturer Therefore freight claims for damages aga...

Страница 3: ...mmissioning 4 Pre installation Checklist 4 General Information 5 Dimensions Weights 7 Installation Instructions 14 Electrical Requirements 24 Pre Startup Checklist 26 Maintenance 27 Warranty Information 30 Troubleshooting Checklist 31 Unit Wiring 33 ...

Страница 4: ...tion site for microbial growth mold which may cause odors and damage to the equipment and building materials If there is evidence of microbial growth mold on the interior insulation the insulation should be removed and replaced prior to operating the system Jobsite Storage This unit is intended for indoor use only To protect the unit from damage due to the elements and to prevent possible IAQ cont...

Страница 5: ...l 7 8 I D Heating Auxiliary Coil 1 2 Nominal 5 8 I D Steam Heating Coil 1 FNPT Direct Expansion Coil 3 8 O D Liquid 7 8 O D Suction nance oiling is not needed and or bearing replacement Filters Filter sizing for the unit ventilator are an off the shelf design to reduce or help eliminate local stocking of the fil ters Sliding Fan Deck Convenient access to the fan motor and wheels for maintenance an...

Страница 6: ...on with the face and bypass damper Table 1 OA RA actuator specification Table 3 Mod water valve specification Power Supply 24 VAC 20 50 60 HZ 24 VAC 10 Power Consumption Running 2 5 W Holding 1 W Transformer Sizing 5 VA class 2 power source Overload Protection Electronic throughout 0 to 95 degree rotation Control Signal 2 to 10 VDC 3 point floating with Trane controls Angle of Rotation Maximum 95 ...

Страница 7: ...n Type Quantity FC 2 FC 2 FC 4 FC 4 Motor Data Quantity 1 1 2 2 Horsepower ea 1 4 1 4 1 10 1 10 Number of Fan Speeds Standard 3 3 3 3 If DX or electric heat used 1 1 1 1 Number of Fan Speed ZN520 3 3 3 3 If exhaust fan or ERSA used 2 2 2 2 If DX or electric heat used 1 1 1 1 Coil Volume gal Coil Type A 0 178 0 228 0 277 0 327 B 0 311 0 410 0 510 0 610 C 0 311 0 410 0 510 0 610 D 0 444 0 571 0 704 ...

Страница 8: ...8 UV SVN03D EN Dimensions Standard Depth Unit ...

Страница 9: ...UV SVN03D EN 9 Dimensions Falseback Unit ...

Страница 10: ...10 UV SVN03D EN Dimensions Dynamic Air Barrier Unit ...

Страница 11: ...UV SVN03D EN 11 Dimensions End Covers ...

Страница 12: ...12 UV SVN03D EN Dimensions Wall Boxes ...

Страница 13: ... pro vides the crossover for the cold water only The crossover pipe is factory in sulated with 3 8 thick insulation 2 Expansion compensation between the factory piping package and the cross over piping is achieved using a flex hose rated at 250 psi working pressure flex hose is only available with factory mounted piping packages 3 Expansion compensation for the crossover piping must be handled ext...

Страница 14: ...h load bearing capacity The lintel may be omitted on masonry wall installations Weep holes are provided in the out side face of the bottom channel in the wallbox frame Install all wall boxes to permit free drainage through the weep holes to the outside of the building All wallboxes are furnished with dia mond pattern expanded aluminum bird screen Note V1 and V2 vertical wall models are all unflang...

Страница 15: ...n the floor for a return air duct electrical and piping sup ply lines fed through the floor See page 7 for unit weights 2 Wall space design should allow the unit to be mounted to the wall se curely The wall surface behind the unit should be smooth and lev el Wall and floor moldings should be removed prior to installation A wall slightly out of level may cause problems with unconditioned air leakin...

Страница 16: ... 2 13 22 44 79 00 10 00 59 00 26 stepdown falseback 1 00 2 13 21 44 79 00 10 00 59 00 25 stepdown falseback 1 00 2 13 20 44 79 00 10 00 59 00 125 Standard Unit no Falseback 1 31 13 50 2 75 90 39 10 38 69 64 Standard falseback 1 00 2 13 26 00 91 00 10 00 71 00 29 stepdown falseback 1 00 2 13 24 44 91 00 10 00 71 00 28 stepdown falseback 1 00 2 13 23 44 91 00 10 00 71 00 27 stepdown falseback 1 00 2...

Страница 17: ...ent 5 Ensure the unit rests tightly against the wall Check for proper seal and that air does not leak un derneath the unit Subbase option A subbase may be used to increase the unit height and aid in leveling the unit The subbase is shipped separately for field installation Slots and leveling screws are provided on the subbase 1 Remove the leveling legs provided with the unit See Figure 4 Figure 4 ...

Страница 18: ...connections Piping packages are not shipped insu lated Any insulation should be provid ed in the field by the installing contractor The auxiliary drain pan optional is the main condensate connection to the unit when specified The chilled water or DX coil drain pan will empty into the auxiliary drain pan if a factory installed auxiliary pan is ordered All field piping condensate connections should ...

Страница 19: ...hrough the back of the unit Access piping knockouts are lo cated in the rear panels of the unit as shown in dimensional section of this manual Recommended refrigerant line con nections for various unit combinations are given in Table 7 Typical Superheat Charging Charts are shown in the Trane Service Facts found in the con densing unit section manual Refriger ant charge weights can also be determin...

Страница 20: ...2 Remove the cartridge assembly from the valve body with the en closed tool 3 Solder the valve in accordance with normal soldering practices 4 Re install the cartridge after solder ing by tightening until it bottoms out The top surface of the car tridge will be flush with the top edge of the body casting Note Do not overtighten Maxi mum torque is 40 in lb 5 Replace valve actuator and wire in accor...

Страница 21: ...ilure the valve will stay in the posi tion it was in before loss of power When power is restored the valve will again respond to controller demand Isolation Valves Installation The valve can be mounted in any posi tion on a vertical line If the valve is mounted horizontally the actuator must be even with or above the center line Make sure there is enough room to remove actuator cover for servicing...

Страница 22: ...nt for specific information Failure to do so may result in equipment fail ure When installing field provided controls do not alter or remove any built in unit safeties Tamper ing with unit safeties may cause unit overheating and possible fire hazard Do not remove or alter the wiring of the Time Delay Relay DL Do ing so may result in premature motor failures Unit ventilator controls and control wir...

Страница 23: ...tructions provided with the condensing unit for control testing and system start up If sweat type field piped systems are be ing used then pressure testing evacu ation and refrigerant charging will be required Two bulbs will also be shipped with a split system unit Frost stat bulb TXV valve used with R410a Both components are to be field in stalled using the installation kit shipped with the unit ...

Страница 24: ...9 20 36 5 40 265 60 1 1 0 1 4 1 6 11 70 42 20 43 20 54 0 60 460 60 3 1 0 1 4 1 0 0 00 0 00 1 00 1 3 15 460 60 3 1 0 1 4 1 3 5 85 7 00 8 00 10 0 15 460 60 3 1 0 1 4 1 4 7 80 14 10 15 10 18 9 20 460 60 3 1 0 1 4 1 6 11 70 14 10 15 10 18 9 20 VUVE100 115 60 1 3 0 1 4 1 0 0 00 0 00 3 00 3 8 15 208 60 1 1 6 1 4 1 0 0 00 0 00 1 60 2 0 15 208 60 1 1 6 1 4 1 3 5 86 28 20 29 80 37 3 40 208 60 1 1 6 1 4 1 4...

Страница 25: ...60 7 70 265 60 1 0 9 1 10 2 6 19 50 70 40 72 20 90 0 100 460 60 3 0 9 1 10 2 0 0 00 0 00 1 80 2 0 15 460 60 3 0 9 1 10 2 3 9 75 11 70 13 50 16 6 20 460 60 3 0 9 1 10 2 4 13 00 23 50 25 30 31 40 35 460 60 3 0 9 1 10 2 6 19 50 23 50 25 30 31 4 35 VUVE150 115 60 1 2 0 1 10 2 0 0 00 0 00 4 00 4 5 15 208 60 1 1 0 1 10 2 0 0 00 0 00 2 00 2 3 15 208 60 1 1 0 1 10 2 3 8 56 41 20 43 20 53 8 60 208 60 1 1 0...

Страница 26: ...wiring diagram ____ Is the piping system clean complete and correct ____ Is unit serviceable See clearance specifications on page 7 ____ Are all the unit access panels secure and in place ____ Is the water flow established and circulating through all the units ____ Is the condensate line properly sized run trapped and pitched ____ Does the indoor blower turn freely without rubbing ____ Has all wor...

Страница 27: ... system unit ventilators include a condensing unit and the instructions provided with the condensing unit will apply to the entire refrigerant system Filters The air filters supplied with Trane UV s are specially designed for high lint content Depending upon room condi tions these filters will normally need to be replaced every 4 to 8 weeks To assure proper unit operation inspect the filters month...

Страница 28: ...t panel 2 Disconnect P trap from drain pan 3 Disconnect fan plug 4 Slide fan board by pulling deck forward Figure 17 CAUTION Equipment Damage Support the fanboard to prevent the deck from sliding too far for ward and falling out of the unit Failure to do so may cause equip ment damage 5 When reinstalling use the same steps in reverse order Motor The fan motor is a permanent split ca pacitor type m...

Страница 29: ...w appropriate steps explained for cartridge as sembly removal 3 If the motor or other internal parts of the actuator is damaged replace the entire actuator assembly Note These hydronic valves are de signed and tested for silent operation However water noise may occur as a result of high water velocity Piping noises may also occur in high temper ature over 212 F systems with insuf ficient water pre...

Страница 30: ... months from shipment Extended Warranty The optional extended warranty is a second through fifth year warranty The time starts at the end of standard 1 year coverage through the fifth year These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start up Warranty Information ...

Страница 31: ...ture setting Start the warm up cycle earlier in the morning to provide appropriate time frame to increase room temperature prior to space occupation X Sensor is mounted on a block wall that is leaking cold air into the room through the mounting holes Relocate sensor X Face and bypass damper or coil valve is malfunctioning Replace malfunctioning component or contact the control s contractor or if T...

Страница 32: ...iliary radiation X Radiation controls malfunctioning Check the operation of the wall fin controls Room too hot X Room sensor is not properly set Reset room sensor temperature X Clogged filter Replace filter X Face and bypass damper or coil valve is malfunctioning Replace malfunctioning component or contact the control s contractor or if Trane controls see CNT SVX04A EN for more information concern...

Страница 33: ...UV SVN03D EN 33 Unit Wiring Field Installed Wiring 120V 1 PH 3 Speed ...

Страница 34: ...34 UV SVN03D EN Unit Wiring End Device Controls 120V 1 PH 3 Speed DX Hot Water ...

Страница 35: ...UV SVN03D EN 35 Unit Wiring End Device Package 480V 3 PH 3 Speed Chilled Water Electric Heat 6 Element page 1 ...

Страница 36: ...36 UV SVN03D EN Unit Wiring End Device Package 480V 3 PH 3 Speed Chilled Water Electric Heat 6 Element page 2 ...

Страница 37: ...UV SVN03D EN 37 Unit Wiring End Device Package 120V 1 PH 3 Speed 4 Pipe Hot Water Chilled Water ...

Страница 38: ...38 UV SVN03D EN Unit Wiring Tracer ZN520 120V 1 PH 3 Speed 4 Pipe Hot Water Chilled Water ...

Страница 39: ...UV SVN03D EN 39 ...

Страница 40: ... change design and specifications without notice Literature Order Number UV SVN03D EN Date October 2007 Supersedes UV SVN03C EN May 2006 Trane A business of American Standard Companies www trane com For more information contact your local district office or e mail us at comfort trane com ...

Отзывы: