System Troubleshooting Chart (Continued)
SYMPTOM
PROBABLE CAUSE
RECOMMENDED ACTION
Q. Economizer will not
1. Economizer connector not
1. Check connector, and connect if necessary.
operate.
plugged into unit wiring
harness
2. Economizer Actuator
2. Verify that 24 VAC is present between ECA terminals 24 VAC and Common.
(ECA) has failed
Place the unit in econ test mode, economizer actuator should drive open.
In any other unit test mode, economizer actuator should drive to minimum
position. If ECA does not drive as specified, replace ECA.
3. Wiring or terminal failure.
3. Check wiring and terminals. Repair or replace if necessary.
4. ECA is defective.
4. Perform the ECA Test Procedures discussed previously.
R. Minimum position
1. Remote Minimum position
1. With the main power off, check the resistance between terminals P
is at zero, cannot
potentiometer has failed.
and P1 at the ECA by rotating the remote minimum position
be adjusted. Economizer
potentiometer knob. Resistance should be 50 to 200 Ohms.
still modulates.
2. Minimum position
2. Rotate the onboard minimum position potentiometer knob.
potentiometer has failed.
If ECA does not drive to different minimum position, replace ECA.
S. Economizer goes to
1. OAS has failed.
1. Check the OAS at connector P8 by disconnecting P8 from J8 on the
minimum position,
RTRM. Check resistance between P8-1 and P8-2, refer to the
and will not modulate.
2. MAS has failed.
Resistance versus Temperature Chart. Replace sensor if necessary.
2. Check the MAS at connector P23 by disconnecting P23 from MAT on
the ECA. "MAT" is marked on the actuator. Check for
resistance between P23-1 and P23-2, refer to the Resistance versus
Temperature Chart. Replace sensor if necessary.
T. Economizer modulates,
1. Comparative enthalpy setup, 1. Check the return air sensor (RAS) at connector P10 by disconnecting
but system does not
RAS or RHS failed.
P10 from RAT on the ECA.
seem to operate as
System is operating using
Check for resistance between P10-1 and P10-2, refer to the
effeciently as in the past.
Referance enthalpy
Resistance versus Temperature Chart. Replace the sensor
if necessary.
Check the return air humidity sensor (RHS) by measuring the
operating current at terminals RAH-1 and RAH-2 on the ECA.
Normal operating current is 4 to 20 milliamps mA.
Note:
The humidity sensors are polarity sensitive, and will not operate
if connected backwards.
2. Referance enthalpy setup,
2. Check the outside humidity sensor (OHS) by measuring the opeating
OHS has failed.
current at terminals OAH-1, and OAH-2 on the ECA. Normal
System is operating using
operating current is 4 to 20 milliamps mA.
dry bulb control.
3. Comparative enthalpy setup, 3. Perform #2 above.
OHS has failed.
System is operating using
dry bulb control.
U. Power Exhaust will
1. Exhaust motor has failed.
1. Check the exhaust fan motor, and replace if necessary.
not operate.
2. XFR has failed.
2. Check the exhaust fan contactor (XFR). Replace if necessary
3. ECA has failed.
3. Perform the ECA Test Procedures discussed previously.
4. XFSP has Failed
4. Perform the Exhaust Fan Setpoint Test Procedures discussed
previously.
V. IGV/ VFD will not
1. RTAM has Failed
1. Perform the RTAM Test Procedures discussed previously.
operate properly
2. IGV / VFD has Failure
2. Check the IGV / VFD
3. Setpoint Failure
3. Perform the IGV / VFD Setpoint Test Procedures discussed
previously.
Содержание Voyager RT-SVX17C-EN
Страница 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Страница 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Страница 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Страница 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Страница 78: ......
Страница 79: ......
Страница 80: ......