36
System Operation (Continued)
Condenser Fan Sequencing Control
The condenser fans are cycled according to the outdoor air
temperature and the number of cooling steps that are operat-
ing. Table 16 lists the temperatures at which the A and B
Condenser Fan Outputs on the RTRM switches the fans
"Off". The fans are switched back "ON" when the outdoor
temperature rises approximately 5° F above the "Off" tem-
perature.
Figure 12 shows the condenser fans as viewed from the top
of the unit facing the control panel. Whenever a condenser
fan is cycled back "On", the condenser fan Outputs A and B
and the compressor steps are de-energized for approxi-
mately 7 seconds to prevent problems with fan windmill.
Table 16
Condenser Fan/Compressor Sequence
Unit Size C om pressor Staging Sequence (N ote 1 C ondenser Fan Output O/A Tem perature (
o
F)
(Tons)
Step 1
Step2
Step 3
Output A
Output B
Fans "Off"
C PR 1*
Fan #2
70
27.5 - 30
Fan #3
90
C PR 1, 2
N/A
Fan #2
-10
Fan #3
60
C PR 1*
Fan #2
65
35
Fan #3
85
C PR 1, 2
N/A
Fan #2
-20
Fan #3
55
C PR 1 **
Fan #2
50
Fan #3, 4
70
40
C PR 2, 3***
Fan #2
20
Fan #3, 4
60
C PR 1, 2, 3
Fan #2
-30
Fan #3, 4
50
C PR 1**
Fan #2
20
Fan #3, 4
60
50
C PR 2, 3***
Fan #2
-10
Fan #3, 4
55
C PR 1, 2, 3
Fan #2
-30
Fan #3, 4
-30
Figure 12
Condenser Fan Location
Note:
1. The Compressor(s) listed under each step are the operating compressors. On 27.5 to 35 ton units
with Lead/Lag, CPR1 will alternate but the fan sequence will remain the same. On 40 and 50 ton units
with Lead/Lag, the compressor(s) in step 2 & 3 will alternate and the fan sequence listed for that step
will be in operation.
2. Conventional thermostat sequence: Y1=CPR1, Y2=CPR2 (40 & 50 CPR 2,3), Y1 + Y2 = CPR1,2 (40 & 50
CPR 1,2,3)
* - Single circuit, manifolded compressors pair.
** - First Stage, Number one refrigeration circuit, Stand alone compressor is “On”.
***- First Stage is “Off”, Number two refrigeration circuit, manifolded compressor pair is “On” operating simulta-
neously.
Содержание Voyager RT-SVX17C-EN
Страница 8: ...8 Figure 1 Unit Dimensions for TC_ TE_ and YC_330 360 and 420 MBH Units Low Heat ...
Страница 9: ...9 Figure 1 continued Unit Dimensions for YC_330 360 and 420 MBH Units High Heat ...
Страница 10: ...10 Figure 1 continued Unit Dimensions for TC_ TE_ and YC_480 and 600 MBH Units Low High Heat ...
Страница 24: ...24 Figure 10 Typical FieldWiring Requirements for CV Control Options ...
Страница 78: ......
Страница 79: ......
Страница 80: ......