1.6.4 Panel Voltage and Frame Ratings
defines the voltage and hp ratings of the frames sizes for the panel. See
for overall and
mounting dimensions.
Panel P2
(B3 - Drive)
Bypass
Non Bypass
FC102/202/322
FC102/202/322
FC302
Volts VAC
HP (KW)
208 & 230
7.5 (5.5) - 15 (11)
7.5 (5.5) - 15 (11)
7.5 (5.5) - 10 (7.5)
460 & 600
15 (11) - 25 (18.5)
15 (11) -25 (18.5)
15 (11) - 20 (15)
Panel P3
(B4 - Drive)
Bypass
Non Bypass
FC102/202/322
FC102/202/322
FC302
Volts VAC
HP (KW)
208
20(15)
20 (15) - 25 (18.5)
15 (11) - 20 (15)
230
20 (15) - 25 (18.5)
460 & 600
30 (22) - 50 (37)
30 (22) - 50 (37)
25 (18.5) - 40 (30)
Panel P4
(C3 - Drive)
Bypass
Non Bypass
FC102/202/322
FC102/202/322
FC302
Volts VAC
HP (KW)
208
25 (18.5) - 40 (30)
30 (22) - 40 (30)
25 (18.5) - 30 (22)
230
30 (22) - 40 (30)
460 & 600
60 (45) - 75 (55)
60 (45) - 75 (55)
50 (37) - 60 (45)
Panel P5)
(C4 - Drive)
Bypass
Non Bypass
FC102/202/322
FC102/202/322
FC302
Volts VAC
HP (KW)
208 & 230
50 (37) - 60 (45)
50 (37) - 60 (45)
40 (30) - 50 (37)
460 & 600
100 (75) - 125 (90)
100 (75) - 125 (90)
75 (55) - 100 (75)
Table 1.4 Panel Voltage and Frame Ratings
1.7 Power Component Functions
1.7.1 Power Fusing
For main panel power fuses, only use the specified fuse or
an equivalent replacement. For drive fuses only use the
specified fuse. See the fuse ratings label on the inside
cover of the unit or
,
and
Main fusing
Main fuses are located ahead of the drive and bypass.
Main fuses are designed to protect the circuitry within the
bypass panel but is not adequate to protect the drive.
Main fuses are dual-element, time-delay types and mount
inside the bypass enclosure.
Drive fusing
Drive fuses are located ahead of the drive and are a fast-
acting type. Drive fuses are standard in all bypass and non-
bypass panels.
5,000 or 100,000 amp SCCR
The bypass panel supplied with a non fusible Main
Disconnect Switch is 5,000 amps short-circuit current rating
(SCCR). The bypass panel supplied with a Fusible
disconnect or circuit breaker is 100,000 amp SCCR. The
non bypass panel supplied with a non-fusible Main
Disconnect is 100,000 amp SCCR. See the panel label for
SCCR rating.
NOTE!
The 600 V circuit breaker option is 5,000 amp (SCCR).
Introduction
Vertical Bypass/Non Bypass Panel
1-6
MG.13.A1.22 - VLT
®
is a registered Danfoss trademark
1
1
Содержание VLT AQUA Drive FC 202 VLT AutomationDrive FC 301
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual Vertical Bypass Non Bypass Panel...
Страница 3: ...Safety Vertical Bypass Non Bypass Panel MG 13 A1 22 VLT is a registered Danfoss trademark...
Страница 45: ...Installation Vertical Bypass Non Bypass Panel 3 28 MG 13 A1 22 VLT is a registered Danfoss trademark 3 3...
Страница 49: ...Start Up Vertical Bypass Non Bypass Panel 4 4 MG 13 A1 22 VLT is a registered Danfoss trademark 4 4...
Страница 88: ...www danfoss com drives MG13A122 130R0264 MG13A122 Rev 2011 08 10...
Страница 89: ......