UV-SVN002-EN
Maintenance
Filters - continued
There are a number of filters available
for use with the Trane Classroom Unit
Ventilators. The following section
explains maintenance and replacement
of these filters.
Each filter is replaced in the manner
previously discussed.
Throwaway Filters
Throwaway filters contain adhesive
coated glass fibers which are enclosed
in a cardboard frame. Remove old
filters from the unit and dispose of the
entire filter. Replace with a new filter
making sure the air flow direction
arrows are pointing toward the dis-
charge end of the unit.
Permanent/Renewable
Polyurethane Filters
Permanent/renewable filters consist of
a polyurethane filter pad enclosed in a
rigid frame. The frame is hinged at the
back with dimple fastener at the front.
With the filter removed, open the
frame, remove the pad and wash in a
mild detergent solution. Allow the pad
to dry and replace in the frame.
Reinstall the filter. Over time, the filter
may wear out. Replacement pads may
be ordered through Trane.
Removal of the Drain Pan
The unit ventilators drain pan is remov-
able for periodic cleaning or easy
access for maintenance/drainage
issues. Use the following
Figures 50-
52,
and the below steps for removing
the drain pan.
1. Turn off power to the unit and remove
the front panel by turning camlocks .
2. Disconnect the condensate drain line.
3. Remove the support plates on each
end by taking out the fastening
screws.
4. Remove the 2 screws on the front
face of the pan to release it.
NOTE:
The drain pan is installed at
an angle to allow drainage. For each
end of the drain pan, remember the
position (top or bottom slot) from
which the fastener was removed.
5. When reinstalling, use the same
Figure 51:
Removal of screws holding
drain pan in place.
Figure 50:
Removal of screws in sup-
port plate of drain pan.
Figure 52:
Slide drain pan out of unit
for inspection/cleaning.
Содержание UV-SVN02B-EN
Страница 32: ...32 UV SVN002 EN Wiring Diagrams Figure 38 Field Installed Controls 120V 1 Speed Unit Mounted Fan Switch...
Страница 33: ...UV SVN002 EN 33 Wiring Diagrams Figure 39 Field Installed Controls 120V 2 Speed Unit Mounted Fan Switch...
Страница 36: ...36 UV SVN002 EN Wiring Diagrams Figure 42 Power Diagram For 208V or 240V 3 Phase 3 Wire Electric Heat...
Страница 38: ...38 UV SVN002 EN Wiring Diagrams Figure 44 Power Diagram For 480V 3 Phase 4 Wire Electric Heat...
Страница 39: ...UV SVN002 EN 39 Wiring Diagrams Figure 45 End Device Package 120V 4 Pipe Hot Water Chilled Water...
Страница 40: ...40 UV SVN002 EN Wiring Diagrams Figure 46 End Device Package 120V Hot Water DX Cooling...
Страница 41: ...UV SVN002 EN 41 Wiring Diagrams Figure 47 208V or 240V 3 Phase 3 Wire Electric Heat DX Cooling...
Страница 50: ...50 UV SVN002 EN Accessories Wall Boxes Figure 59 Vertical wallbox V1 V3 V2 V6 dimensions...