background image

4

BAS-PRC006-EN

The Tracer ZN511 zone controller 
provides digital control of fan coils and 
water-source heat pumps. The Tracer 
ZN511 improves comfort control and 
provides stand-alone or networked 
building automation.

Inputs and outputs

Tracer ZN511 inputs and outputs include:

Analog inputs

: zone temperature, 

entering or leaving water temperature, 
discharge air temperature, zone tem-
perature setpoint, fan mode switch

Binary inputs

: occupancy, conden-

sate overflow, low water temperature, 
low pressure protection, high pres-
sure protection

Outputs

: water-source heat pump: 

compressor 1, compressor 2, two-
position outside air damper, reversing 
valve, fan on/off
Fan coil: fan high, fan medium, fan 
low, 1 cool, 1 heat, two-position 
outside air damper

Generic points

 for use with a Tracer 

Summit building automation system: 
binary input (shared with occupancy), 
binary output (shared with outside air 
damper)

The generic inputs pass information to 
the building automation system. They do 
not affect the operation of the unit. The 
generic binary output is controlled by 
the building automation system and its 
state is not changed by unit operation, 
even under a diagnostic shutdown.

Features

Easy installation

The controller can be installed in existing 
Trane and competitive HVAC equipment 
without major wiring changes, and 
clearly labeled screw terminals ensure 
that wires are connected quickly and 
accurately. A compact enclosure design 
simplifies installation in minimal space.

Entering water temperature sampling

A traditional system using a two-way 
control valve on a fan coil might not 
sense the correct entering water 
temperature during long periods when 
the control valve is closed. The Tracer 
ZN511 solves this problem by opening 
the valve for three minutes to allow the 
water temperature to stabilize before 

the temperature is taken. This feature 
allows the use of two-way control valves 
to provide accurate two-pipe system 
changeover for 1heat/1 cool applications.

Automatic heat/cool mode 
determination

The Tracer ZN511 automatically 
determines whether heating or cooling 
is needed to maintain comfort levels, 
without the need to manually adjust unit 
controls. The controller measures the 
zone temperature and setpoint 
temperature, then uses a proportional/
integral algorithm to maintain zone 
temperature at the setpoint.

Occupied and unoccupied operation

The occupancy input works with a 
motion (occupancy) sensor or time 
clock. A communicated value from a 
building automation system through the 
LonTalk communication link can also be 
used. The input allows the controllers to 
use unoccupied (setback) temperature 
setpoints.

Random start

This feature randomly staggers multiple-
unit start-up to reduce electrical demand 
spikes.

Warm-up and cool-down

This feature is available with the 
installation of an outside air damper. If 
the room temperature drifts too far from 
the setpoint, the controller temporarily 
closes the damper to bring the 
temperature to the desired setpoint as 
quickly as possible.

Manual output test

Pressing the test button on the 
controller exercises all binary outputs in 
sequence. This feature is an invaluable 
troubleshooting tool.

Peer-to-peer communication

Multiple controllers can share data if 
they are bound together. Shared data 
can include setpoint, zone temperature, 
mode, and fan status. Applications 
having more than one unit serving a 
single large space can benefit from this 
feature, which prevents multiple units 
from simultaneously heating and 
cooling.

Interoperability

The Tracer ZN511 conforms to the 
LonMark

®

 Space Comfort Controller 

(SCC) profile and communicates via the 
LonTalk protocol. This allows it to work 
with other control systems that support 
LonTalk and the SCC profile.

Continuous fan or fan-cycling 
operation

Users can choose to have the fan run 
continuously at a given speed, or cycle 
on and off automatically by selecting the 

AUTO

 mode.

Equipment protection

The Tracer ZN511 includes inputs that 
allow for the following equipment 
protection:

• Refrigerant high- and low-pressure 

protection to prevent the unit from 
operating with high/low refrigeration 
pressure levels (heat pump only)

• Compressor minimum on and off tim-

ers to extend compressor life by pre-
venting short cycling (heat pump only)

• A condensate overflow switch to pre-

vent water damage to the building

• Low-temperature detection to prevent 

compressor operation during 
abnormal conditions (heat pump) or 
coil freeze-up (fan coil)

Timed override

The timed override function for after 
hours operation allows users to request 
unit operation by the touch of a button 
on the unit zone sensor. Additionally, 
users can press the 

CANCEL

 button at 

any time to place the unit back into 
unoccupied mode.

Fan status

The controller monitors the fan output 
status as proof of airflow. This method is 
cost effective and commonly used on 
direct-drive fan applications.

Filter maintenance

Filter maintenance status is based on 
the cumulative hours of operation of the 
unit fan. The controller has timers that 
can be reset, and when the time limit 
expires, Tracer Summit software or the 
Rover service tool indicates that unit 
maintenance is recommended.

Tracer ZN511 zone controller

Содержание Tracer ZN511

Страница 1: ...BAS PRC006 EN January 2005 Tracer Controls Tracer ZN511 and ZN521 Zone Controllers...

Страница 2: ...tem via a LonTalk communication link LonTalk allows the controllers to operate in peer to peer configuration and to communicate with other compatible building control systems Trane offers a variety of...

Страница 3: ...4 Inputs and outputs 4 Features 4 Wiring diagram for the ZN511 zone controller 5 Tracer ZN521 zone controller 6 Inputs and outputs 6 Features 6 Wiring diagram for the ZN521 zone controller 8 Network a...

Страница 4: ...rough the LonTalk communication link can also be used The input allows the controllers to use unoccupied setback temperature setpoints Random start This feature randomly staggers multiple unit start u...

Страница 5: ...GND FAN AI1 LED ZN PIN GND ZONE SENSOR SERVICE ANALOG INPUTS COMM5 COMM5 AC POWER GND GND GND 24V BINARY INPUTS BI3 BI2 BI1 BI4 V4 BINARY OUTPUTS 3 BI5 V5 2 1 4 5 6 LED STATUS 5 4 3 2 1 On Cancel 6 H...

Страница 6: ...s to provide accurate two pipe system changeover for 1heat 1 cool applications Automatic heat cool mode determination The Tracer ZN521 automatically determines whether heating or cooling is needed to...

Страница 7: ...tive humidity input An analog input can be configured as a relative humidity input The controller can use this value to support the dehumidification function Active dehumidification This feature keeps...

Страница 8: ...AI3 FAN GND AI1 ZN GND LED SET PIN ZONE SENSOR SERVICE ANALOG INPUTS COMM5 COMM5 AC POWER 24V 24V GND 24V BINARY INPUTS BI3 BI1 BI2 BI4 BINARY OUTPUTS 2 1 4 3 7 6 5 8 9 LED STATUS 10 5 4 3 2 1 On Canc...

Страница 9: ...cation on the LonTalk communication link Figure 3 Tracer zone controllers network architecture Building control unit BCU Tracer Summit PC workstation Unit ventilator Water source heat pump Zone sensor...

Страница 10: ...sor options Figure 4 Zone sensors compatible with Tracer zone controllers BAS order number Use Fan Zone Timed override buttons Comm jack High Med Low Auto Off Setpoint thumbwheel Temperature sensor On...

Страница 11: ...C Relative humidity From 5 to 95 noncondensing Agency listings compliance CE Immunity EN 50082 1 1997 EN 50082 2 1995 CE Emissions EN 50081 1 1992 CISPR 22 UL and C UL listed Energy management system...

Страница 12: ...ght to change design and specifications without notice Literature Order Number BAS PRC006 EN File Number PL ES BAS 000 PRC006 0105 Supersedes February 2002 The Trane Company An American Standard Compa...

Отзывы: