BAS-SVN141D-EN
7
Step 3: Install the UC400 2H/2C and Air-Fi
®
Wireless for Non-Trane RTUs
Step 3: Install the UC400 2H/2C and Air-Fi
®
Wireless for Non-Trane RTUs
If required for this site, install the UC400 2H/2C and Air-Fi Wireless on Non-Trane
equipment. For more information, see Tracer UC400 Pre-programmed for RTU or Heat
Pump (X39641251-01B). The point list below is for your convenience.
Note:
Ensure Air-Fi
®
Wireless and zone sensors are addressed per the submittal.
Table 2.
Analog inputs
Label Functions
AI1
Zone Temperature
AI2
Zone Temperature Setpoint
AI4
Discharge Air Temp
AI5
Outdoor Air Temp
Table 3.
Binary inputs
Label Functions
BI1
Occupancy Input
Table 4.
Binary outputs
Label Functions
B01
BO1 Supply Fan
B04
Cool stage 1 (Y
1
)
BO5
Cool stage 2 (Y
2
)
BO6
Heat stage 1 (W
1
)
BO7
Heat stage 2 (W
2
)
BO8
Not Used
BO9
Not Used