RT-PRC017-EN
34
Performance
Data
Table PD-21 - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4620
651
0.51
694
0.59
740
0.68
787
0.79
831
0.89
869
0.99
901
1.08
931
1.17
959
1.26
986
1.35
5200
722
0.70
761
0.79
798
0.88
841
1.00
883
1.11
923
1.23
958
1.35
989
1.45
1017
1.55
1045
1.65
5780
793
0.94
830
1.04
863
1.14
898
1.25
937
1.37
975
1.51
1011
1.64
1045
1.77
1075
1.89
1103
2.01
6350
865
1.23
899
1.34
930
1.45
961
1.56
994
1.68
1028
1.82
1063
1.96
1097
2.11
1129
2.26
1159
2.40
6930
937
1.57
970
1.70
999
1.81
1027
1.93
1055
2.05
1085
2.19
1118
2.34
1150
2.50
1181
2.66
1211
2.82
2.24 Nom kW Over-Sized Motor & High Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
400
425
450
475
500
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr & Drive
4620
1011
1.43
1036
1.52
1059
1.61
1082
1.69
1104
1.78
1127
1.87
1149
1.96
1170
2.05
1191
2.14
1212
2.24
5200
1070
1.75
1094
1.85
1117
1.95
1139
2.05
1161
2.15
1182
2.24
1203
2.35
1222
2.44
1243
2.54
1262
2.64
5780
1128
2.12
1152
2.23
1176
2.34
1198
2.45
1219
2.56
1241
2.67
1261
2.78
1280
2.88
1299
2.99
1319
3.11
6350
1186
2.53
1210
2.65
1233
2.78
1256
2.90
1278
3.03
1298
3.15
1319
3.27
-
-
-
-
-
-
6930
1239
2.97
1267
3.13
1291
3.27
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.24 Nom kW Over-Sized Motor & High Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.
Table PD-21a - Belt Drive Evaporator Fan Performance - YSC102AD*H - High Heat - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Std Motor & Low Static Drive
2 HP Standard Motor & Drive
2720
651
0.69
694
0.79
740
0.92
787
1.06
831
1.20
869
1.33
901
1.45
931
1.57
959
1.69
986
1.81
3060
722
0.94
761
1.06
798
1.18
841
1.34
883
1.49
923
1.65
958
1.81
989
1.95
1017
2.08
1045
2.22
3400
793
1.26
830
1.40
863
1.53
898
1.67
937
1.84
975
2.02
1011
2.20
1045
2.37
1075
2.54
1103
2.69
3740
865
1.65
899
1.80
930
1.94
961
2.09
994
2.26
1028
2.44
1063
2.63
1097
2.83
1129
3.03
1159
3.22
4080
937
2.11
970
2.27
999
2.43
1027
2.59
1055
2.75
1085
2.94
1118
3.14
1150
3.35
1181
3.57
1211
3.78
3 HP Over-Sized Motor & Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Std Motor & Drive
3 HP Over-Sized Motor & Drive
2720
1011
1.92
1036
2.04
1059
2.15
1082
2.27
1104
2.39
1127
2.51
1149
2.64
1170
2.75
1191
2.88
1212
3.00
3060
1070
2.35
1094
2.48
1117
2.61
1139
2.75
1161
2.88
1182
3.01
1203
3.15
1222
3.27
1243
3.41
1262
3.54
3400
1128
2.84
1152
2.99
1176
3.14
1198
3.29
1219
3.43
1241
3.58
1261
3.73
1280
3.87
1299
4.02
1319
4.17
3740
1186
3.40
1210
3.56
1233
3.73
1256
3.90
1278
4.06
1298
4.22
1319
4.39
-
-
-
-
-
-
4080
1239
3.99
1267
4.20
1291
4.39
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP Over-Sized Motor & Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty
Will Not Be Affected.