Model
Number
Description
Digit 1 - Unit Function
Y = DX Cooling, Gas Heat
Digit 2 - Efficiency
S = Standard Efficiency
Digit 3 - Airflow
C = Convertible
Digits 4,5,6 - Nominal Gross Cooling
Capacity (MBh)
kW
Tons
060 = 17.6
5
072 = 21.1
6
090 = 26.4
7.5
102 = 29.9
8.5
120 = 35.1
10
Digit 7 - Major Design Sequence
A = First
Digit 8 - Unit Voltage
D = 380-415/50/3
Digit 9 - Unit Controls
R = ReliaTel
™
Microprocessor
Digit 10 - Heating Capacity
L = Low
H = High
Digit 11 - Minor Design Sequence
A = First Sequence
Y
S
C 060 A
D
R
L
A
**
C
0
0
0
0
0
0
0
0
0
0
1
1
2
3 4,5,6 7
8 9
10
11 12,13 14
15
16 17
18
19
20 21
22
23
24
25
Digits 12, 13 - Service Sequence
**
=
Factory Assigned
Digit 14 - Fresh Air Selection
0 = No Fresh Air
A = Manual Outside Air Damper 0-50%
B = Motorized Outside Air Damper 0-50%
C = Economizer, Dry Bulb 0-100%
without Barometric Relief
D = Economizer, Dry Bulb 0-100%
with Barometric Relief
E = Economizer, Reference Enthalpy
0-100% without Barometric Relief
F = Economizer, Reference Enthalpy
0-100% with Barometric Relief
G = Economizer, Comparative Enthalpy
0-100% without Barometric Relief
H = Economizer, Comparative Enthalpy
0-100% with Barometric Relief
Digit 15 - Supply Fan/Drive Type/Motor
0 = Standard Drive
1 = Oversized Motor
Digit 16 - Hinged Service AccessFilters
0 = Standard Panels/Standard Filters
A = Hinged Access Panels/Standard Filters
B = Standard Panels/50 mm (2”)
Pleated Filters
C = Hinged Access Panels/50 mm 2”
Pleated Filters
Digit 17 - Condenser Coil Protection
0 = Standard Coil
1 = Standard Coil with Hail Guard
2 = Epoxy Coated Condenser Coil
3 = Epoxy Coated Condenser Coil with
Hail Guard
Digit 18 - Through the Base Provisions
0 = No Through the Base Provisions
Digit 19 - Disconnect/Circuit Breaker/Phase
Monitor (3 phase only)
0 = No Disconnect or Circuit Breaker
3 = Phase Monitor Only (No Disconnect,
No Circuit Breaker)
Digit 20 - Convenience Outlet
0 = No Convenience Outlet
Digit 21 - Communications Options
0 = No Communications Interface
1 = Comm-3/4 Communications Interface
2 = Comm-5 Communications Interface
Digit 22 - Refrigeration System Option
0 = Standard Refrigeration System
Digit 23 - Refrigeration Controls
0 = No Refrigeration Control
Digit 24 - Smoke Detector
0 = No Smoke Detector
Digit 25 - Monitoring Controls
0 = No Monitoring Control
1 = Clogged Filter Switch
2 = Fan Failure Switch
3 = DischargeAir Sensing Tube
4 = Clogged Filter Switch and Fan Fail
Switch
5 = Clogged Filter Switch and Discharge
Air Sensing Tube
6 = Fan Fail Switch and Discharge Air
Sensing Tube
7 = Clogged Filter and Fan Fail Switches
and Discharge Air Sensing Tube