![Trane Precedent YSC060-120 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/trane/precedent-ysc060-120/precedent-ysc060-120_user-manual_1149474026.webp)
RT-PRC017-EN
26
Performance
Data
Table PD-13 - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Standard Motor
&
Drive
3260
579
0.24
639
0.30
690
0.35
736
0.40
780
0.46
824
0.52
866
0.59
907
0.65
947
0.71
986
0.78
3670
636
0.33
692
0.39
741
0.46
784
0.51
826
0.57
865
0.64
903
0.71
943
0.78
979
0.84
1017
0.91
4080
696
0.45
746
0.51
794
0.58
836
0.64
874
0.70
911
0.77
947
0.84
982
0.92
1017
1.00
1051
1.07
4490
757
0.58
802
0.64
847
0.72
888
0.80
924
0.86
959
0.93
993
1.00
1026
1.08
1058
1.17
1089
1.25
4890
818
0.74
858
0.81
900
0.88
940
0.97
977
1.05
1010
1.13
1042
1.20
1073
1.27
1104
1.36
1133
1.45
1.12 Nom kW Standard Motor & Drive
1.50 Nom kW Over-Sized Motor
& High Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
CFM
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor
& Hi Static Drive
3260
1023
0.84
1059
0.92
1093
0.98
1126
1.06
1156
1.12
3670
1053
0.98
1087
1.06
1121
1.13
1153
1.21
1185
1.29
4080
1085
1.15
1119
1.23
1151
1.30
1182
1.38
1214
1.47
4490
1122
1.34
1153
1.42
1184
1.50
1215
1.59
-
-
4890
1163
1.54
1192
1.64
1221
1.72
-
-
-
-
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1.12 Nom kW Std Mtr
& Hi Static Drive
←←←←←
Table PD-13a - Belt Drive Evaporator Fan Performance - YSC072AD*H - High Heat - Horizontal Configuration - (IP)
External Static Pressure (Inches of Water)
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor
&
Drive
1920
579
0.33
639
0.40
690
0.47
736
0.54
780
0.62
824
0.70
866
0.79
907
0.87
947
0.95
986
1.04
2160
636
0.45
692
0.53
741
0.61
784
0.68
826
0.76
865
0.85
903
0.95
943
1.04
979
1.13
1017
1.23
2400
696
0.60
746
0.68
794
0.78
836
0.86
874
0.94
911
1.03
947
1.13
982
1.23
1017
1.34
1051
1.44
2640
757
0.78
802
0.86
847
0.96
888
1.07
924
1.16
959
1.25
993
1.35
1026
1.45
1058
1.56
1089
1.68
2880
818
1.00
858
1.08
900
1.18
940
1.30
977
1.41
1010
1.51
1042
1.61
1073
1.71
1104
1.82
1133
1.94
1-1/2 HP Standard Motor & Drive
2 HP Over-Sized Motor
& Hi Static Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Hi Static Drive
1920
1023
1.13
1059
1.23
1093
1.32
1126
1.42
1156
1.51
2160
1053
1.32
1087
1.42
1121
1.52
1153
1.62
1185
1.72
2400
1085
1.54
1119
1.65
1151
1.75
1182
1.85
1214
1.96
2640
1122
1.79
1153
1.90
1184
2.01
1215
2.13
-
-
2880
1163
2.07
1192
2.19
1221
2.31
-
-
-
-
2 HP Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
1-1/2 HP Std Motor
& Hi Static Drive
←←←←←
Содержание Precedent YSC060-120
Страница 1: ...Packaged Gas Electric Rooftop Units Precedent YSC060 120 50 Hz RT PRC017 EN February 2004 ...
Страница 45: ...45 RT PRC017 EN Dimensional Data YSC060 All dimensions are in inches millimeters YSC060 ...
Страница 57: ...57 RT PRC017 EN ...
Страница 58: ...RT PRC017 EN 58 ...
Страница 59: ...59 RT PRC017 EN ...