![Trane Pivot BAYSTAT814 Series Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/trane/pivot-baystat814-series/pivot-baystat814-series_installation-operation-and-maintenance-manual_1150351009.webp)
BAS-SVX078E-EN
9
–
Choose a mounting location that ensures adequate signal strength from the unit to the Internet
router.
–
Do not mount the unit more than 30 feet from the wireless router.
–
For strong signal strength, ensure there are no more than three (3) interior walls between the
unit and the router.
–
Do not mount the unit in areas where electromagnetic emissions from other devices, appliances,
or where wiring can interfere with communication to the unit.
–
Do not mount the unit in recessed areas, near metal objects, or near structures.
–
Do not have metal obstructions, concrete or brick walls between the unit and the router.
Do not mount the unit closer than 2 inches to any pipes, duct work, or other metal obstructions.
•
Wired (Ethernet IEEE 802.3)
–
The Pivot thermostat can be connected to the Internet using the built-in RJ-45 connector. When
using a wired connection, verify that a CAT 5, or better, Ethernet cable with an RJ-45 plug is
present from the unit to the router.
Mounting
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
When it is necessary to work with live electrical components, have a qualified licensed
electrician or other individual who has been properly trained in handling live electrical
components perform these tasks.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury.
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Verify that
no power is present with a voltmeter.
Note:
If replacing an existing unit, remove the unit from the wall, record the color/terminal markings of
each wire, and disconnect the wires from old unit. Do not let the wires fall back through the wall.
1. Turn off all power to cooling/heating equipment.
2. Remove the Pivot thermostat from the box and carefully pry the sub-base away from the unit with a
flat-blade screwdriver.
3. Route the wires through the opening of the sub-base.
4. If using a wired Internet connection, route the Ethernet cable through the opening.
5. Place the sub-base against the wall in the desired location and mark the mounting holes as shown
below.