![Trane Pivot BAYSTAT814 Series Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/trane/pivot-baystat814-series/pivot-baystat814-series_installation-operation-and-maintenance-manual_1150351020.webp)
20
BAS-SVX078E-EN
Table 3.
Group 3 sensor settings
Menu Item
Options [Default]
Description
Use Internet Weather**
[No]*, [Yes]
This menu item is asking if the installer wants to
use Internet Weather as a temperature source for
lockouts during heat pump operation, temperature
overrides for outdoor air temperature ventilation, or
outdoor temperature for Optimal Start/Stop
calculations.
See Outdoor Air Sensor Priority section below if
both Internet Weather and a wired OAT sensor are
desired as primary and secondary source for
outdoor air temperature.
*During initial installer setup, the only choice will be
‘No’ because an Internet connection does not yet
exist and therefore Internet Weather has not yet
been set up. After an Internet connection is made
and Internet Weather is set up (via the User Setup
Wizard on the Settings Menu), the default changes
to Yes, and No is also a choice.
Even if No is selected, Internet Weather values will
still be available to display on the Home screen on
the Outdoor Temperature widget. To display
Internet Weather on the Outdoor Temperature
widget, navigate to
Home > Menu > Settings >
Thermostat > Temperature Calibration > Select
Internet Weather
under Outdoor Sensor column.
Configure ODT Input**
[None]
Outdoor Air Temperature
Other Temperature
Binary Input
Outdoor Air Temperature and Other Temperature
requires wiring a 10K Type 2 thermistor sensor to
ODT Input. See Optional Equipment section for
sensor part numbers.
Outdoor Air Temperature (OAT) will be used for
temperature lockouts, overrides, and Optimal S/S
calculations.
The Outdoor Air Temperature value can also be
displayed on the Home screen Outdoor
Temperature widget if enabled. To display ODT
Input, Outdoor Air Temperature value on the
Outdoor Temperature widget, navigate to
Home >
Menu > Settings > Thermostat > Temperature
Calibration > Select Local OAT Sensor
under
Outdoor Sensor column.
Note:
Internet forecast and sky conditions in the
widget will continue to be displayed in the
widget with temperature from ODT input.
Other Temperature can be selected to display a
temperature other than outdoor air. The value can
be displayed on the thermostat Home screen as a
widget, and on the mobile app. In addition, the
temperature can be set up in the mobile app for
high/low alerts. See Alerts section in User Guide. It
is not used for lockouts, overrides or any other
calculation or control.
Binary Input responds to an open or closed
external contact such as a mechanical relay, and
displays the state on the thermostat Home screen
and on the mobile app. In addition, either binary
state can be set up as an alert. See Alerts section
in the User Guide.
ODT Other Temperature Input Label
[Input ODT], Installer entered name
Pressing the Input ODT button brings up a keypad
allowing the installer to name the button, such as
“Discharge Air”. The input value will be available on
a widget that can be displayed on the Home screen
by navigating to
Home > Menu > Settings >
Screen > Screen Layout > [button label]
, and in
the mobile app. The value is not used for lockouts
or any other control.
Note:
Special characters exist that cannot be used
in the name.