PTAC-PRC001-EN

20

Mechanical
Specifications

Unit Chassis

Each unit will be slide-out design shipped
with room cabinet front installed. Unit
chassis will have the ability to be installed
with zero reversing clearance from
finished floor. An electrical power cord
will be included with chassis and
installed by the manufacturer to assure
proper NEMA 6 or 7 configuration and
UL approved length. Unit will be tested
for conformance to ASTME water
infiltration specification ASTME 331-86
which assures no water infiltration when
tested at eight inches of rain per hour at
63 mph wind for 15 minutes.

Room Cabinet/Front Panel

The room cabinet/front panel will have
sloped discharge so that obstructions are
not placed on unit. The discharge
conditioned air can be directed into the
room at an angle of 15 to 40 degrees
from the vertical position. The discharge
grille will be a polycarbonate material to
resist bending, cracking, rusting and
corrosion. The front panel will be able to
be field secured to chassis to inhibit
tampering. Cabinet depth will be seven-
inch to minimize unit’s impact on room
space.

Filter

The filter will be accessible without
removing room front. Filter material will
be nylon mesh, permanent cleanable.

Condenser/Evaporator Fans

One direct drive with a permanent split
capacitor two-speed motor. The
condenser fan will be propeller type and
the indoor evaporator fan will be a
centrifugal blower type.

Cooling Condensate Removal

High humidity conditions may call for
condensate removal system. The
outdoor fan diffuses water directly on to
the outdoor condenser coil for rapid
evaporation and increased cooling
efficiency.

Compressor

The compressor will be hermetically
sealed, internally isolated, rotary-type
and permanently mounted on rubber
isolators. No removal or adjustment of
compressor hold down bolts will be
required during installation.

Coils

Coils will have rifled copper tubing
expanded into rippled-edge louvered
aluminum fins.

Heat Pumps

Heat pumps will include a changeover
thermostat that senses an outside coil
switch-over temperature of 25°F,
lock-open refrigerant valve during heat
pump operation, temperature-activated
defrost drain and automatic emergency
heat operation to override the heat
pump’s changeover thermostat and
bring on electric resistance heaters in the
event of a sealed system failure. Unit will
not operate compressor and electric
heaters simultaneously.

Outside Air Damper/Vent Control

The vent control will allow 65 to 70 cfm
of fresh air to be drawn into the room.
This fresh air can provide ventilation
when the blower is operating. To obtain
access to the vent control, remove the
cabinet front. The vent control lever is on
the left side of the chassis. The control
lever must be rotated to either open or
close the damper. Actual vent cfm
performance will vary due to application
and installation conditions.

Filtered Outdoor Air Intake

The outdoor air intake will be filtered
with a talc-filled polypropylene filter that
will reduce dust from coming into the
room.

Paint System Corrosion Protection

All  units are built with hot-dipped
galvanized steel. Metal parts are then run
through a six-stage zinc phosphate
cleaner/pretreatment, painted with a
cathodic electroplating of an epoxy resin
paint and baked for 20 minutes at 350°F.
All exterior parts that are exposed to
sunlight get an additional coating of
polyester and are baked for 20 minutes
at 350°F for additional protection from
the fading effects of ultraviolet rays. This
paint process makes the unit highly
resistant to normal rust, corrosion and
fading. It is the best paint process in the
industry today.

Corrosion-Resistant Chassis (Standard
Option)

The condenser coil is painted using
cathodic electrocoat. The bottom ¼ of the
compressor is coated with a water borne
resin. The outdoor side of interior parts
are top coated, in addition, the base pan
is cathodic electrocoated.

Содержание Packaged TerminalAir Conditioners & Heat Pumps

Страница 1: ...PackagedT erminalAir Conditioners Heat Pumps PTAC PRC001 EN October 2000...

Страница 2: ...oners PTACs and heat pumps are ideally suited for offices apartments hotels motels and institutional homes Key benefits which make the units a wise choice are Energy efficiency Reliability Quiet opera...

Страница 3: ...efits Application Considerations Selection Procedure Model Number Description Performance Data Cool and Heat Performance Electric Power Power ConnectionWiring Dimension andWeights Mechanical Specifica...

Страница 4: ...mperatures of 40 F or below the unit activates the fan motor and either the electric resistance heater or the hydronic heater to help prevent pipes or fixtures from freezing This also overrides front...

Страница 5: ...seven inch depth one of the shallowest silhouettes in the industry today To inhibit tampering the front can be secured to the chassis with hidden screws Our unit s new stylish design and neutral color...

Страница 6: ...nelWall Installation PanelWall and BlockVeneer Installation On applications not requiring subbase or leveling legs unit may be flush mounted to floor Sleeve Installation Data Framing forWall Case Fram...

Страница 7: ...Door G Hydronic with Power Door J Power Door K Condensate Pump with PowerVent L Condensate Pump with Power Door Stock Style Models PTEC0701GCA PTEC0901GCA PTEC1201GCA PTEC1501GCA PTEC1501JCA PTHC0701G...

Страница 8: ...05 1110 1120 1120 1485 1505 1505 EER 11 5 11 5 11 5 11 2 11 2 11 2 10 7 10 7 10 7 9 3 9 3 9 3 Unit without Electric Heater Min Circuit Ampacity 2 4 4 0 4 0 3 6 5 1 5 1 4 4 7 3 7 3 5 7 8 4 8 4 7 4 cfm...

Страница 9: ...3 2 3 2 3 2 3 1 3 1 3 1 2 8 2 8 2 8 2 42 5500 5700 5700 7200 7300 7300 9800 10000 10000 12200 12300 12300 37 4900 5100 5100 6400 6500 6500 9000 9200 9200 11200 11300 11300 32 4300 4500 4500 5600 5700...

Страница 10: ...55 3280 34 8935 3060 34 73 80 10585 4790 45 10020 4580 46 9420 4365 46 8795 4145 47 85 10450 5875 56 9880 5665 57 9270 5445 59 8640 5230 61 75 11265 8715 77 10610 8410 79 9875 8070 82 9000 7675 85 61...

Страница 11: ...55 3480 36 9135 3260 36 73 80 10785 4990 46 10220 4780 47 9620 4565 47 8995 4345 48 85 10650 6075 57 10080 5865 58 9470 5645 60 8840 5430 61 75 11365 8815 78 10710 8510 79 9975 8170 82 9100 7775 85 61...

Страница 12: ...0 34 73 80 10480 4705 45 9920 4495 45 9315 4275 46 8690 4050 47 85 10345 5730 55 9775 5520 56 9165 5300 58 8535 5075 59 75 11165 8615 77 10510 8310 79 9775 7970 82 8900 7575 85 61 80 11120 10110 91 10...

Страница 13: ...0 3445 36 9035 3220 36 73 80 10680 4905 46 10120 4695 46 9515 4475 47 8890 4250 48 85 10545 5930 56 9975 5720 57 9365 5500 59 8735 5275 60 75 11365 8815 78 10710 8510 79 9975 8170 82 9100 7775 85 61 8...

Страница 14: ...4991 1 88 1 89 0 66 16596 15061 14068 12584 19212 16006 16165 13519 20173 17689 16999 15158 2 00 2 10 0 76 16751 15195 14199 12696 19268 16142 16212 13635 20387 17846 17179 15293 2 13 2 32 0 85 16884...

Страница 15: ...its without electric heaters is 15 amps Overcurrent protection on 265 volt models must be cartridge style time delay fuses included and factory installed on Trane chassis 4 Total watts for 7 000 and 9...

Страница 16: ...bottom of sleeve Bottom drain to be located by customer Drain kit shipped separate 4 Unit provides 20 percent outside air 5 Detachable cord ships attached to unit Cord can be removed for direct attac...

Страница 17: ...17 PTAC PRC001 EN Dimension and Weights Field Supplied Extension...

Страница 18: ...finished interior wall Notes 1 This kit completely encloses all plumbing and coils but still allows easy access to controls 2 The chassis can slide out for easy service without removing hydronic plum...

Страница 19: ...ct extension kit are possible options These kits transfer air from one room to another yet allow different air flows for the rooms airflow distribution can be adjusted from 65 45 to 80 20 FrontView Du...

Страница 20: ...ring installation Coils Coils will have rifled copper tubing expanded into rippled edge louvered aluminum fins Heat Pumps Heat pumps will include a changeover thermostat that senses an outside coil sw...

Страница 21: ...ingTerminals The LS IN terminals will provide a connection for a switch that can be added to close the circuit and lockout the compressor and electric heat when the power company or energy management...

Страница 22: ...be attached to the transition piece to carry up to 40 percent of the conditioned air to the adjoining room Powered OutsideVent and Damper Kit An optional power vent kit can be installed to increase cf...

Страница 23: ...urity Key Locks The installation of Trane s security key locks helps prevent tampering of the controls used to set temperature heating and cooling functions Locks are available for all PTAC models Rem...

Страница 24: ...ssor or connecting tubing which proves to be defective due to workmanship or materials Limited Second through FifthYear Warranty During the 2nd through 5th year Trane will provide free of charge funct...

Страница 25: ...formation contact your local distributor dealer local district office or e mail us at comfort trane com SinceTheTrane Company has a policy of continuous product and product data improvement it reserve...

Отзывы: