background image

13

PTAC-PRC001-EN

Performance
Data

Table PD-7 — PTHC Heat Pump — 230/265V

WBT Ent

DBT Ent

Outdoor Temperature (°F)

Nominal

Indoor

Indoor

85

95

105

115

Unit

Coil

Coil

Total

Sen

%

Total

Sen

%

Total

Sen

%

Total

Sen

%

Size

(°F)

(°F)

Btu

Btu

SH

Btu

Btu

SH

Btu

Btu

SH

Btu

Btu

SH

75

6780

5795

85

6480

5645

87

6130

5765

94

5810

5630

97

61

80

7030

7030

100

6765

6765

100

6370

6370

100

6080

6080

100

85

7305

7305

100

7130

7130

100

6845

6845

100

6420

6420

100

75

7540

4105

54

7255

4240

58

6780

4250

63

6390

4100

64

07

67

80

7445

5485

74

*7100

5350

75

6760

5395

80

6370

5275

83

85

7490

6670

89

7205

6545

91

6790

6370

94

6430

6430

100

75

8435

2935

35

7985

2900

36

7585

2765

36

7170

2620

37

73

80

8345

4080

49

7975

3950

50

7515

3945

52

7110

3810

54

85

8250

5385

65

7850

5095

65

7445

4945

66

7040

4805

68

75

8490

6320

74

8040

6100

76

7550

5860

78

7055

5620

80

61

80

8425

7375

88

7985

7145

89

7515

6905

92

7010

6990

100

85

8485

8485

100

8120

8120

100

7725

7725

100

7305

7305

100

75

9620

5105

53

9160

4975

54

8560

4700

55

7985

4600

58

09

67

80

9505

6090

64

*9000

5860

65

8450

5685

67

7875

5370

68

85

9345

7285

78

8910

7145

80

8295

6870

83

7720

6600

85

75

10810

3875

36

10250

3665

36

9650

3445

36

9035

3220

36

73

80

10680

4905

46

10120

4695

46

9515

4475

47

8890

4250

48

85

10545

5930

56

9975

5720

57

9365

5500

59

8735

5275

60

75

11365

8815

78

10710

8510

79

9975

8170

82

9100

7775

85

61

80

11320

10310

91

10675

9990

94

9915

9625

97

9210

9210

100

85

11605

11605

100

11065

11065

100

10400

10400

100

9705

9705

100

75

12870

7010

54

12305

6770

55

11420

6405

56

10540

6050

57

12

67

80

12730

8430

66

*12000

8125

68

11215

7805

70

10300

7470

73

85

12525

9915

79

11905

9660

81

11005

9315

85

10080

8975

89

75

14535

5160

36

13745

4865

35

12940

4570

35

12025

4245

35

73

80

14360

6620

46

13560

6330

47

12740

6030

47

11730

5675

48

85

14170

8085

57

13390

7800

58

12470

7500

60

11450

7120

62

75

13255

10255

77

12510

9890

79

11605

9470

82

10660

9015

85

61

80

13155

11955

91

12370

11550

93

11430

11085

97

10805

10805

100

85

13475

13475

100

12790

12790

100

11995

11995

100

11365

11365

100

75

15020

8200

55

14360

7920

55

13290

7440

56

12225

6975

57

15

67

80

14835

9805

66

*14000

9440

67

13030

9045

69

12020

8650

72

85

14570

11490

79

13785

11170

81

12685

10730

85

11820

10420

88

75

16835

6025

36

16090

5740

36

15115

5385

36

14010

4920

35

73

80

16740

7745

46

15845

7410

47

14825

7005

47

13640

6555

48

85

16500

9395

57

15570

9045

58

14520

8690

60

13395

8305

62

*These capacities are based on ARI rating point 80/67 entering air temperature, 95°F outdoor ambient.

Содержание Packaged TerminalAir Conditioners & Heat Pumps

Страница 1: ...PackagedT erminalAir Conditioners Heat Pumps PTAC PRC001 EN October 2000...

Страница 2: ...oners PTACs and heat pumps are ideally suited for offices apartments hotels motels and institutional homes Key benefits which make the units a wise choice are Energy efficiency Reliability Quiet opera...

Страница 3: ...efits Application Considerations Selection Procedure Model Number Description Performance Data Cool and Heat Performance Electric Power Power ConnectionWiring Dimension andWeights Mechanical Specifica...

Страница 4: ...mperatures of 40 F or below the unit activates the fan motor and either the electric resistance heater or the hydronic heater to help prevent pipes or fixtures from freezing This also overrides front...

Страница 5: ...seven inch depth one of the shallowest silhouettes in the industry today To inhibit tampering the front can be secured to the chassis with hidden screws Our unit s new stylish design and neutral color...

Страница 6: ...nelWall Installation PanelWall and BlockVeneer Installation On applications not requiring subbase or leveling legs unit may be flush mounted to floor Sleeve Installation Data Framing forWall Case Fram...

Страница 7: ...Door G Hydronic with Power Door J Power Door K Condensate Pump with PowerVent L Condensate Pump with Power Door Stock Style Models PTEC0701GCA PTEC0901GCA PTEC1201GCA PTEC1501GCA PTEC1501JCA PTHC0701G...

Страница 8: ...05 1110 1120 1120 1485 1505 1505 EER 11 5 11 5 11 5 11 2 11 2 11 2 10 7 10 7 10 7 9 3 9 3 9 3 Unit without Electric Heater Min Circuit Ampacity 2 4 4 0 4 0 3 6 5 1 5 1 4 4 7 3 7 3 5 7 8 4 8 4 7 4 cfm...

Страница 9: ...3 2 3 2 3 2 3 1 3 1 3 1 2 8 2 8 2 8 2 42 5500 5700 5700 7200 7300 7300 9800 10000 10000 12200 12300 12300 37 4900 5100 5100 6400 6500 6500 9000 9200 9200 11200 11300 11300 32 4300 4500 4500 5600 5700...

Страница 10: ...55 3280 34 8935 3060 34 73 80 10585 4790 45 10020 4580 46 9420 4365 46 8795 4145 47 85 10450 5875 56 9880 5665 57 9270 5445 59 8640 5230 61 75 11265 8715 77 10610 8410 79 9875 8070 82 9000 7675 85 61...

Страница 11: ...55 3480 36 9135 3260 36 73 80 10785 4990 46 10220 4780 47 9620 4565 47 8995 4345 48 85 10650 6075 57 10080 5865 58 9470 5645 60 8840 5430 61 75 11365 8815 78 10710 8510 79 9975 8170 82 9100 7775 85 61...

Страница 12: ...0 34 73 80 10480 4705 45 9920 4495 45 9315 4275 46 8690 4050 47 85 10345 5730 55 9775 5520 56 9165 5300 58 8535 5075 59 75 11165 8615 77 10510 8310 79 9775 7970 82 8900 7575 85 61 80 11120 10110 91 10...

Страница 13: ...0 3445 36 9035 3220 36 73 80 10680 4905 46 10120 4695 46 9515 4475 47 8890 4250 48 85 10545 5930 56 9975 5720 57 9365 5500 59 8735 5275 60 75 11365 8815 78 10710 8510 79 9975 8170 82 9100 7775 85 61 8...

Страница 14: ...4991 1 88 1 89 0 66 16596 15061 14068 12584 19212 16006 16165 13519 20173 17689 16999 15158 2 00 2 10 0 76 16751 15195 14199 12696 19268 16142 16212 13635 20387 17846 17179 15293 2 13 2 32 0 85 16884...

Страница 15: ...its without electric heaters is 15 amps Overcurrent protection on 265 volt models must be cartridge style time delay fuses included and factory installed on Trane chassis 4 Total watts for 7 000 and 9...

Страница 16: ...bottom of sleeve Bottom drain to be located by customer Drain kit shipped separate 4 Unit provides 20 percent outside air 5 Detachable cord ships attached to unit Cord can be removed for direct attac...

Страница 17: ...17 PTAC PRC001 EN Dimension and Weights Field Supplied Extension...

Страница 18: ...finished interior wall Notes 1 This kit completely encloses all plumbing and coils but still allows easy access to controls 2 The chassis can slide out for easy service without removing hydronic plum...

Страница 19: ...ct extension kit are possible options These kits transfer air from one room to another yet allow different air flows for the rooms airflow distribution can be adjusted from 65 45 to 80 20 FrontView Du...

Страница 20: ...ring installation Coils Coils will have rifled copper tubing expanded into rippled edge louvered aluminum fins Heat Pumps Heat pumps will include a changeover thermostat that senses an outside coil sw...

Страница 21: ...ingTerminals The LS IN terminals will provide a connection for a switch that can be added to close the circuit and lockout the compressor and electric heat when the power company or energy management...

Страница 22: ...be attached to the transition piece to carry up to 40 percent of the conditioned air to the adjoining room Powered OutsideVent and Damper Kit An optional power vent kit can be installed to increase cf...

Страница 23: ...urity Key Locks The installation of Trane s security key locks helps prevent tampering of the controls used to set temperature heating and cooling functions Locks are available for all PTAC models Rem...

Страница 24: ...ssor or connecting tubing which proves to be defective due to workmanship or materials Limited Second through FifthYear Warranty During the 2nd through 5th year Trane will provide free of charge funct...

Страница 25: ...formation contact your local distributor dealer local district office or e mail us at comfort trane com SinceTheTrane Company has a policy of continuous product and product data improvement it reserve...