background image

16

Adjust refrigerant level to attain proper gage pressure.

5.

Add refrigerant

 if the design liquid line pressure is lower than the 

chart value.

Connect gages to refrigerant bottle and unit as illustrated (Figure 

40).

Purge all hoses.

Open bottle.

Stop  adding  refrigerant  when  liquid  line  pressure  matches  the 

Refrigerant Charging Chart.

Recover refrigerant 

if the design liquid line pressure is lower than 

the chart value.

Figure 40

Stabilize the system.

Wait  20  minutes  for  the  system  condition  to  stabilize  between 

adjustments.

Remove gages.

Replace service port caps to prevent leaks. Tighten finger tight plus 

an additional 1/6 turn.

6.

Record system Information for reference (Table 8).

Record  system  pressures  and  temperatures  after  charging  is 

complete.

7.

When  the  liquid  line  pressure  match  the  chart,  the  system  is 

properly charged.

20 MIN

.

Figure 41

Description

Value

Outdoor model number
Measured Outdoor Ambient

                  °F

Measured Indoor Ambient

                  °F

Liquid Gage Pressure

PSIG

Suction Gage Pressure

PSIG

Table 8

55

60

65

70

75

80

85

90

95

100

105

110

115

165

161

157

153

149

145

141

137

133

129

125

121

117

113

109

105

Suction 

Pre

ss

ure

 a

t

La

rge

 S

erv

ic

Va

lv

e(

ps

ig)

Cooling

Mode

Outdoor Ambient Temperature(

)

Liquid Pressure at Small Service Valve(psig)

14SEER R410A HP Charge Chart 4 TON(Cooling mode)

55

60

65

70

75

80

85

90

95

100

105

110

115

165

161

157

153

149

145

141

137

133

129

125

121

117

113

109

105

Suction 

Pre

ss

ure

 a

t

La

rge

 S

erv

ic

Va

lv

e(

ps

ig)

Cooling

Mode

Outdoor Ambient Temperature(

)

Liquid Pressure at Small Service Valve(psig)

14SEER R410A HP Charge Chart 5 TON(Cooling mode)

255

273

291

310

330

351

371

396

420

445

469

253

271

289

308

328

349

369

394

418

443

467

251

269

287

306

326

347

367

392

416

441

465

231

249

267

285

304

324

345

365

390

414

439

463

229

247

265

283

302

322

343

363

388

412

437

461

227

245

263

281

300

320

341

361

386

410

435

459

206

225

243

261

279

298

318

339

359

384

408

433

457

204

223

241

259

277

296

316

337

357

382

406

431

455

204

222

240

258

275

294

314

335

355

380

404

429

453

202

220

238

256

273

292

312

333

353

378

402

427

451

200

218

236

254

271

290

310

331

351

376

400

425

449

198

216

234

252

269

288

308

329

349

374

398

423

447

196

214

232

250

267

286

306

327

347

372

396

421

445

194

212

230

248

265

284

304

325

345

370

394

419

443

192

210

228

246

263

282

302

323

343

368

392

417

441

190

208

226

244

261

280

300

321

341

366

390

415

439

249

267

285

303

323

344

364

392

415

441

466

247

265

283

301

321

342

362

391

413

439

464

245

263

281

299

319

340

360

389

411

437

462

225

243

261

279

297

317

338

358

387

409

435

460

223

241

259

277

295

315

336

356

385

407

433

458

221

239

257

275

293

313

334

354

383

405

431

456

201

219

237

255

273

291

311

332

352

381

403

429

454

199

217

235

253

271

289

309

330

350

379

401

427

452

197

215

233

251

269

287

307

328

348

377

399

425

450

195

213

231

249

267

285

305

326

346

375

397

423

448

193

211

229

247

265

283

303

324

344

373

395

421

446

191

209

227

245

263

281

301

322

342

371

393

419

444

189

207

225

243

261

279

299

320

340

369

391

417

442

187

205

223

241

259

277

297

318

338

367

389

415

440

185

203

221

239

257

275

295

316

336

365

387

413

438

183

201

219

237

255

273

293

314

334

363

385

411

436

Содержание Oxbox AC 18

Страница 1: ...may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death RECOGNIZE THIS SYMBOL AS AN INDICATION OF IM...

Страница 2: ...GERANT LINE ROUTING 5 7 REFRIGERANT LINE BRAZING 7 8 REFRIGERANT LINE LEAK CHECK 8 9 EVACUATION 8 10 SERVICE VALVE 8 11 ELECTRICAL LOW VOLTAGE 9 12 ELECTRICAL HIGH VOLTAGE 10 13 START UP 10 14 SYSTEM...

Страница 3: ...ice equipments Refrigerant cylinders are painted a Rose color to indicate the type of refrigerant and may contain a dip tube to allow for charging of liquid refrigerant into the system All R 410A syst...

Страница 4: ...ches clearance must be provided in front of the control box access panels and any other side requiring service Units should be elevated 3 12 inches above the pad or rooftop depending on local weather...

Страница 5: ...ice pressure rating Leak detectors should be disigned to detect R410A Recovery equipments including refrigerant recovery containers must be specifically designed to handle R410A Do not use an R22 TXV...

Страница 6: ...t Total vertical Change Lift __________ Feet Model Suction line connection Liquid line connection 18 3 4 3 8 24 3 4 3 8 30 3 4 3 8 36 3 4 3 8 42 3 4 3 8 48 7 8 3 8 60 7 8 3 8 optional standard optiona...

Страница 7: ...e refrigerant lines run through a wall or sill they should be insulated and isolated Isolate the lines from all ductwork Minimize the number of 90 turns Use PVC piping as a conduit for all underground...

Страница 8: ...13 Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Suction Line Wall Ductwork Isolator Line Set Figure 14 Figure 15 Secure Suction Line using isolators every 8 feet Secu...

Страница 9: ...Braze the refrigerant lines to the service valves Check liquid line filter drier s directional flow arrow to confirm correct direction of refrigeration flow away from outdoor unit and toward evaporat...

Страница 10: ...lines and indoor coil 10 Service valves 10 1 Open the service valves Observe the micron gauge Evacuation is complete if the micron gauge does not rise above 500 microns in one 1 minute Once evacuatio...

Страница 11: ...225 Ft 14 AWG 300 Ft Table 6 11 2 Low voltage hook up diagrams Air Handler Hook up Diagram Low Voltage connection must be made inside the outdoor unit case Figure 26 Figure 27 FOR TWO STAGE HEAT THER...

Страница 12: ...utdoor unit Field provided flexible electrical conduit must be used for high voltage wiring 12 3 High voltage ground Ground the outdoor unit per National State and Local Code requirements Figure 29 Fi...

Страница 13: ...9 10 11 and 12 have been completed Set System Thermostat to OFF 1 2 Turn on disconnect to apply power to the indoor and outdoor units 3 Wait one 1 hour before starting the unit if compressor crankcase...

Страница 14: ...se weigh in charge method Note It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55 F For best results the...

Страница 15: ...3 379 405 431 457 194 211 228 247 267 286 308 329 351 377 403 429 455 192 209 226 245 265 284 306 327 349 375 401 427 453 55 60 65 70 75 80 85 90 95 100 105 110 115 165 161 157 153 149 145 141 137 133...

Страница 16: ...279 298 321 343 366 393 420 447 474 202 220 238 257 277 296 319 341 364 391 418 445 472 200 218 236 255 275 294 317 339 362 389 416 443 470 198 216 234 253 273 292 315 337 360 387 414 441 468 196 214...

Страница 17: ...0 431 457 231 247 263 282 299 321 342 364 384 408 429 455 229 245 261 280 297 319 340 362 382 406 427 453 227 243 259 278 295 317 338 360 380 404 425 451 208 225 241 257 276 293 315 336 358 378 402 42...

Страница 18: ...Pressure at Small Service Valve psig 14SEER R410A HP Charge Chart 5 TON Cooling mode 255 273 291 310 330 351 371 396 420 445 469 253 271 289 308 328 349 369 394 418 443 467 251 269 287 306 326 347 367...

Страница 19: ...If 5 F T4 75 F unit can operate in heating Once the manual defrost mode is finished please turn the switch SW3 1 back to off Discharge temperature protection Discharge temperature 275 F compressor st...

Страница 20: ...50 15 57 95 56 17 45 97 6 10 138 2 45 16 56 17 57 16 98 98 5 96 139 2 40 17 54 46 58 16 52 99 5 82 140 2 35 18 52 80 59 16 08 100 5 68 141 2 30 19 51 20 60 15 65 101 5 55 142 2 25 20 49 65 61 15 23 10...

Страница 21: ...P P P P P P P P S S S S S S P P P P P P P P P P P P P P P S S S S S P S S S S S S S S S P P S S S S S S S S P P P P S S S S S S S S S S S P P S S S S S P P P P P P P S S P P P C Cooling H Heating P P...

Страница 22: ...A2 A1 L2 T2 L1 T1 BLACK YELLOW C Y LOW WARNING CABINET MUST BE PERMANMENTLY GOUNDED AND ALL WIRING TO CONFORM TO I E C N E C C E C C L C AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAM...

Страница 23: ...21 17 2 For HP MANUAL DEFROST AUTOMATIC DEFROST NORMAL DEFROST DEFROSTING CYCLE 60MIN DEFROSTING CYCLE 30MIN 1 2 0 3 RESERVED Figure 45...

Страница 24: ...6A 14 YES J4AH4E60A1C00AA 0 073 4AYTXVH3G2436A 14 YES J4GXCB004AC6HUA 0 070 4AYTXVH3G2436A 14 NO J4MXCB004AC6HCA 0 070 4AYTXVH3G2436A 14 NO J4AH4P42A1C00AA 0 075 4AYTXVH3G4248A 14 YES J4AH4E60A1C00AA...

Отзывы: