background image

1.  Key to symbols and safety instructions

1.1 Key to symbols

1.2 Safety

The following keywords are defined and can be used in this document:

Warnings  in  this  document  are  identified  by  a  warning 

triangle. Keywords at the start of a warning indicate the 

type and seriousness of the ensuing risk if measures to 

prevent the risk are not taken.

This symbol indicates important information where there 

is no risk to people or property.

DANGER 

indicates  a  hazardous  situation  which,  if  not  avoided,  will 

result in death or serious injury.

WARNING

 indicates a hazardous situation which, if not avoided, could

result in death or serious injury.

CAUTION

 indicates a hazardous situation which, if not avoided, could

result in minor to moderate injury.

NOTICE

 is used to address practices not related to personal injury.

CAUTION:

CAUTION:

This  document  is  customer  property  and  is  to  remain  with

this  unit.  Please  return  to  service  information  pack  upon

completion of work.

These  instructions  do  not  cover  all  variations  in  systems

or  provide  for  every  possible  contingency  to  be  met  in

connection with the installation.

Should  further  information  be  desired  or  should  particular

problems  arise  which  are  not  covered  sufficiently  for  the

purchaser’s  purposes,  the  matter  should  be  referred  to  your

installing dealer or local distributor.

WARNING: HAZARDOUS VOLTAGE

Failure to follow this warning could result in property damage,

severe personal injury or death.

Disconnect  all  electric  power,  including  remote  disconnects

before  servicing.  Follow  proper  lockout/tagout  procedures  to

ensure the power cannot be inadvertently energized.

WARNING: REFRIGERANT OIL

CAUTION: HOT SURFACE

This  information  is  intended  for  use  by  individuals  possessing 

adequate backgrounds of electrical and mechanical experience. Any 

attempt  to  repair  a  central  air  conditioning  product  may  result  in 

personal injury and/or property damage.

These units use R-410A refrigerant which operates at 50% to 70% 

higher  pressures  than R-22.  Use  only  R-410A  approved  service 

equipments.  Refrigerant  cylinders  are  painted  a  “Rose”  color  to 

indicate the type of refrigerant and may contain a “dip” tube to allow 

for charging of liquid refrigerant into the system. All R-410A systems 

use a POE oil that readily absorbs moisture from the atmosphere

.

 To 

limit  this  “hygroscopic”  action,  the  system  should  remain  sealed 

whenever possible. If a system has been opening to the atmosphere 

for more than 4 hours, the compressor oil must be replaced. Never 

break a vacuum with air and always change the driers when opening 

the system for component replacement.

May cause minor to severe burning. Failure to follow this Caution 

could result in property damage or personal injury. Do not touch 

the top of compressor.

WARNING: BRAZING REQUIRED

Failure to inspect lines or use proper service tools may result in 

equipment damage or personal injury. 

All  outdoor  unit  and  evaporator  coil  connections  are 

copper-to-copper  and  should  be  brazed  with  a 

phosphorous-copper  alloy  material  such  as  Silfos-5  or 

equivalent. Do not use soft solder.

CAUTION: CONTAINS REFRIGERANT

Failure to follow proper procedures can result in personal illness 

or injury or severe equipment damage. System contains oil and 

refrigerant  under  high  pressure.  Recover  refrigerant  to  relieve 

pressure before opening system.

CAUTION: GROUNDING REQUIRED

Failure  to  inspect  or  use  proper  service  tools  may  result  in 

equipment  damage  or  personal  injury.  Reconnect  all  grounding 

devices. All parts of this product that are capable of conducting 

electrical  current  are  grounded.  If  grounding  wires,  screws, 

straps, clips, nuts or washers used to complete a path to ground 

are removed for service, they must be returned to their original 

position and properly fastened.

WARNING: SERVICE VALVES

Failure  to  follow  this  warning  will  result  in  abrupt  release  of 

system charge and may result in personal injury and/or property 

damage. Extreme caution should be exercised when opening the 

Liquid Line Service Valve. Turn valve stem counterclockwise only 

until the stem contacts the rolled edge. No torque is required.

This document contains a wiring diagram and service information.

1

All phases of this installation must comply with NATIONAL, STATE, AND 

LOCAL CODES. 

Содержание Oxbox AC 18

Страница 1: ...may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death RECOGNIZE THIS SYMBOL AS AN INDICATION OF IM...

Страница 2: ...GERANT LINE ROUTING 5 7 REFRIGERANT LINE BRAZING 7 8 REFRIGERANT LINE LEAK CHECK 8 9 EVACUATION 8 10 SERVICE VALVE 8 11 ELECTRICAL LOW VOLTAGE 9 12 ELECTRICAL HIGH VOLTAGE 10 13 START UP 10 14 SYSTEM...

Страница 3: ...ice equipments Refrigerant cylinders are painted a Rose color to indicate the type of refrigerant and may contain a dip tube to allow for charging of liquid refrigerant into the system All R 410A syst...

Страница 4: ...ches clearance must be provided in front of the control box access panels and any other side requiring service Units should be elevated 3 12 inches above the pad or rooftop depending on local weather...

Страница 5: ...ice pressure rating Leak detectors should be disigned to detect R410A Recovery equipments including refrigerant recovery containers must be specifically designed to handle R410A Do not use an R22 TXV...

Страница 6: ...t Total vertical Change Lift __________ Feet Model Suction line connection Liquid line connection 18 3 4 3 8 24 3 4 3 8 30 3 4 3 8 36 3 4 3 8 42 3 4 3 8 48 7 8 3 8 60 7 8 3 8 optional standard optiona...

Страница 7: ...e refrigerant lines run through a wall or sill they should be insulated and isolated Isolate the lines from all ductwork Minimize the number of 90 turns Use PVC piping as a conduit for all underground...

Страница 8: ...13 Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Suction Line Wall Ductwork Isolator Line Set Figure 14 Figure 15 Secure Suction Line using isolators every 8 feet Secu...

Страница 9: ...Braze the refrigerant lines to the service valves Check liquid line filter drier s directional flow arrow to confirm correct direction of refrigeration flow away from outdoor unit and toward evaporat...

Страница 10: ...lines and indoor coil 10 Service valves 10 1 Open the service valves Observe the micron gauge Evacuation is complete if the micron gauge does not rise above 500 microns in one 1 minute Once evacuatio...

Страница 11: ...225 Ft 14 AWG 300 Ft Table 6 11 2 Low voltage hook up diagrams Air Handler Hook up Diagram Low Voltage connection must be made inside the outdoor unit case Figure 26 Figure 27 FOR TWO STAGE HEAT THER...

Страница 12: ...utdoor unit Field provided flexible electrical conduit must be used for high voltage wiring 12 3 High voltage ground Ground the outdoor unit per National State and Local Code requirements Figure 29 Fi...

Страница 13: ...9 10 11 and 12 have been completed Set System Thermostat to OFF 1 2 Turn on disconnect to apply power to the indoor and outdoor units 3 Wait one 1 hour before starting the unit if compressor crankcase...

Страница 14: ...se weigh in charge method Note It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55 F For best results the...

Страница 15: ...3 379 405 431 457 194 211 228 247 267 286 308 329 351 377 403 429 455 192 209 226 245 265 284 306 327 349 375 401 427 453 55 60 65 70 75 80 85 90 95 100 105 110 115 165 161 157 153 149 145 141 137 133...

Страница 16: ...279 298 321 343 366 393 420 447 474 202 220 238 257 277 296 319 341 364 391 418 445 472 200 218 236 255 275 294 317 339 362 389 416 443 470 198 216 234 253 273 292 315 337 360 387 414 441 468 196 214...

Страница 17: ...0 431 457 231 247 263 282 299 321 342 364 384 408 429 455 229 245 261 280 297 319 340 362 382 406 427 453 227 243 259 278 295 317 338 360 380 404 425 451 208 225 241 257 276 293 315 336 358 378 402 42...

Страница 18: ...Pressure at Small Service Valve psig 14SEER R410A HP Charge Chart 5 TON Cooling mode 255 273 291 310 330 351 371 396 420 445 469 253 271 289 308 328 349 369 394 418 443 467 251 269 287 306 326 347 367...

Страница 19: ...If 5 F T4 75 F unit can operate in heating Once the manual defrost mode is finished please turn the switch SW3 1 back to off Discharge temperature protection Discharge temperature 275 F compressor st...

Страница 20: ...50 15 57 95 56 17 45 97 6 10 138 2 45 16 56 17 57 16 98 98 5 96 139 2 40 17 54 46 58 16 52 99 5 82 140 2 35 18 52 80 59 16 08 100 5 68 141 2 30 19 51 20 60 15 65 101 5 55 142 2 25 20 49 65 61 15 23 10...

Страница 21: ...P P P P P P P P S S S S S S P P P P P P P P P P P P P P P S S S S S P S S S S S S S S S P P S S S S S S S S P P P P S S S S S S S S S S S P P S S S S S P P P P P P P S S P P P C Cooling H Heating P P...

Страница 22: ...A2 A1 L2 T2 L1 T1 BLACK YELLOW C Y LOW WARNING CABINET MUST BE PERMANMENTLY GOUNDED AND ALL WIRING TO CONFORM TO I E C N E C C E C C L C AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAM...

Страница 23: ...21 17 2 For HP MANUAL DEFROST AUTOMATIC DEFROST NORMAL DEFROST DEFROSTING CYCLE 60MIN DEFROSTING CYCLE 30MIN 1 2 0 3 RESERVED Figure 45...

Страница 24: ...6A 14 YES J4AH4E60A1C00AA 0 073 4AYTXVH3G2436A 14 YES J4GXCB004AC6HUA 0 070 4AYTXVH3G2436A 14 NO J4MXCB004AC6HCA 0 070 4AYTXVH3G2436A 14 NO J4AH4P42A1C00AA 0 075 4AYTXVH3G4248A 14 YES J4AH4E60A1C00AA...

Отзывы: