Models
Cooling Only

MCC 518 AB
MCC 524 AB
MCC 530 AB
MCC 536 AB

February 2000

Installation Manual

Split System, 1-5 Tons
18,000 - 38,000 Btu
Underceiling Type
MCC Series 50 Hz

CASSETTE

Содержание MCC 518 AB

Страница 1: ...MCC SVN01A EN Models Cooling Only MCC 518 AB MCC 524 AB MCC 530 AB MCC 536 AB February 2000 Installation Manual Split System 1 5 Tons 18 000 38 000 Btu Underceiling Type MCC Series 50 Hz CASSETTE...

Страница 2: ...n 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at appropria...

Страница 3: ...ormation 2 Indoor Unit Installation 4 Outdoor Unit Installation 5 Connection of Refrigerant Tubing and Condensate Drain Piping 6 Leak Check and System Evacuation 7 Electrical Installation 8 Wiring Dia...

Страница 4: ...re 1 also ensure that the position dose not interfere with light fitting sprinkle head etc Determine the ceiling hole by using the paper pattern Determine the mounting position on ceiling by using pos...

Страница 5: ...r do not disturb the users or their neighbors Easy access to check and to maintain Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles Caution Installation in the foll...

Страница 6: ...to prevent dust or water from getting into the tubes before they are used 8 Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together This...

Страница 7: ...valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas gauge ports 9 Leak test the entire system Using proper procedures and caution repair any leaks found and repeat...

Страница 8: ...trical Connections See Section Wiring System Diagram Bare the ends of electric wire After retaining the wire check that all the terminal screws are firmly tightened Indoor Unit Remove the right side p...

Страница 9: ...MCC SVN01A EN 9 220 240 1 50 Hz MCC518 536AB Wiring Diagram...

Страница 10: ...bove suspension brackets 180 mm 180 mm 230 mm 230 mm C Height of condensate drain above ceiling 230 mm 230 mm 280 mm 280 mm D Pipe exit position 165 mm 165 mm 215 mm 215 mm 950 390 340 512 330 370 350...

Страница 11: ...MCC SVN01A EN 11 Notes...

Страница 12: ...reserves the right to change design and specifications without notice Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Bangkok 10110 http www trane com An American Standar...