Figure 15

Figure 10

Figure 9

Figure 11

Figure 12

Figure 13

Copper

tubing

Reamer

Before

After

Flare nut

Flare tool

Copper

tubing

Apply refrigerant

lubricant here

Flare nut

Union

Give a slope

Figure 14

,,

,,

,,

yy

yy

yy

,,,

,,,

,,,

yyy

yyy

yyy

Drain hose

Connection of Refrigerant Tubing
and Condensate Drain Piping

Deburring

Connecting the unit with flaring
procedure

1. Flaring (If piping is procured or cut

at the site). Cut the copper tube to
the required length with a tube
cutter. It is recommended to cut
approx. 30-50 cm. longer than the
tubing length you estimate.

2. Hold each pipe downward when

cutting and remove burrs at the
end of the copper tube with a tube
reamer or file. This process is
important and should be done
carefully to make a good flare
(Figure 9 and Figure 10).

A good flare should have the
following characteristics:

-

Inside surface is glossy and
smooth.

-

Edge is smooth.

-

Tapered sides are of uniform length.

Bending

5. When bending the tube, be careful

not to crush it. To prevent crushing
of the tube, bend it gently and do
not bend the tube at a radius
curvature of less than 100 mm.

6. If the copper tube is bent or pulled

too often, it will become stiff. Do
not bend the pipe more than three
times at one place.

Cautions before Connecting
Tubes Tightly

7. Be sure to apply a sealing cap

or water-proof tape to prevent
dust or water from getting into
the tubes before they are used.

8. Be sure to apply refrigerant

lubricant to the matching surfaces
of the flare and union before
connecting them together. This
is effective for reducing gas leaks
(Figure 12).

10. Tighten the flare nut to the

specified tightening torque with
torque wrench and adjustable
wrench.

Condensate Drain Piping

-

The drain hose should run straight
down the wall to a level where the
runoff will not stain the wall.

-

There should be no traps. Avoid
putting the end of the hose in
water.

-

To conveniently drain the system,
the drain hose must slant
downward, with a slope of at least
1 : 50 to prevent leakage as shown
in figure 14.

When reaming, hold the tube end
downward and be sure that no
copper scraps fall into the tube.

3. Remove the flare nut from the

unit and be sure to mount it on
the copper tube.

4. Make a flare at the end of copper

tube with a flare tool (Figure 11).

Connection

9. For proper connection, align the

union tube and flare tube straight
with each other, then screw in the
flare nut lightly at first to obtain a
smooth match (Figure 13).

-

When the drain hose is placed in
the room, insulate the hose with
foam polyethylene to avoid
damage to the ceiling or furniture.

-

After completing installation of
refrigerant lines, wiring and drain
connections, bind the tubing,
wiring and drain hose (check if
local codes permit binding) into a
bundle by using tape at 100 or
200 mm (4" to 8") intervals. Make
sure the drain hose is at the bottom
of the bundle (Figure 15).

Содержание MCC 518 AB

Страница 1: ...MCC SVN01A EN Models Cooling Only MCC 518 AB MCC 524 AB MCC 530 AB MCC 536 AB February 2000 Installation Manual Split System 1 5 Tons 18 000 38 000 Btu Underceiling Type MCC Series 50 Hz CASSETTE...

Страница 2: ...n 7 days of delivery If any concealed damage is discovered send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer Warning Warnings are provided at appropria...

Страница 3: ...ormation 2 Indoor Unit Installation 4 Outdoor Unit Installation 5 Connection of Refrigerant Tubing and Condensate Drain Piping 6 Leak Check and System Evacuation 7 Electrical Installation 8 Wiring Dia...

Страница 4: ...re 1 also ensure that the position dose not interfere with light fitting sprinkle head etc Determine the ceiling hole by using the paper pattern Determine the mounting position on ceiling by using pos...

Страница 5: ...r do not disturb the users or their neighbors Easy access to check and to maintain Ensure the spaces indicated by arrows from the wall ceiling fence or other obstacles Caution Installation in the foll...

Страница 6: ...to prevent dust or water from getting into the tubes before they are used 8 Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together This...

Страница 7: ...valves on manifold gauge set and remove refrigerant charging hoses from liquid and gas gauge ports 9 Leak test the entire system Using proper procedures and caution repair any leaks found and repeat...

Страница 8: ...trical Connections See Section Wiring System Diagram Bare the ends of electric wire After retaining the wire check that all the terminal screws are firmly tightened Indoor Unit Remove the right side p...

Страница 9: ...MCC SVN01A EN 9 220 240 1 50 Hz MCC518 536AB Wiring Diagram...

Страница 10: ...bove suspension brackets 180 mm 180 mm 230 mm 230 mm C Height of condensate drain above ceiling 230 mm 230 mm 280 mm 280 mm D Pipe exit position 165 mm 165 mm 215 mm 215 mm 950 390 340 512 330 370 350...

Страница 11: ...MCC SVN01A EN 11 Notes...

Страница 12: ...reserves the right to change design and specifications without notice Trane Thailand 7th Floor Ploenchit Center Building 2 Sukhumvit Road Klongtoey Bangkok 10110 http www trane com An American Standar...

Отзывы: