10
TWE5-PRC001-EN-10-15-99
Performance
Data Cooling
English Units
TWJ030CA WITH TWE040CA4-B AT 1100 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
30.7
25.1
27.1
29.1
31.0*
31.6*
2.65
85
63
33.0
21.2
23.2
25.2
27.2
29.2
2.75
67
35.3
16.9
18.9
20.9
22.9
24.9
2.84
71
37.7
12.5
14.5
16.5
18.5
20.4
2.94
59
30.1
24.9
26.9
28.9
30.5*
31.2*
2.78
90
63
32.3
21.0
22.9
24.9
26.9
28.9
2.87
67
34.6
16.6
18.6
20.6
22.6
24.6
2.97
71
37.0
12.2
14.2
16.2
18.2
20.2
3.07
59
29.5
24.6
26.6
28.6
30.0*
30.7*
2.91
95
63
31.7
20.7
22.7
24.7
26.7
28.7
3.00
67
33.9
16.4
18.4
20.4
22.3
24.3
3.10
71
36.2
12.0
14.0
15.9
17.9
19.9
3.20
59
28.8
24.3
26.3
28.3
29.3*
30.0*
3.04
100
63
30.9
20.4
22.4
24.3
26.3
28.3
3.13
67
33.0
16.0
18.0
20.0
22.0
24.0
3.23
71
35.3
11.6
13.6
15.6
17.6
19.6
3.33
59
28.0
24.0
26.0
27.9
28.7*
29.4*
3.17
105
63
30.0
20.0
22.0
24.0
26.0
28.0
3.27
67
32.1
15.7
17.7
19.7
21.7
23.7
3.36
71
34.3
11.3
13.3
15.3
17.3
19.3
3.46
59
26.5
23.3
25.3
26.8*
27.4*
28.1*
3.45
115
63
28.4
19.4
21.4
23.4
25.4
27.3
3.54
67
30.4
15.1
17.1
19.0
21.0
23.0
3.63
71
32.4
10.7
12.7
14.6
16.6
18.6
3.73
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
975
1275
TOTAL CAP.
X0.98
X1.02
SENS. CAP.
X0.95
X1.07
COMPR. KW
X0.99
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 34100 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 3104 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 9.05 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE
VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWJ036CA WITH TWE030CA4 AT 1100 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
33.9
25.9
27.8
29.7
31.6
33.4
2.52
85
63
36.7
22.4
24.3
26.1
28.0
29.9
2.60
67
39.5
18.4
20.3
22.1
24.0
25.9
2.68
71
42.5
14.3
16.2
18.0
19.9
21.8
2.77
59
33.4
25.7
27.6
29.4
31.3
33.2
2.65
90
63
36.1
22.1
24.0
25.9
27.8
29.6
2.73
67
38.9
18.1
20.0
21.9
23.8
25.6
2.82
71
41.8
14.0
15.9
17.8
19.7
21.5
2.91
59
32.8
25.4
27.3
29.2
31.1
32.9*
2.78
95
63
35.5
21.9
23.8
25.6
27.5
29.4
2.87
67
38.3
17.9
19.8
21.6
23.5
25.4
2.95
71
41.2
13.8
15.7
17.5
19.4
21.3
3.04
59
32.1
25.1
27.0
28.9
30.7
32.4*
2.92
100
63
34.7
21.5
23.4
25.3
27.2
29.0
3.00
67
37.4
17.6
19.4
21.3
23.2
25.1
3.09
71
40.2
13.5
15.3
17.2
19.1
21.0
3.18
59
31.3
24.8
26.7
28.5
30.4
31.8*
3.06
105
63
33.9
21.2
23.1
25.0
26.8
28.7
3.14
67
36.5
17.2
19.1
21.0
22.8
24.7
3.23
71
39.3
13.1
15.0
16.9
18.7
20.6
3.31
59
29.8
24.1
26.0
27.9
29.7
30.6*
3.35
115
63
32.2
20.5
22.4
24.3
26.2
28.0
3.42
67
34.8
16.5
18.4
20.3
22.2
24.0
3.50
71
37.4
12.5
14.3
16.2
18.1
19.9
3.58
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
975
1275
TOTAL CAP.
X0.98
X1.02
SENS. CAP.
X0.95
X1.06
COMPR. KW
X0.99
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 38500 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2957 WATTS
I.D. FAN POWER = 540 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWJ036CA WITH TWE040CA4-B AT 1400 CFM
(CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
72
74
76
78
80
KW
59
37.2
30.6
33.0
35.5
37.6*
38.5*
2.63
85
63
40.1
25.8
28.3
30.7
33.1
35.6
2.71
67
43.1
20.6
23.0
25.4
27.9
30.3
2.80
71
46.2
15.2
17.6
20.1
22.5
25.0
2.89
59
36.5
30.3
32.7
35.2
37.0*
37.9*
2.76
90
63
39.3
25.5
28.0
30.4
32.8
35.3
2.85
67
42.3
20.3
22.7
25.1
27.6
30.0
2.94
71
45.3
14.9
17.3
19.8
22.2
24.7
3.03
59
35.8
30.0
32.4
34.9
36.5*
37.3*
2.90
95
63
38.6
25.2
27.7
30.1
32.5
35.0
2.99
67
41.5
20.0
22.4
24.8
27.3
29.7
3.07
71
44.4
14.6
17.0
19.5
21.9
24.4
3.17
59
34.9
29.6
32.0
34.5
35.7*
36.5*
3.04
100
63
37.6
24.8
27.3
29.7
32.1
34.6
3.13
67
40.4
19.6
22.0
24.4
26.9
29.3
3.22
71
43.3
14.2
16.6
19.1
21.5
24.0
3.31
59
34.0
29.2
31.6
34.1*
34.9*
35.8*
3.19
105
63
36.6
24.4
26.9
29.3
31.7
34.2
3.27
67
39.3
19.2
21.6
24.0
26.5
28.9
3.36
71
42.1
13.8
16.2
18.7
21.1
23.6
3.45
59
32.1
28.4
30.8
32.6*
33.4*
34.2*
3.48
115
63
34.6
23.6
26.1
28.5
30.9
33.4
3.56
67
37.1
18.4
20.8
23.2
25.7
28.1
3.64
71
39.8
13.0
15.4
17.9
20.3
22.8
3.73
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1175
1525
TOTAL CAP.
X0.97
X1.01
SENS. CAP.
X0.92
X1.04
COMPR. KW
X0.98
X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 41300 BTUH
AIRFLOW = 1350 CFM
COMPRESSOR POWER = 3066 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 10.80 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.