TWE5-PRC001-EN-10-15-99
9
Performance
Data Cooling
Metric Units
TWJ020CA WITH TWE030CA4 AT 1189 CMH
(CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
22.2
23.3
24.4
25.6
26.7
KW
15.0
5.3
4.5
4.9
5.3
5.4*
5.6*
1.3
29.4
17.2
5.8
3.8
4.2
4.5
4.9
5.3
1.4
19.4
6.2
3.0
3.4
3.8
4.1
4.5
1.4
21.7
6.7
2.2
2.6
3.0
3.3
3.7
1.5
15.0
5.2
4.5
4.9
5.2
5.4*
5.5*
1.4
32.2
17.2
5.7
3.8
4.1
4.5
4.9
5.2
1.5
19.4
6.1
3.0
3.3
3.7
4.1
4.5
1.5
21.7
6.5
2.2
2.5
2.9
3.3
3.6
1.5
15.0
5.1
4.5
4.8
5.2*
5.3*
5.4*
1.5
35.0
17.2
5.5
3.7
4.1
4.5
4.8
5.2
1.5
19.4
6.0
2.9
3.3
3.7
4.0
4.4
1.6
21.7
6.4
2.1
2.5
2.9
3.2
3.6
1.6
15.0
5.0
4.4
4.7
5.0*
5.2*
5.3*
1.5
37.8
17.2
5.4
3.7
4.0
4.4
4.8
5.2
1.6
19.4
5.8
2.9
3.2
3.6
4.0
4.4
1.6
21.7
6.2
2.1
2.4
2.8
3.2
3.5
1.7
15.0
4.8
4.3
4.7
4.9*
5.1*
5.2*
1.6
40.6
17.2
5.2
3.6
4.0
4.3
4.7
5.1
1.6
19.4
5.6
2.8
3.2
3.5
3.9
4.3
1.7
21.7
6.1
2.0
2.4
2.7
3.1
3.5
1.8
15.0
4.6
4.2
4.6*
4.7*
4.8*
5.0*
1.7
46.1
17.2
4.9
3.5
3.8
4.2
4.6
5.0*
1.8
19.4
5.3
2.7
3.0
3.4
3.8
4.2
1.8
21.7
5.7
1.9
2.3
2.6
3.0
3.4
1.9
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1061
1358
TOTAL CAP.
X0.99
X1.01
SENS. CAP.
X0.95
X1.06
COMPR. KW
X0.99
X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 5.98 KW
AIRFLOW = 1189 CMH
COMPRESSOR POWER = 1562 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
S.E.E.R. = 10.30 BTUH/WATT
E.E.R. = 9.50 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWJ024CA WITH TWE030CA4 AT 1528 CMH
(CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
22.2
23.3
24.4
25.6
26.7
KW
15.0
7.1
5.8
6.2
6.7
7.1*
7.3*
1.9
29.4
17.2
7.6
4.9
5.4
5.8
6.3
6.7
2.0
19.4
8.2
3.9
4.4
4.8
5.3
5.7
2.0
21.7
8.8
2.9
3.4
3.8
4.3
4.7
2.1
15.0
7.0
5.7
6.2
6.7
7.0*
7.2*
2.0
32.2
17.2
7.5
4.8
5.3
5.8
6.2
6.7
2.1
19.4
8.1
3.9
4.3
4.8
5.2
5.7
2.1
21.7
8.6
2.8
3.3
3.8
4.2
4.7
2.2
15.0
6.9
5.7
6.2
6.6
6.9*
7.1*
2.1
35.0
17.2
7.4
4.8
5.2
5.7
6.2
6.6
2.2
19.4
7.9
3.8
4.2
4.7
5.2
5.6
2.2
21.7
8.5
2.8
3.3
3.7
4.2
4.6
2.3
15.0
6.7
5.6
6.1
6.5
6.8*
7.0*
2.2
37.8
17.2
7.2
4.7
5.2
5.6
6.1
6.6
2.3
19.4
7.7
3.7
4.2
4.7
5.1
5.6
2.3
21.7
8.3
2.7
3.2
3.6
4.1
4.6
2.4
15.0
6.5
5.5
6.0
6.4
6.7*
6.8*
2.3
40.6
17.2
7.0
4.7
5.1
5.6
6.0
6.5
2.4
19.4
7.5
3.7
4.1
4.6
5.0
5.5
2.4
21.7
8.1
2.6
3.1
3.6
4.0
4.5
2.5
15.0
6.2
5.4
5.9
6.2*
6.4*
6.6*
2.5
46.1
17.2
6.7
4.5
5.0
5.4
5.9
6.3
2.6
19.4
7.1
3.5
4.0
4.4
4.9
5.4
2.7
21.7
7.7
2.5
3.0
3.4
3.9
4.3
2.7
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1358
1741
TOTAL CAP.
X0.99
X1.01
SENS. CAP.
X0.95
X1.06
COMPR. KW
X0.99
X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 7.94 KW
AIRFLOW = 1528 CMH
COMPRESSOR POWER = 2239 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 180 WATTS
E.E.R. = 8.90 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWJ030CA WITH TWE030CA4 AT 1698 CMH
(CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
I.D.
TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
D.B.
W.B.
CAP.
22.2
23.3
24.4
25.6
26.7
KW
15.0
8.5
6.7
7.2
7.7
8.2
8.6*
2.6
29.4
17.2
9.1
5.7
6.2
6.7
7.2
7.7
2.7
19.4
9.8
4.6
5.1
5.6
6.1
6.6
2.8
21.7
10.5
3.5
4.0
4.5
5.0
5.5
2.8
15.0
8.4
6.6
7.1
7.6
8.1
8.5*
2.7
32.2
17.2
9.0
5.6
6.1
6.7
7.1
7.6
2.8
19.4
9.6
4.5
5.0
5.5
6.1
6.6
2.9
21.7
10.3
3.4
3.9
4.4
5.0
5.4
3.0
15.0
8.2
6.5
7.1
7.6
8.1
8.4*
2.8
35.0
17.2
8.8
5.6
6.1
6.6
7.1
7.6
2.9
19.4
9.5
4.5
5.0
5.5
6.0
6.5
3.0
21.7
10.1
3.4
3.9
4.4
4.9
5.4
3.1
15.0
8.0
6.5
7.0
7.5
8.0
8.2*
3.0
37.8
17.2
8.6
5.5
6.0
6.5
7.0
7.5
3.0
19.4
9.2
4.4
4.9
5.4
5.9
6.4
3.1
21.7
9.9
3.3
3.8
4.3
4.8
5.3
3.2
15.0
7.8
6.4
6.9
7.4
7.9*
8.0*
3.1
40.6
17.2
8.4
5.4
5.9
6.4
6.9
7.4
3.2
19.4
9.0
4.3
4.8
5.3
5.8
6.3
3.3
21.7
9.6
3.2
3.7
4.2
4.7
5.2
3.4
15.0
7.4
6.2
6.7
7.2
7.5*
7.7*
3.3
46.1
17.2
8.0
5.2
5.7
6.2
6.7
7.2
3.4
19.4
8.6
4.1
4.6
5.2
5.7
6.2
3.5
21.7
9.2
3.0
3.5
4.0
4.5
5.0
3.6
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
1486
1910
TOTAL CAP.
X0.98
X1.01
SENS. CAP.
X0.95
X1.05
COMPR. KW
X0.99
X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.49 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 3002 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 8.30 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.