Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Digit 31 - Flow switch
X = None
F = Field installed flow switch
Digit 32 - Electrical Panel Protection
X = Enclosure with dead front protection
1 = Enclosure with IP20 protection
Digit 33 - Master Slave
X = Standard Unit
Digit 34 - Unit User Interface
L = Standard, Local UI supplied (TD7)
Digit 35 - Energy meter
X = No energy meter
M = Energy meter installed
Digit 36 - Open for future use = X
Digit 37 - Variable Primary Flow
X = Constant speed Pump - no AFD
F = Constant Speed Pump -AFD Adjustment
P = Variable Speed Pump - Constant delta P
T = Variable Speed Pump - Constant delta T
Digit 38 - Open for future use = X
Digit 39 - Open for future use = X
Digit 40 - Power socket
X = None
P = Included (230V - 100W)
Digit 41 - Factory tests
X = No final performances test
B = Test A+Visual Inspection
E = Performance test w/o customer
Digit 42 - Installation accessory
X = None
1 = Neoprene Isolators
4 = Neoprene pads
Digit 43 - Literature language
B = Bulgarian
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 44 - Shipping package
X = Standard protection
A = Containerization package
Digit 45 - Refrigerant
1 = R134a
2 = R513A
Z= R1234ze(E)
Digit 46 - Open for future use = X
Digit 47 - Open for future use = X
Digit 48 - Design special
X = none
S = special
Unit model number description