![Trane GMND-SVX01B-EN Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/trane/gmnd-svx01b-en/gmnd-svx01b-en_installation-operation-and-maintenance-manual_1149990025.webp)
Installation: Electrical
GMND-SVX01B-EN
25
firing. This setpoint should be measured for the best
results. Use the recommended ranges as a guide. If further
information is needed, consult your thermostat
manufacturer’s instructions.
Recommended Heat Anticipator Setting Ranges:
Fan Time Delay Control
Leads from the fan time delay controls are factory wired to
the junction box. The fan control is a time delay relay
(approximately 45 seconds ON, 65 seconds OFF). The fan
control is rated at 17 amps.
Notes:
•
The start-up fan delay should not exceed 90 seconds
from a cold start.
•
For all wiring connections, refer to the wiring diagram
shipped with your unit (either affixed to the side jacket
or enclosed in your unit’s installation instruction
envelope). Should any original wire supplied with the
heater have to be replaced, it must be replaced with
wiring material having a temperature rating of at least
105°C.
Should any high limit wires have to be replaced, they
must be replaced with wiring material having a
temperature rating of 200°C minimum.
25 ft. (7.6 m) T’stat
Wiring
50 ft. (15.2 m) T’stat Wiring
0.85 to 0.90 A
0.90 to 1.1 A Max. Setting on T’stat