Trane GMND-SVX01B-EN Скачать руководство пользователя страница 12

12

GMND-SVX01B-EN

Installation: Mechanical

Note:

Furnace sizing should be based on heat loss 
calculations where the furnace output equals or 
exceeds heat loss.

Aircraft Hangers. 

Separated Combustion must be 

installed in aircraft hangars as follows: in aircraft hangars, 
duct furnaces must be at least 10 feet (3.0 m) above the 
upper surface of wings or engine enclosures of the highest 
aircraft to be stored in the hangar, and 8  feet (2.4  m) above 
the floor in shops, offices and other sections of the hangar 
where aircraft are not stored or housed. In Canada, 
installation is suitable in aircraft hangars when acceptable 
to the enforcing authorities.

Public Garages. 

In repair garages, duct furnaces must 

be installed in a detached building or room separate from 
repair areas as specified in the latest edition of NFPA 88B, 
Repair Garages.

In parking structures, duct furnaces must be installed so 
that the burner flames are located a minimum of 18  inches 
(457 mm) above the floor or protected by a partition not 
less than 18 inches (457 mm) high. Refer to the latest 
edition of NFPA 88A, Parking Structures.

In Canada, installation must be in accordance with the 
latest edition of CGA B149 “Installation Codes for Gas 
Burning Appliances and Equipment.”

Clearances

Note:

Increasing the clearance distances may be 
necessary if there is a possibility of distortion or 
discoloration of adjacent materials.

Maintain adequate clearances around air openings into 
combustion chamber:

NOTICE: 

Equipment Damage!

Do not install duct furnaces in corrosive or flammable 
atmospheres! Premature failure of, or severe damage to 
the unit could result! Avoid locations where extreme 
drafts can affect burner operation. Duct furnaces must 
not be installed in locations where air for combustion 
would contain chlorinated, halogenated or acidic 
vapors. If located in such an environment, premature 
failure of the unit could occur!

NOTICE: 

Maintain Minimum Thermostat Setting!

Separated Combustion Duct Furnaces should not be 
installed to maintain low temperatures and/or freeze 
protection of buildings. A minimum of 50°F (10°C) 
thermostat setting must be maintained. If duct furnaces 
are operated to maintain lower than 50°F (10°C), hot 
flue gases are cooled inside the heat exchanger to a 
point where water condenses onto the heat exchanger 
walls. The result is a mildly corrosive acid that 
prematurely corrodes the aluminized heat exchanger 
and can actually drip water down from the duct furnace 
onto the floor surface. Additional duct furnaces should 
be installed if a minimum 50°F (10°C) thermostat 
setting cannot be maintained. Failure to follow these 
recommendations could result in equipment or 
property damage.

WARNING

Overheating or Flooding Could Cause Fire 
or Explosion!

Overheating or flooding (where any part of the duct 
furnace has been under water) could result in fire or 
explosion. Should overheating occur, or the gas supply 
fails to shut off, shut off the manual gas valve to the 
duct furnace before shutting off the electrical supply. 
Do not use the duct furnace if any part has been under 
water. Immediately call a qualified service technician to 
inspect the duct furnace and replace any gas control 
which has been underwater. Failure to follow these 
recommendations could result in death or serious 
injury.

WARNING

Hazardous Gases and Flammable Vapors!

Exposure to hazardous gases from fuel substances 
have been shown to cause cancer, birth defects or other 
reproductive harm. Improper installation, adjustment, 
alteration, service or use of this product could cause 
flammable mixtures. To avoid hazardous gases and 
flammable vapors follow proper installation and set up 
of this product and all warnings as provided in this 
manual. Failure to follow all instructions could result in 
death or serious injury.

WARNING

Combustible Materials!

Maintain proper clearance between the unit heat 
exchanger, vent surfaces, and combustible materials. 
Refer to unit nameplate and installation instructions for 
proper clearances. Improper clearances could result in a 
fire hazard. Failure to maintain proper clearances could 
result in death or serious injury or property damage.

Table 3.

Minimum clearances

Sides

18” (457 mm)

Top

6” (152 mm)

Bottom

25” (635 mm)

Flue

6” (152 mm)

Note:

When the clearances required for accessibility are greater than the 

minimum required safety clearances, the accessibility clearances 

take precedence.

Содержание GMND-SVX01B-EN

Страница 1: ...c knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in th...

Страница 2: ...em ATTENTION READ THIS MANUAL AND ALL LABELS ATTACHED TO THE UNIT CAREFULLY BEFORE ATTEMPTING TO INSTALL OPERATE OR SERVICE THESE UNITS CHECK UNIT DATA PLATE FOR TYPE OF GAS AND ELECTRICAL SPECIFICATI...

Страница 3: ...l components perform these tasks Failure to follow all of the recommended safety warnings provided could result in death or serious injury WARNING Overheating or Flooding Could Cause Fire or Explosion...

Страница 4: ...hipment immediately when received to determine if any damage has occurred to the unit during shipment After the unit has been uncrated check for any visible damage to the unit If any damage is found t...

Страница 5: ...ion Piping 16 Gas Piping 16 Pipe Sizing 16 Pipe Installation 17 Installation Venting 18 Combustion Air Venting and Piping 18 Exhaust Venting 19 Installation Concentric Vent Terminal 21 Horizontal Term...

Страница 6: ...3 Rooftop Heating Unit Motor Selection 0 None Indoor Unit and Rooftop Duct Furnace Digit 14 Rooftop Fan Section 0 None Indoor Unit and Rooftop Duct Furnace Digit 15 Miscellaneous Options 0 None A 409...

Страница 7: ...ment or CGA B149 2 Installation Codes for Propane Gas Burning Appliances and Equipment These duct furnaces have been designed and certified to comply with CGA 2 6 Also see sections on installation in...

Страница 8: ...hould be used When connecting to existing gas lines be sure to valve off the gas supply ahead of connection point To avoid explosion or possible fire always purge all residual gas from piping before c...

Страница 9: ...General Information GMND SVX01B EN 9 Figure 2 Internal furnace assembly 1 Flue Collector 2 Heat Exchanger 3 Burner Drawer 1 2 3...

Страница 10: ...2 85 175 23 3 8 21 22 5 8 4 1 2 1 2 207 594 533 575 102 93 200 26 1 8 23 3 4 25 3 8 5 1 2 1 2 227 664 603 645 127 103 225 28 7 8 26 1 2 28 1 8 5 3 4 1 2 or 3 4 246 733 673 714 127 116 250 31 5 8 29 1...

Страница 11: ...873 50 0 02 3 930 11 0 48 250 250 125 200 2 056 90 0 09 9 251 20 1 96 73 2 36 6 58 6 0 970 50 0 02 4 366 11 0 49 300 300 150 240 2 467 90 0 10 11 101 20 2 00 87 8 43 9 70 3 1 164 50 0 02 5 240 11 0 5...

Страница 12: ...ermostat setting must be maintained If duct furnaces are operated to maintain lower than 50 F 10 C hot flue gases are cooled inside the heat exchanger to a point where water condenses onto the heat ex...

Страница 13: ...observe smoke and reflected light and to detect the presence of leaks in the heating equipment are required both upstream and downstream from gas duct furnaces These panels must be sealed to prevent...

Страница 14: ...ger holes WARNING Heavy Objects Ensure that all hardware used in the suspension of each duct furnace is capable of supporting the unit weight Failure to do so could result in unit falling off its moun...

Страница 15: ...bottom panels oriented such that the sides with the larger holes are facing the unit heater create a sub assembly by attaching the top panel P N 251 07942 00X and the bottom panel P N 251 07943 00X t...

Страница 16: ...ired with LP gas consult the local LP gas dealer for pipe size information Before any connection is made to an existing line supplying other gas appliances contact the local gas company to make certai...

Страница 17: ...60 325 300 280 35 39 6 26 9 21 8 18 7 16 4 15 0 13 9 13 0 12 2 11 3 10 2 9 20 8 50 7 93 1 1 2 1 610 2100 1460 1180 990 900 810 750 690 650 620 550 500 460 430 41 59 5 41 3 33 4 28 0 25 5 22 9 21 2 19...

Страница 18: ...ack the valve WARNING Hazard of Explosion Never use an open flame to detect gas leaks Explosive conditions may occur Use a leak test solution or other approved methods for leak testing Failure to foll...

Страница 19: ...ead building structures at three foot 1 m intervals Exhaust Venting 1 Vent system installation must be in accordance with the latest edition of N F P A 54 ANSI Z223 1 National Fuel Gas Code In Canada...

Страница 20: ...s 9 The exhaust vent system must remain at a minimum of six inches 152 mm from all combustible materials Any part of the vent system that passes through a combustible material must be properly insulat...

Страница 21: ...bleshooting procedures recommended in this manual could result in exposure to electrical mechanical or other potential safety hazards Always refer to the safety warnings provided throughout this manua...

Страница 22: ...sten with sheet metal screws Install the flue terminal on the 5 inch pipe and fasten in place see Figure 14 p 22 Step 4 Connect the flue pipe and the combustion air pipe from the concentric adapter to...

Страница 23: ...e terminal on the 5 inch pipe and fasten in place Seal the joint between the 5 inch pipe and the inlet air cap with silicone sealant to prevent the entry of water see Figure 16 p 23 Step 4 Connect the...

Страница 24: ...34H or T834N thermostats Also refer to Figure 17 p 24 for other wiring connections Thermostat Heat Anticipator Adjustments The initial heat anticipator setpoint should equal the thermostat s current a...

Страница 25: ...is rated at 17 amps Notes The start up fan delay should not exceed 90 seconds from a cold start For all wiring connections refer to the wiring diagram shipped with your unit either affixed to the sid...

Страница 26: ...rom air currents and in accordance with the furnished instructions Initial Lighting 1 Openthe manual gas valve in the gas supply line to the duct furnace Loosen the union in the gas supply line to pur...

Страница 27: ...Gas Valve Honeywell 8B Main Gas Valve White Rodgers 9 Honeywell Ignitor 10 Honeywell Pilot Burner 11 Honeywell Pilot Orifice 12 Honeywell Electrode Sensor Lead 13 Hi Limit Switch Located on Rear Head...

Страница 28: ...t least 15 minutes adjust the primary air flow to the burners Turn the friction locked manually rotated air shutters clockwise to close or counterclockwise to open For correct air adjustment close the...

Страница 29: ...ustment cap Manifold Pressure Adjustment If the manifold pressure requires adjustment remove the cap from the pressure regulator and turn the adjustment screw clockwise to increase the pressure or cou...

Страница 30: ...nless you fully understand the controls Remarks _____________________________________________________________________________________________________ __________________________________________________...

Страница 31: ...p 28 9 Check all gas control valves and pipe connections for leaks 10 Check the operation of the automatic gas valve by lowering the setting of the thermostat stopping the operation of the gas duct f...

Страница 32: ...r required 300 400 units 6 dia flue outlet Increaser required to be supplied by manufacturer Ref No Description 1 Blower Housing Assembly 2 Speed Nut 3 Motor 4 Washer Plain 5 Plate Adapter 6 Blower Wh...

Страница 33: ...emove nut Item 5 that secures the Motor Support Shipping Bracket Item 6 to the Mounting Adapter Plate Pull this bracket away from the Motor Mounting Adapter Plate Remove three phillips head screws Ite...

Страница 34: ...Parts Please send the following information to your local Parts center If further assistance is needed contact the manufacturer s customer service department Model number Serial Number Part descriptio...

Страница 35: ...place Refer to Operation p 26 B Flame pops back 1 Excessive primary air 1 Close air shutter Refer to Operation p 26 2 Burner orifice too small 2 Check with local gas supplier for proper orifice size a...

Страница 36: ...9 Check and tighten all wiring connections per diagrams 10 Defective ignition control 10 Replace if necessary Also see U V and W symptoms I Condensation of water vapor 1 Condensation of water vapor 1...

Страница 37: ...elay 3 Motor protector cycling on and off 3 Check motor amps against motor name plate rating check voltage replace venter relay motor if defective 4 Motor not properly oiled 4 Refer to label on motor...

Страница 38: ...use match to test presence of gas is easily detected by the odor 4 Check pilot line for kinks Ensure there are no drafts W Pilot lights Main valve does not energize 1 Loose S8600 connections 1 Check...

Страница 39: ...GMND SVX01B EN 39 Wiring Diagrams Figure 22 Standard wiring diagram for unit with S8600 ignition system...

Страница 40: ...Wiring Diagrams 40 GMND SVX01B EN Figure 23 Standard wiring diagram for unit with G770 ignition system...

Страница 41: ...ontrols and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the right...

Отзывы: