PKG-PRC007-EN
38
Electrical
Data
Table ED-2 — Genius – Electrical Features - SRVE/SIVE 050
Nominal Operation Values
Compressor
Fan Motor
Fan Motor
Consumption
Current
Fan
Voltage
KW
CNO
KW
CNO
KW
CNO
KW
A
220V
18.60
4.14
7.32
30.06
STD
380V
6.39
10.77
1.22
2.39
2.23
4.23
9.84
17.39
440V
9.30
2.07
3.65
15.02
220V
18.60
5.53
7.32
31.45
Option 1
380V
6.39
10.77
1.64
3.19
2.23
4.23
10.26
18.19
440V
9.30
2.76
3.65
15.71
220V
18.60
7.32
7.32
33.24
Option 2
380V
6.39
10.77
2.23
4.23
2.23
4.23
10.85
19.23
440V
9.30
3.66
3.65
16.61
Plenum Box
220V
18.60
7.32
7.32
33.24
Option
380V
6.39
10.77
0.45
1.04
2.23
4.23
9.07
16.04
440V
9.30
0.90
3.65
13.85
Maximum Operation Values
Compressor
Fan Motor
Fan Motor
Current
Fan
Voltage
CMO
CMO
CMO
A
220V
24.98
5.18
9.15
39.32
STD
380V
14.46
2.99
5.28
22.73
440V
12.49
2.59
4.58
19.66
220V
24.98
6.91
9.15
41.04
Option 1
380V
14.46
3.99
5.28
23.73
440V
12.49
3.46
4.58
20.52
220V
24.98
9.15
9.15
43.28
Option 2
380V
14.46
5.28
5.28
25.02
440V
12.49
4.58
4.58
21.64
Plenum Box
220V
24.98
2.25
9.15
36.38
Option
380V
14.46
1.30
5.28
21.04
440V
12.49
1.13
4.58
18.19
Start-up Values
Compressor
Fan Motor
Fan Motor
Fan
Voltage
LRA
LRA
LRA
220V
171.00
30.92
60.45
STD
380V
99.00
17.85
34.90
440V
85.50
15.46
30.23
220V
171.00
48.36
60.45
Option 1
380V
99.00
27.92
34.90
440V
85.50
24.18
30.23
220V
171.00
60.45
60.45
Option 2
380V
99.00
34.90
34.90
440V
85.50
30.23
30.23
Plenum Box
220V
171.00
11.25
60.45
Option
380V
99.00
6.50
34.90
440V
85.50
5.63
30.23
•
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
CMO = Maximum operation current.
•
LRA = Locked rotor amps.
•
STD Option - evaporator fan motor -1.5 CV.
•
Option 1 - evaporator fan motor -2 CV.
•
Option 2 - evaporator fan motor -3 CV.
•
Plenum box option - evaporator fan motor -0.5 CV.
•
Power of the condenser fan motor -3 CV.
•
Size the electrical wiring using the maximum operation currents.