Table PD-6 — Gross Cooling Capacities SAVE-050
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
16.0
19.5
23.0
16.0
19.5
23.0
DB
m3/h
(°C)
TGC
SHC
l/s
TGC
SHC
l/s
TGC
SHC
l/s
TGC
SHC
l/s
TGC
SHC
l/s
TGC
SHC
l/s
24
16.1
13.2
0.81
18.0
10.3
0.92
20.1
7.3
1.00
15.7
13.0
0.81
17.6
10.1
0.92
19.6
7.1
1.00
3060
27
16.2
15.6
0.81
18.0
12.7
0.92
20.1
9.7
1.00
15.7
15.3
0.81
17.6
12.5
0.92
19.6
9.5
1.00
29
16.6
16.9
0.83
18.0
14.7
0.92
20.1
11.7
1.00
16.2
16.6
0.83
17.5
14.5
0.89
19.6
11.5
1.00
32
17.4
17.7
0.89
18.0
16.6
0.92
20.1
13.6
1.00
17.0
17.3
0.89
17.6
16.4
0.92
19.6
13.4
1.00
24
16.3
13.7
0.83
18.3
10.6
0.92
20.3
7.4
1.00
15.8
13.4
0.83
17.8
10.3
0.92
19.8
7.2
1.00
3315
27
16.4
16.1
0.83
18.3
13.1
0.92
20.3
9.9
1.00
16.0
15.8
0.83
17.7
12.8
0.92
19.8
9.7
1.00
29
17.0
17.3
0.86
18.2
15.2
0.92
20.3
12.0
1.00
16.6
16.9
0.86
17.7
15.0
0.92
19.8
11.8
1.00
32
17.8
18.1
0.89
18.6
17.2
0.92
20.3
14.1
1.00
17.4
17.8
0.89
17.8
17.0
0.92
19.8
13.9
1.00
24
16.5
14.1
0.83
18.4
10.8
0.92
20.6
7.4
1.03
16.0
13.9
0.83
18.0
10.6
0.92
20.0
7.3
1.03
3570
27
16.7
16.6
0.86
18.4
13.5
0.92
20.5
10.1
1.03
16.2
16.3
0.83
18.0
13.3
0.92
20.0
9.9
1.00
29
17.3
17.7
0.89
18.4
15.7
0.92
20.5
12.3
1.03
17.0
17.3
0.89
17.9
15.5
0.92
20.0
12.2
1.00
32
18.1
18.5
0.92
18.5
17.8
0.92
20.5
14.6
1.03
17.8
18.1
0.92
18.0
17.6
0.92
20.0
14.4
1.00
24
16.7
14.5
0.86
18.6
11.0
0.94
20.7
7.5
1.03
16.2
14.3
0.83
18.1
10.8
0.92
20.2
7.3
1.03
3825
27
16.9
17.0
0.86
18.6
13.8
0.94
20.7
10.3
1.03
16.5
16.7
0.86
18.1
13.6
0.92
20.2
10.1
1.03
29
17.7
18.0
0.89
18.6
16.2
0.94
20.7
12.6
1.03
17.3
17.6
0.89
18.1
16.0
0.92
20.2
12.5
1.03
32
18.5
18.9
0.92
18.7
18.3
0.94
20.7
15.0
1.03
18.1
18.5
0.92
18.3
18.1
0.94
20.2
14.8
1.03
Table PD-6 — Gross Cooling Capacities SAVE-050 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
Ent.
16.0
19.5
23.0
DB
m3/h
(°C)
TGC
SHC
l/s
TGC
SHC
l/s
TGC
SHC
l/s
24
15.2
12.8
0.81
17.1
9.9
0.89
19.1
6.9
1.00
3060
27
15.3
15.1
0.81
17.1
12.3
0.89
19.1
9.3
1.00
29
15.9
16.2
0.86
17.1
14.2
0.89
19.1
11.3
1.00
32
16.6
17.0
0.89
17.1
16.2
0.89
19.0
13.3
1.00
24
15.4
13.2
0.83
17.3
10.1
0.92
19.3
7.0
1.00
3315
27
15.5
15.6
0.83
17.3
12.7
0.92
19.3
9.5
1.00
29
16.2
16.6
0.86
17.3
14.8
0.92
19.3
11.6
1.00
32
17.0
17.4
0.89
17.3
16.8
0.92
19.3
13.7
1.00
24
15.6
13.7
0.83
17.5
10.4
0.92
19.5
7.1
1.00
3570
27
15.8
16.0
0.86
17.4
13.0
0.92
19.5
9.8
1.00
29
16.6
16.9
0.89
17.4
15.3
0.92
19.5
12.0
1.00
32
17.4
17.7
0.92
17.6
17.3
0.92
19.5
14.2
1.00
24
15.7
14.1
0.83
17.6
10.6
0.92
19.7
7.1
1.03
3825
27
16.1
16.4
0.86
17.6
13.4
0.92
19.6
9.9
1.03
29
16.9
17.2
0.89
17.6
15.8
0.92
19.6
12.3
1.03
32
17.7
18.0
0.94
17.8
17.8
0.94
19.6
14.6
1.03
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
Total Cap.
Sens. Cap.
(°C)
l/s
kW
kW
2.5
2.21
1.01
1.01
4.0
1.39
1.01
1.01
5.5
1.00
1.00
1.00
7.0
0.79
0.99
1.00
8.5
0.66
0.99
1.00
10.0
0.56
0.98
0.99