ACC-SVN264B-EN

General Information - FIAECON103*

This section covers installation of low leak economizers for 
12.5 to 25 ton downflow units in the D cabinet (digit 39 = D).

Inspection 

1. Unpack all components of the kit.
2. Check carefully for shipping damage. If any damage is 

found, report it immediately, and file a claim against the 
transportation company.

3. Visually inspect the components for shipping damage as 

soon as possible after delivery, before it is stored. 
Concealed damage must be reported within 15 days.

4. If concealed damage is discovered, stop unpacking the 

shipment.

5. Do not remove damaged material from the receiving 

location. Take photos of the damage, if possible. The 
owner must provide reasonable evidence that the damage 
did not occur after delivery.

6. Notify the carrier’s terminal of damage immediately by 

phone and by mail. Request an immediate joint inspection 
of the damage by the carrier and the consignee.

Note:

Do not attempt to repair any damaged parts until the 
parts are inspected by the carrier’s representative.

Parts List

NOTICE

Corrosion Damage!

Failure to use recommended caulking/sealant could 

cause corrosion related failures to refrigerant 

components.

1

2

3

4

5

6

8

7

Carton A

Carton B

9

10

11

12

13

Outside Air Damper

Figure 10. Low leak economizer (12.5 to 25 tons - downflow)

Содержание FIAECON102 Series

Страница 1: ...WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires...

Страница 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Страница 3: ...lways follow local regulations Introduction ACC SVN264B EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without w...

Страница 4: ...7 Economizer Wiring 8 Minimum Position Setting for One Speed Indoor Fan 8 Minimum Position Setting 8 Dry Bulb Settings 8 General Information FIAECON103 9 Inspection 9 Parts List 9 Installation FIAECO...

Страница 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Страница 6: ...filler panel 3 Between top of filler panel and unit only if filler panel is required 4 Top of hood triangle seal between hood and hood flange 5 Around barometric relief hood seal between barometric re...

Страница 7: ...emove the slack in wire harness 7 Attach powered exhaust with self drilling screws See Figure 6 8 Verify wire harness is clear of gears doors and any sharp edges of metal 9 Hook up electrical as descr...

Страница 8: ...to Service Test step Ventilation Low Fan Speed 3 Navigate to the Settings Fresh ReturnAir menu Set the Design Minimum OADamper Position at Min Fan Capacity to the desired value 4 Wait at least 30 seco...

Страница 9: ...unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur afte...

Страница 10: ...ter 1 9 Hardware bag 52 Type AB sheet metal screws with sealing washer 10 16 x 5 8 in Identification label Installation instructions 1 Field only parts Carton B a a These parts are already installed i...

Страница 11: ...rear fresh air access panels from the unit and set them aside Figure 11 Panel removal Unit Access Panel Front Do Not Remove If Hinged Unit Access Panel Rear Unit End Panel 2 For a factory installed lo...

Страница 12: ...he left side of the outdoor air damper assembly as shown in Figure 17 Figure 17 Outside air block off panel installation Outside Air Block off Outdoor Air Damper Assembly 8 Secure outdoor air damper a...

Страница 13: ...brackets should be installed on the flat side of the hood panel with the flanges facing away from the panel 13 Attach the triangle hood panels on the left and right side of the damper assembly Use fiv...

Страница 14: ...anels on the front and back of the unit Figure 24 Back panel and barometric relief parts Horizontal Return Block off Panel Barometric Relief Assembly Note The back panel will be replaced with the baro...

Страница 15: ...e carrier and the consignee Note Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative Parts List NOTICE Corrosion Damage Failure to use recommended...

Страница 16: ...ontaining ship with parts from the outdoor air damper assembly Refer to Figure 27 for the following assembly process 3 Installthehorizontalductconversionkitpertheinstructions included with that kit 4...

Страница 17: ...facing away from the panel 10 Attach the triangle hood panels on the left and right side of the damper assembly Use five screws for each hood panel The hood panels have pre installed gasket between t...

Страница 18: ...nd panel reinstallation Unit End Panel Diverter Panel Identification Label 16 Install the access panel on the front of the unit 17 Using field supplied silicone sealant seal all seams cracks and gaps...

Страница 19: ...s and route the controls harness from the sensor to the fresh air options module located in the return enclosure using the factory installed wire ties Connect the harness J9 connector to the fresh air...

Страница 20: ...ations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residen...

Отзывы: