Figure 19. Actuator harness routing

Route Acutator 

Controls Harness

Thru Pop-In Wire Ties

Fresh Air Options Module

Return Enclosure

Actuator Controls Harness

Route Actuator Controls Harness

Thru Pop-In Wire Ties

Return Enclosure

Actuator Controls

Harness

Installation - FIAECON103*

ACC-SVN264B-EN

13 

For factory installed, start with below steps

:

10. To allow for the barometric relief option installation, remove 

the return air rear block-off. Install the barometric relief 
option per the installation instructions (ACC-SVN156*-
EN).

Figure 20. Return air rear block-off removal

Return Air Rear Block-off

Note:

For 

Step 11

 to 

Step 16

, refer to 

Figure 21

11. Attach the rear filter angle bracket to the unit with four 

screws along the bottom of the damper assembly. The 
surface between the two parts has gasket pre-installed on 
the bracket. 

12. Attach the filter side angle brackets to both triangle hood 

panels using two screws each. The brackets should be 
installed on the flat side of the hood panel with the flanges 
facing away from the panel. 

13. Attach the triangle hood panels on the left and right side of 

the damper assembly. Use five screws for each hood 
panel. The hood panels have pre-installed gasket between 
the hood panels and the damper assembly. The flanges of 
the panels are to the outside of the unit. 

14. Install the hood front support bracket with two screws on 

each side onto the triangle hood panels. The hood front 
support bracket has pre-installed gasket that will face away 
from the unit. 

15. Attach the filter top support bracket in the middle of the 

bottom of each triangle hood panels with two screws on 
each side panel so the flat surface is facing down. 

16. Slide the filter into the filter frame that was just created in 

Step 11

 

Step 15

.

Figure 21. Hood assembly

8

5

3

6

4

1

2

17. On the back panel removed and set aside in 

Step 1

, attach 

the economizer diverter panel to the bottom of the back 
panel with four screws. The diverter panel will be on the 
outside surface with gasket pre-installed along the 
interface surface with the back panel.

Содержание FIAECON102 Series

Страница 1: ...WARNING Only qualified personnel should install and service the equipment The installation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires...

Страница 2: ...at is used in these service procedures In addition some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants Know the appli...

Страница 3: ...lways follow local regulations Introduction ACC SVN264B EN 3 Copyright This document and the information in it are the property of Trane and may not be used or reproduced in whole or in part without w...

Страница 4: ...7 Economizer Wiring 8 Minimum Position Setting for One Speed Indoor Fan 8 Minimum Position Setting 8 Dry Bulb Settings 8 General Information FIAECON103 9 Inspection 9 Parts List 9 Installation FIAECO...

Страница 5: ...provide reasonable evidence that the damage did not occur after delivery 6 Notify the carrier s terminal of damage immediately by phone and by mail Request an immediate joint inspection of the damage...

Страница 6: ...filler panel 3 Between top of filler panel and unit only if filler panel is required 4 Top of hood triangle seal between hood and hood flange 5 Around barometric relief hood seal between barometric re...

Страница 7: ...emove the slack in wire harness 7 Attach powered exhaust with self drilling screws See Figure 6 8 Verify wire harness is clear of gears doors and any sharp edges of metal 9 Hook up electrical as descr...

Страница 8: ...to Service Test step Ventilation Low Fan Speed 3 Navigate to the Settings Fresh ReturnAir menu Set the Design Minimum OADamper Position at Min Fan Capacity to the desired value 4 Wait at least 30 seco...

Страница 9: ...unpacking the shipment 5 Do not remove damaged material from the receiving location Take photos of the damage if possible The owner must provide reasonable evidence that the damage did not occur afte...

Страница 10: ...ter 1 9 Hardware bag 52 Type AB sheet metal screws with sealing washer 10 16 x 5 8 in Identification label Installation instructions 1 Field only parts Carton B a a These parts are already installed i...

Страница 11: ...rear fresh air access panels from the unit and set them aside Figure 11 Panel removal Unit Access Panel Front Do Not Remove If Hinged Unit Access Panel Rear Unit End Panel 2 For a factory installed lo...

Страница 12: ...he left side of the outdoor air damper assembly as shown in Figure 17 Figure 17 Outside air block off panel installation Outside Air Block off Outdoor Air Damper Assembly 8 Secure outdoor air damper a...

Страница 13: ...brackets should be installed on the flat side of the hood panel with the flanges facing away from the panel 13 Attach the triangle hood panels on the left and right side of the damper assembly Use fiv...

Страница 14: ...anels on the front and back of the unit Figure 24 Back panel and barometric relief parts Horizontal Return Block off Panel Barometric Relief Assembly Note The back panel will be replaced with the baro...

Страница 15: ...e carrier and the consignee Note Do not attempt to repair any damaged parts until the parts are inspected by the carrier s representative Parts List NOTICE Corrosion Damage Failure to use recommended...

Страница 16: ...ontaining ship with parts from the outdoor air damper assembly Refer to Figure 27 for the following assembly process 3 Installthehorizontalductconversionkitpertheinstructions included with that kit 4...

Страница 17: ...facing away from the panel 10 Attach the triangle hood panels on the left and right side of the damper assembly Use five screws for each hood panel The hood panels have pre installed gasket between t...

Страница 18: ...nd panel reinstallation Unit End Panel Diverter Panel Identification Label 16 Install the access panel on the front of the unit 17 Using field supplied silicone sealant seal all seams cracks and gaps...

Страница 19: ...s and route the controls harness from the sensor to the fresh air options module located in the return enclosure using the factory installed wire ties Connect the harness J9 connector to the fresh air...

Страница 20: ...ations without notice We are committed to using environmentally conscious print practices Trane and American Standard create comfortable energy efficient indoor environments for commercial and residen...

Отзывы: