RLC-SVX19E-GB
47
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Dimensional Data
The dimensional data below are given for reference only. Dimensions details, dimensions of hydraulic connections,
electrical connections, isolator positioning, specific features for heat recovery and free cooling are included in
submittals and diagrams provided in documentation package.
Figure 5
–
Units RTAF 090 to 205 SE HE XE
Operating weight (kg)
090
105
125
145
155
175
190
205
SN LN unit
SE
3295
3330
3510
3970
4240
4400
4820
4845
HE_XE
3595
3630
3810
4220
4485
4640
5075
5210
Hydraulic module DPSP
SE
3645
3690
3910
4410
4780
4945
5365
5390
HE_XE
3975
4020
4240
4660
5025
5180
5615
5750
Hydraulic module DPHP
SE
3730
3760
3955
4575
4840
4995
5420
5445
HE_XE
4055
4090
4285
4820
5090
5240
5680
5810
XLN unit
SE
+80
+80
+80
+100
+100
+100
+120
+120
XE
+100
+100
+100
+120
+120
+120
+140
+140
Hydraulic module VPF
SE-HE-XE
+70
DPSP: Dual Pump Standard Pressure
DPHP: Dual Pump High Pressure
Important! Additional space is required to remove evaporator tubes.
For RTAF 090 to 245: 2.5 m in front of the unit (evaporator side).