RLC-SVX19E-GB
67
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Heat recovery option is made with a plate heat exchanger in series with the air-cooled condenser. This heat
exchanger benefits the discharge gas superheat as well as a part of the condensing gas heat to be transferred to hot
water system.
All Submittals, lifting diagrams, neoprene pads positioning and wiring diagrams have been supplied with the chiller
order.
PHR General data
PHR
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
090
105
125
145
155
175
190
205
245 (2)
Heating capacity (1)
Gross heating Capacity (1)
(kW)
82
94
110
131
141
154
169
183
220
Condenser
Type
Stainless steel Copper Brazed plate Heat exchanger
Circuit 1 BPHE
B3-095
28pl
B3-095
28pl
B3-095
28pl
B3-095
28pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
Circuit 2 BPHE
B3-095
28pl
B3-095
28pl
B3-095
28pl
B3-095
28pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
B3-095
40pl
Nominal water connection
size (Grooved coupling)
(in) -
(mm) 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm 2’’ - 50mm
Water content volume
(l)
10.0
10.0
10.0
10.0
12.0
12.0
12.0
12.0
12.0
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
250
280
310
350
380
410
415
450 (2)
Heating capacity (1)
Gross heating Capacity (1)
(kW)
215
244
269
300
332
363
363
398
Condenser - Water Cooled (PHR)
Type
Stainless steel Copper Brazed Plates Heat Exchanger
Circuit 1 BPHE
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
Circuit 2 BPHE
B3-095
40pl
B3-095
40pl
B3-095
40pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
B3-095
70pl
Nominal water connection
size (Grooved coupling)
(in) -
(mm) 2” - 50mm 2” - 50mm 2” - 50mm 2” - 50mm 2” - 50mm 2” - 50mm 2” - 50mm 2” - 50mm
Water content volume
(l)
30
30
30
35
35
35
35
35
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - Condenser water temperature 40°C/45°C .
For accurate value refer to OWU
(2) Variable speed compressor only
Figure 23 – Water pressure drop - heat recovery heat exchanger
1.00
10.00
100.00
1
10
Pre
ss
ure
d
ro
p (
kP
a)
Water flow (L/s)
1 = RTAF 90/105/125/145
2 = RTAF 155/175/190/205/245
3 = RTAF 250/280/310
4 = RTAF 350/380/410/415/450
1
2
3
4
Partial Heat Recovery