background image

18-CD19D7-22

9

Installer’s Guide

*

SEE OUTLINE DRAWING

w

LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT

*

*

*

*

CUT OUT

FOR

SIDE

FILTER

FRONT

of Furnace

3. The side panels on upflow furnaces include locating

notches which may be used as guides for cutting an
opening for return air.  Refer to Figure 12 and the
outline drawing on page 4 for duct connection dimen-
sions for various furnaces.

4. If a 3/4" flange is to be used for attaching the air inlet

duct, add to cut where indicated by dashed lines in
Figure 12. Cut corners diagonally and bend outward to
form flange.

5. If flanges are not required, and a filter frame is in-

stalled, cut along knockout guidelines.

6.

Upflow Furnaces:

  Use the optional filter rack on

either side or on the bottom if the filter is to be used
within the furnace cabinet.

When the upflow furnace is installed in the horizontal
right or left application and a return duct is attached to
the top side as shown in Figure 11,  install the filter in a
remote location.

WARNING

!

TO PREVENT INJURY OR DEATH DUE TO CONTACT 
WITH MOVING PARTS, TURN THE POWER TO THE 
FURNACE OFF BEFORE SERVICING FILTERS.

Do not install the filter in the return duct directly above
the furnace in horizontal applications.

When the upflow furnace is installed in the horizontal
right or left application and a close coupled (less than
36") return duct is attached to the bottom side of the
furnace as shown in Figure 11, securely attach a 1/2"
mesh metal hardware cloth protective screen to the
inside bottom of the filter grill 

to prevent personal

injury from contacting moving parts when reach-
ing into the return opening to replace the filter.

Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to
noise considerations.

Downflow Furnaces: 

 Brackets are factory supplied to

mount filters in the return air duct work.

7. Connect the duct work to the furnace.  See Outline

Drawing (pages 4&5) for supply and return duct size and
location.  Flexible duct connectors are recommended to
connect both supply and return air ducts to the furnace.
If only the front of the furnace is accessible, it is
recommended that both supply and return air ple-
nums are removable.

8. When replacing a furnace, old duct work should be

cleaned out.  Thin cloths should be placed over the
registers and the furnace fan should be run for 10 min-
utes.  Don’t forget to remove the cloths before you start
the furnace.

RETURN AIR FILTERS
(FILTER AND FILTER RACK ARE NOT

SUPPLIED WITH UNIT)

TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS

These furnaces require high velocity type air filters.  The
optional filters may be located within the furnace blower
compartment for UPFLOW furnaces in either a BOTTOM or
SIDE (left side or right side) return air inlet.  Some optional
filters may need to be trimmed for side or bottom filter use.

NOTE:

On upflow 5 or 6 ton airflow models where the airflow
requirement exceeds 1800 CFM - Models will require
return air openings and  filters on:  (1) both sides; or (2)
one side and the bottom; or (3) just the bottom.

WARNING

!

Do not install the filter in the return duct directly above the 
furnace in horizontal applications. Install the filter remotely. 
Installing the filter directly above the furnace in horizontal 
applications may cause property damage, serious injury or 
death.

FILTER

REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.

Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.

q

The furnace and the blower filter rack installation can be seen
in Figure 13.

The optional furnace filter in the bottom or side configuration
can be removed by simply turning the two latches on the
blower door and tilting the door forward.

The filter rails are spring loaded for automatic adjustment to
allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width
needed for bottom or side return.

Содержание DD1A040A9241A Series

Страница 1: ...rotation ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service informati...

Страница 2: ...g ignition input rate temperature rise and venting according to the manufacturer s instructions 10 This product must be piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts S...

Страница 3: ...drops or ducts with equivalent lengths and sizes See Field Wiring Diagrams for Twinning on page 16 for proper hookup CAUTION To prevent shortening its service life the furnace should not be used as a...

Страница 4: ...4 18 CD19D7 22 Installer s Guide From Dwg 21C341699 Rev 7 UD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 5: ...18 CD19D7 22 5 Installer s Guide From Dwg 21C341700 Sh 1 Rev 3 DD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 6: ...234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 1234567890123456789012345678901212345...

Страница 7: ...FURNACE SHOWN Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equipment installed Air for combustion and ventilation requirements can be supplied fro...

Страница 8: ...he furnace is located in a utility room adjacent to the living area the system should be carefully designed with returns which minimize noise transmission through the return air grille Although these...

Страница 9: ...n Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace If only the front of the furnace is accessible it is recommended that both supply and return air p...

Страница 10: ...inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the furnace cabinet side See Figures 13 14 16 NOTE Remove the bottom front...

Страница 11: ...e side of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 15...

Страница 12: ...1 2 DO NOT CUT CUT ON LINE Airflow Airflow d TABLE 7 CABINET WIDTH FILTER SIZE FILTER BRACKET LOCATION 14 1 2 2 14X20X1 12 7 8 17 1 2 2 16X20X1 14 3 8 21 2 16X20X1 13 1 8 24 1 2 2 16X20X1 11 5 8 Locat...

Страница 13: ...ercent NOTE If desired a side wall termination can be accom plished through the use of an add on draft inducer The inducer must be installed according to the inducer manufacturer s instructions Set th...

Страница 14: ...before servicing the unit Failure to follow this warning could result in electrical shock personal injury or death D 2 4 X 7 g GAS VENT TERMINATION ROOF PITCH MINIMUM HEIGHT FLAT TO 7 12 OVER 7 12 TO...

Страница 15: ...m As with all gas appliances using electrical power this furnace shall be connected into a permanently live electric circuit It is recommended that it be provided with a separate circuit protection de...

Страница 16: ...3 Rev 2 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEATING ONLY THERMOSTAT 1 STAGE HEAT ONLY THERMOSTAT WITH FAN SWITCH FURNACE...

Страница 17: ...he gas valve for propane is 13 8 W C Mini mum pressure is 11 0 W C All gas fittings must be checked for leaks using a soapy solution before lighting the furnace DO NOT CHECK WITH AN OPEN FLAME The fol...

Страница 18: ...em 2 Attach a manifold pressure gauge with flexible tubing to the outlet pressure boss marked OUT P on White Rodgers gas valve model 36G or 36J See Figure 28 for White Rodgers gas valve model 36J See...

Страница 19: ...if orifice change is required Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may req...

Страница 20: ...ty of the unit it must be checked out on initial start up by the installer To check for proper operation of the limit switches set the thermostat to a temperature higher than the indicated temperature...

Страница 21: ...ignition is not achieved it will lockout the furnace 3 POWER FAILURE If there is a power failure during a heating cycle the system will restart the ignition sequence automatically when power is resto...

Страница 22: ...22 18 CD19D7 22 Installer s Guide NOTES...

Страница 23: ...18 CD19D7 22 23 Installer s Guide NOTES...

Страница 24: ...distributor P I 08 02 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Literature Order N...

Отзывы: