background image

18-CD19D7-22

7

Installer’s Guide

Line contact is only permissible between lines formed by
the intersection of the top and two sides of the furnace
casing and the building joists, studs, or framing.

A cutout is provided on both sides of the downflow furnace
cabinet to allow a 90° elbow to be attached inside the cabinet
and the vent piping to connect there.  In horizontal, the
downflow furnace may be vented through the top of the
cabinet if needed. In vertical configuration, the downflow
furnace may be vented using the side cabinet cutouts.  This
venting configuration could be used if an electronic air
cleaner is installed.

When the downflow furnace is vented through the left
side of the furnace cabinet in horizontal or vertical
configuration, Type B vent pipe must be used within the
cabinet.

AIR FOR COMBUSTION AND VENTILATION

Adequate flow of combustion and ventilating air must not be
obstructed from reaching the furnace.  Air openings provided
in the furnace casing must be kept free of obstructions which
restrict the flow of air.  Airflow restrictions affect the effi-
ciency and safe operation of the furnace.  Keep this in mind
should you choose to remodel or change the area which
contains your furnace.  Furnaces must have a free flow of air
for proper performance.

Provisions for combustion and ventilation air shall be made
in accordance with “latest edition” of Section 5.3, Air for
Combustion and Ventilation, of the National Fuel Gas Code,
ANSI Z223.1, or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149
Installation Codes, and applicable provisions of the local
building codes.  Special conditions created by mechanical
exhausting of air and fireplaces must be considered to avoid
unsatisfactory furnace operation.

Furnace locations may be in “confined space” or “unconfined
space”.  Unconfined space is defined in Table 2 and Figure 7.
These spaces may have adequate air by infiltration to
provide air for combustion, ventilation, and dilution of flue
gases.  Buildings with tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier,
etc.), may need additional air provided as described for
confined space.

6

TYPICAL SUSPENDED INSTALLATION

(UPFLOW/HORIZONTAL FURNACE SHOWN)

Confined spaces are installations with less than 50 cu. ft. of
space per 1000 BTU/hr input from all equipment installed.
Air for combustion and ventilation requirements can be
supplied from inside the building as in Figure 9 (page 8), or
from the outdoors, as in Figure 10 (page 8).

1. All air from inside the building as in Figure 9 (page 8):

The confined space shall be provided with two perma-
nent openings communicating directly with an addi-
tional room(s) of sufficient volume so that the combined
volume of all spaces meets the criteria for an unconfined
space. The total input of all gas utilization equipment
installed in the combined space shall be considered in
making this determination.  Refer to Table 3 (page 8), for
minimum open areas required.

2. All air from outdoors as in Figure 10 (page 8): The

confined space shall be provided with two permanent
openings, one commencing within 12 inches of the top
and one commencing within 12 inches of the bottom of
the enclosure.  The openings shall communicate directly,
or by ducts, with the outdoors or spaces (crawl or attic)
that freely communicate with the outdoors.  Refer to
Table 3 (page 8), for minimum open areas required.

3. The following types of installations will 

require

 use of

OUTDOOR AIR for combustion, due to chemical
exposures:

* Commercial buildings
* Buildings with indoor pools
* Furnaces installed in commercial laundry rooms
* Furnaces installed in hobby or craft rooms
* Furnaces installed near chemical storage areas

Exposure to the following substances in the combustion
air supply will also require OUTDOOR AIR for
combustion:

* Permanent wave solutions
* Chlorinated waxes and cleaners
* Chlorine based swimming pool chemicals
* Water softening chemicals
* Deicing salts or chemicals
* Carbon Tetrachloride
* Halogen type refrigerants
* Cleaning solvents (such as perchloroethylene)
* Printing inks, paint removers, varnish, etc.
* Hydrochloric acid
* Cements and glues
* Antistatic fabric softeners for clothes dryers
* Masonry acid washing materials

TABLE 2

MINIMUM AREA IN SQUARE FEET FOR

UNCONFINED SPACE INSTALLATIONS

FURNACE MAXIMUM

BTUH / INPUT RATING

WITH 8 FOOT CEILING

MINIMUM AREA IN SQUARE FEET

OF UNCONFINED SPACE

40,000
60,000
80,000

100,000
120,000
140,000

250
375
500
625
750
875

50 CU. FT. OR MORE
PER 1000 BTU/HR. INPUT
ALL EQUIP. INSTALLED

UNCONFINED

7

CONFINED

LESS THAN 50 CU. FT.
PER 1000 BTU/HR. INPUT
ALL EQUIP INSTALLED

8

Содержание DD1A040A9241A Series

Страница 1: ...rotation ALL phases of this installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service informati...

Страница 2: ...g ignition input rate temperature rise and venting according to the manufacturer s instructions 10 This product must be piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts S...

Страница 3: ...drops or ducts with equivalent lengths and sizes See Field Wiring Diagrams for Twinning on page 16 for proper hookup CAUTION To prevent shortening its service life the furnace should not be used as a...

Страница 4: ...4 18 CD19D7 22 Installer s Guide From Dwg 21C341699 Rev 7 UD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 5: ...18 CD19D7 22 5 Installer s Guide From Dwg 21C341700 Sh 1 Rev 3 DD A 1A OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 6: ...234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 123456789012345678901234567890121234567890123456 1234567890123456789012345678901212345...

Страница 7: ...FURNACE SHOWN Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equipment installed Air for combustion and ventilation requirements can be supplied fro...

Страница 8: ...he furnace is located in a utility room adjacent to the living area the system should be carefully designed with returns which minimize noise transmission through the return air grille Although these...

Страница 9: ...n Flexible duct connectors are recommended to connect both supply and return air ducts to the furnace If only the front of the furnace is accessible it is recommended that both supply and return air p...

Страница 10: ...inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the furnace cabinet side See Figures 13 14 16 NOTE Remove the bottom front...

Страница 11: ...e side of the furnace Confirm that the upper retaining pin screw locks into the engagement hole in the blower deck and the lower pin screw rests against the side of the bottom panel See Figures 14 15...

Страница 12: ...1 2 DO NOT CUT CUT ON LINE Airflow Airflow d TABLE 7 CABINET WIDTH FILTER SIZE FILTER BRACKET LOCATION 14 1 2 2 14X20X1 12 7 8 17 1 2 2 16X20X1 14 3 8 21 2 16X20X1 13 1 8 24 1 2 2 16X20X1 11 5 8 Locat...

Страница 13: ...ercent NOTE If desired a side wall termination can be accom plished through the use of an add on draft inducer The inducer must be installed according to the inducer manufacturer s instructions Set th...

Страница 14: ...before servicing the unit Failure to follow this warning could result in electrical shock personal injury or death D 2 4 X 7 g GAS VENT TERMINATION ROOF PITCH MINIMUM HEIGHT FLAT TO 7 12 OVER 7 12 TO...

Страница 15: ...m As with all gas appliances using electrical power this furnace shall be connected into a permanently live electric circuit It is recommended that it be provided with a separate circuit protection de...

Страница 16: ...3 Rev 2 TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEATING ONLY THERMOSTAT 1 STAGE HEAT ONLY THERMOSTAT WITH FAN SWITCH FURNACE...

Страница 17: ...he gas valve for propane is 13 8 W C Mini mum pressure is 11 0 W C All gas fittings must be checked for leaks using a soapy solution before lighting the furnace DO NOT CHECK WITH AN OPEN FLAME The fol...

Страница 18: ...em 2 Attach a manifold pressure gauge with flexible tubing to the outlet pressure boss marked OUT P on White Rodgers gas valve model 36G or 36J See Figure 28 for White Rodgers gas valve model 36J See...

Страница 19: ...if orifice change is required Furnace input rate and temperature rise should be checked again after changing orifices to confirm the proper rate for the altitude Installations above 4 000 feet may req...

Страница 20: ...ty of the unit it must be checked out on initial start up by the installer To check for proper operation of the limit switches set the thermostat to a temperature higher than the indicated temperature...

Страница 21: ...ignition is not achieved it will lockout the furnace 3 POWER FAILURE If there is a power failure during a heating cycle the system will restart the ignition sequence automatically when power is resto...

Страница 22: ...22 18 CD19D7 22 Installer s Guide NOTES...

Страница 23: ...18 CD19D7 22 23 Installer s Guide NOTES...

Страница 24: ...distributor P I 08 02 Since the manufacturer has a policy of continuous product and product data improvement it reserves the right to change design and specifications without notice Literature Order N...

Отзывы: